TDK-Lambda DPP240-24-1 Industrial Switching Power Supply

Posicionamento do produto: DPP Series Single-phase AC-DC DIN Rail Mount Industrial Switching Power Supply (NRND, Not Recommended for New Design) NRND = Not Recommended for New Design. The manufacturer recommended replacement model is DRB240-24-1. (Observação: Atribuição de pinos, mounting and function compatibility are not fully guaranteed; engineering verification is required.) ✅ Model Definition DPP: Montagem em trilho DIN ...

  • Detalhes do produto

Posicionamento do produto: DPP Series Single-phase AC-DC DIN Rail Mount Industrial Switching Fonte de energia (NRND, Not Recommended for New Design)

NRND = Not Recommended for New Design. The manufacturer recommended replacement model is DRB240-24-1. (Observação: Atribuição de pinos, mounting and function compatibility are not fully guaranteed; engineering verification is required.)

✅ Model Definition

DPP: DIN rail mounting power supply series

240: Rated power 240W

24: Output voltage DC24V

1: Single-phase AC input (sufixo 3 = 3-phase input, DPP240-24-3)

📌 Core Electrical Specifications

ItemParâmetro
EntradaSingle-phase 90~264VAC; DC 210~370Vdc; 47~63 Hz, automatic wide-range selection
SaídaCC24V, corrente nominal 10A, power 240W; adjustable range: 22.5~28.5Vdc
EficiênciaTípico 89%
Output accuracy±1%
Ondulação & Barulho<100mV (20MHz bandwidth)
ProteçãoProteção contra sobrecorrente (120~145% of rated), proteção contra sobretensão, proteção contra curto-circuito
Parallel OperationSuporta até 3 units in parallel, built-in droop current sharing mode; switch to parallel mode; minimum load ≥10% for parallel operation
DC Good RelayBuilt-in power-good dry contact signal for CLP monitoramento
Temperatura operacional-40℃ ~ +71℃ (derating required at full load, refer to datasheet)

📏 Mechanical Dimensions & Instalação

Trilho DIN (TS35) snap-on mounting, enclosed metal housing, resfriamento por convecção natural (sem ventilador)

Largura: 83 milímetros

Altura: 125 milímetros

Profundidade: 126 milímetros

🧾 Terminal Definition (Terminais de parafuso)

  1. DC Good relay
  2. DC Good relay
  3. V+
  4. V+
  5. V-
  6. V-
  7. PE Protective Earth
  8. L Line
  9. N Neutral

🛠️ Typical Application Scenarios

Industrial automation control cabinets, CLPs, sensores, válvulas solenóides, automação predial, test & measurement equipment, factory 24V DC bus power supply.

⚠️ Key Notes

  1. Status: NRND. Available as spare parts for legacy projects; DRB240-24-1 is recommended for new projects. Dimensões de instalação, layout do terminal, DC-Good signal and parallel function differences must be verified.
  2. Operação paralela: Set identical output voltage for all units and toggle switch to parallel mode; single-unit mode provides better load regulation accuracy.
  3. Dissipação de calor: Keep ventilation clearance on all sides; derating required for high ambient temperature.
  4. Certificações: UL/EN/IEC62368-1, industrial safety certification.

🔧 Troubleshooting

Sem saída: Measure L/N input voltage; check upstream circuit breaker and fuse; verify PE grounding; check green LED indicator on power supply.

Voltage drop under load: Sobrecarga, incorrect parallel switch setting, terminais soltos; verify output current ≤10A.

DC Good inactive: Power supply enters latch-off protection; troubleshoot short circuit / overvoltage on downstream circuit.

Excessive ripple: Verifique o aterramento, add electrolytic / ceramic capacitor on output side, inspect cable shielding.

📎 Domestic Alternatives (DIN rail 240W 24V/10A, same specification)

Phoenix Contact QUINT-PS/1AC/24DC/240, Mean Well SDR-240-24, Delta DRP-240-24

TDK-Lambda DPP240-24-1 Complete Installation Guide

Suitable for TS35/7.5 or TS35/15 standard DIN rail. Never mount upside down (output terminals must not face down). Resfriamento por convecção natural, ventilation clearance required on all sides.

  1. Preparação de pré-instalação

1.1 Ferramentas & Materiais

chave Phillips (for terminal screws)

Chave de torque (recomendado)

Cabos: AWG24~AWG10 (screw terminal version)

Standard TS35 DIN rail inside control cabinet

Upstream circuit breaker/fuse, PE protective earth wire

1.2 Pré-condições de segurança

Perform work in power-off state; confirm upstream power is fully disconnected

Class I equipment. PE protective earth must be reliably connected, otherwise electric shock hazard exists

Inspect power supply for damage and terminal oxidation before installation

  1. DIN Rail Mechanical Installation Steps
  2. Hook the top clip of the power supply onto DIN rail;
  3. Press the power supply body inward until the bottom clip clicks and locks;
  4. Shake slightly to confirm secure fixation on rail;
  5. Remoção: Use flat screwdriver to pry down the bottom spring clip and pull the unit outward.

