Siemens 6EP1437-2BA10 SITOP POWER 40 Three-Phase Industrial Power Supply
- Detalhamento do código do modelo
6EP1437-2BA10
6EP: Standard industrial power supply series of SITOP
1437: High-power three-phase AC model, 40A output platform
2: Basic standard version (without redundant diagnostic interface)
BA: Montagem em trilho DIN, 24Saída VCC
10: 3-phase 400–500V input, 40UM / 960W output specification
- Parâmetros elétricos principais
Lado de entrada (3-Phase Industrial Grid)
Input format: 3×400~500V AC, 3-phase 5-wire L1/L2/L3/PE
Freqüência: 50/60Hz
Voltage dip tolerance: Minimum 340V for 2 seconds without output collapse
Wire gauge for input terminals: 0.5~4mm² solid/stranded copper wire
Output Side (Standard Industrial 24VDC)
Rated output: 24CCV / 40UM, total power 960W
Adjustable output voltage range: 22.8~26.4V (tweaked via potentiometer at bottom)
Ondulação & barulho: Ripple <150mVpp, peak noise <240mVpp
Output terminals: Dual groups of +/terminals for parallel connection; wire gauge 0.5~10mm²
Parallel expansion: Two identical units can be directly paralleled for max. 80Uma saída
Funções de proteção (Full-condition Protection)
- Proteção contra curto-circuito: Automatic hiccup current limiting, auto-recovery after fault clearance
- Proteção contra sobretensão (OVP): Output cut-off when voltage >27V
- Proteção contra sobrecarga (OLP): Current limiting at 120% corrente nominal
- Over-temperature Protection (OTP): Shutdown on overheat, auto-restart after cooling down
- Protection against input phase loss, surge and industrial EMC interference
III. Mecânico & Especificações Ambientais
Montagem: Vertical installation on standard 35mm DIN rail
Dimensões gerais (L × A × P): 160 × 125 × 121 milímetros
Peso líquido: Aprox.. 2.0 kg
Classe de proteção: IP20 (for cabinet installation only)
Temperatura operacional: 0~+55°C (full power derating required above 55°C)
Armazenar / temperatura de transporte: -25℃~+85℃
Umidade: 5%~95%RH, sem condensação
Certificações: CE, UL, GL marine certification; compliant with EN61010, EN61000 industrial EMC standards
- Comparison Table of Same-Series 3-Phase Power Supplies
| Número do pedido. | Entrada | 24V Output | Poder | Posicionamento |
| 6EP1436-2BA10 | 3AC 400–500V | 20UM | 480C | Medium-capacity 3-phase power supply |
| 6EP1437-2BA10 | 3AC 400–500V | 40UM | 960C | High-power standard 3-phase power supply |
| 6EP1437-3BA00 | 3AC 400–500V | 40UM | 960C | Equipped with relay signal output (fault contacts 13/14) |
- Definição de terminal
- Input terminals: L1, L2, L3, Educação Física (3 fases + protective earth)
- Output terminals: Dual sets of +24V, 0V (parallel for current sharing)
- Voltage trimming potentiometer: Located at bottom; adjust with flat screwdriver
- Luz indicadora: Solid green = normal output; desligado / flashing = fault (perda de fase, curto-circuito, superaquecimento)
- Cenários típicos de aplicação
- Large PLC control cabinets (S7-1500/400, full-station power supply for ET200SP distributed I/O)
- Multi-axis servo systems, inverter control stations, estações de trabalho robóticas
- Embalagem, triagem logística, automotive welding & assembly production lines
- Tratamento de água, energia eólica, metalurgia, cement and other high-power industrial control equipment
- Centralized 24V power supply scenarios requiring 3-phase industrial incoming power and high current loads
VII. Substituição & Capacity Expansion Solutions
- Upgraded same-spec model: 6EP1437-3BA00 (with fault relay contacts for PLC diagnostic connection)
- Capacity expansion: Parallel two 6EP1437-2BA10 units for max. 80UM / 1920W output
- Downsized alternative: 6EP1436-2BA10 (20UM / 480C) for half-load applications
VIII. Installation Prohibitions & Guia de solução de problemas
Forbidden Operations (Critical Restrictions)
- Horizontal or upside-down mounting is strictly prohibited; blocked cooling air duct triggers rapid over-temperature protection
- Long-term power-on with direct output short circuit will cause continuous hiccup power derating
- Long-term operation with missing input phase accelerates aging of internal power components
- Do not install alongside high-power inverters without partition plates to avoid EMC interference
Common Fault Matrix
| Fenómeno | Causa raiz | Contramedidas |
| Green light off, no 24V output | 3-phase power loss, disjuntor desarmou, internal overheating | Check 3-phase incoming voltage; power off and cool down then restart; clean dust in air duct |
| Green light flashing, output voltage drop | Output overload / curto-circuito | Disconnect loads and locate short circuit by segmentation; limit total load within 40A |
| Output voltage below 23V under load | Undersized cables causing excessive voltage drop | Thicken 24V main cables; add auxiliary power supplies nearby |
| Frequent over-temperature shutdown | Ambient temp >55℃, clogged air duct, fully enclosed cabinet | Install cabinet cooling fan, lower ambient temperature, reserve ≥50mm top & bottom ventilation clearance |
Official Overall Dimensions of Siemens 6EP1437-2BA10 (SITOP POWER 40 3-Phase 40A Power Supply)
- Overall Unit Dimensions (L × A × P, unidade: milímetros)
160 × 125 × 121 milímetros
Largura (horizontal along DIN rail): 160 milímetros
Altura (vertical cooling air flow direction): 125 milímetros
Profundidade (cabinet depth direction): 121 milímetros
Peso líquido: Aprox.. 2.0 kg
- Dimension Differentiation of Confusable Same-Series Models (Avoid Errors in Procurement & Cabinet Layout)
| Número do pedido. | Especificação | L × A × P (milímetros) | Peso |
| 6EP1436-2BA10 | 3-phase 20A | 90 × 125 × 120 | 1.6 kg |
| 6EP1437-2BA10 | 3-phase 40A (without fault contacts) | 160 × 125 × 121 | 2.0 kg |
| 6EP1437-3BA00 | 3-phase 40A (with fault relay) | 160 × 125 × 121 | 2.0 kg |
| 6EP1437-2BA20 (New PSU300S Series) | New generation 40A | 145 × 145 × 150 | 3.1 kg |
- Cabinet Installation Clearance Requirements
- Mounting rail: Standard 35mm TH35 DIN rail, instalação vertical (terminals downward)
- Principal & bottom ventilation clearance: Reserve at least 40mm for heat dissipation; derating mandatory if ambient temp exceeds 55℃
- Side-by-side mounting: Units of same model can be tightly arranged without extra spacing
Nota Suplementar
Dimensions such as 250×180×92 and 145×145×150 shown on some foreign websites belong to the new PSU300S model 6