Heat dissipation requirement: Minimum 25mm ventilation gap on top, fundo, esquerda e direita. Do not mount close to heat-generating components such as contactors and PLCs. Enclosure covering and upside-down mounting are prohibited. (Correct orientation: output terminals upward)

  1. Fiação Terminal (Screw Terminal Version)

Terminal numbering (da esquerda para a direita):

1,2: DC Good relay dry contact (power status passive contact, connect to PLC/alarm circuit)

3,4: V+ DC24V output positive

5,6: VDC24V output negative

7: PE Protective Earth

8: L Line

9: N Neutral

Torque Specification (per manufacturer manual)

Terminais de entrada (L/N/PE): Torque máximo 1.0 N·m

Output terminals (V+ V-, DC Good): Torque máximo 0.65 N·m

Do not over-tighten to avoid screw slipping or terminal base cracking. All conductor strands must be fully inserted into terminals; no exposed copper strands to prevent short circuit.

Sequência de fiação

  1. Connect PE (terminal 7) for reliable earthing first;
  2. Then connect output side: V+, V-, DC Good signal;
  3. Finally connect input side L and N;
  4. Depois da fiação, check for short circuit and poor contact.
  5. DIP Switch Setting (Solteiro / Parallel Mode)

Single/Parallel DIP switch on front panel:

Solteiro (Single Unit): Factory default setting, high load regulation accuracy. Must use this setting for standalone operation.

Paralelo: Até 3 DPP240 units for power expansion. Parallel requirements:

  1. All units set DIP switch to Parallel;
  2. Output cables of all units must have identical wire gauge and length;
  3. System minimum load ≥10% rated current, maximum load ≤90%;
  4. Pre-adjust all power supplies to the same output voltage.

Voltage adjustment: Front panel potentiometer, adjustable range DC22.5~28.5V

  1. Procedimento de comissionamento de inicialização
  2. Em condição de desligamento, use multimeter to confirm no short circuit on input and output loops;
  3. Verify DIP switch position;
  4. Close upstream breaker and power on;
  5. Observe green LED of power supply; measure output voltage to confirm set value;
  6. Check DC Good relay: contacts close when power supply healthy; contacts open during fault / proteção;
  7. Perform loaded test, check temperature rise, confirm no abnormal overheating.
  8. Prohibited Installation Practices (Importante)
  9. ❌ Upside-down mounting (output terminals down), which damages convection cooling and triggers over-temperature protection or permanent damage;
  10. ❌ No 25mm ventilation clearance around unit;
  11. ❌ PE earth connection omitted;
  12. ❌ Parallel operation with cables of unequal length or load less than 10%;
  13. ❌ Improper terminal torque; loose or exposed copper strands;
  14. ❌ Use in high humidity, corrosive and dusty environment without protective enclosure.
  15. Common Installation Issues
  16. No green LED after power-on: Check L/N input voltage, upstream breaker, internal fuse (internal fuse cannot be replaced by user; unit must be returned for repair if damaged)
  17. Voltage drop under load: Terminais soltos, insufficient wire gauge, incorrect parallel switch setting, load exceeds 10A;
  18. Power supply overheating: Insufficient ventilation gap, nearby heat sources, alta temperatura ambiente, desclassificação necessária.

TDK-Lambda DPP240-24-1 Outline Dimensions

Nominal dimensions (DIN rail clip protrusion excluded)

Largura(C): 83 milímetros (3.27 polegada)

Altura(H): 125 milímetros (4.92 polegada)

Profundidade(D): 126 milímetros (4.96 polegada)

Peso: aprox.. 1000g (1kg)

Trilho de montagem: Standard TS35 (7.5 / 15milímetros) Trilho DIN

Cabinet Layout Notes

  1. 83mm width occupies large horizontal space in control cabinet. Compare with alternative DRB240-24-1 (largura aprox.. 41milímetros). DPP series is wider;
  2. Heat dissipation clearance: minimum 25mm on all sides;
  3. Depth 126mm. When designing cabinet depth from backplate to door, extra space for front terminal wiring must be reserved.

Reference Comparison (Alternative Model DRB240-24-1)

DRB240-24-1: 41 × 120 × 125 milímetros, nearly half the width. Large difference in installation space, cannot be directly drop-in replacement.

TDK-Lambda DPP240-24-1 Power Factor

Typical Power Factor PF = 0.7 (230VAC input, carga completa)

This power supply does not integrate active PFC circuit, adopting conventional rectifier topology, resulting in relatively low power factor.

Descrição Complementar

  1. Condição de teste: AC230V, full rated output; PF value decreases under 115VAC low input voltage.
  2. Observação: 0.7 is typical value not minimum; power factor further drops under light load.
  3. System Impact:

If project requires strict harmonic and power factor compliance (por exemplo. EN61000-3-2), add external PFC filter at input front end.

Alternative model DRB240-24-1 of same power level has better PF performance.

  1. Reference input current (carga completa):

230VAC: aprox.. 1.5UM

115VAC: aprox.. 4.0UM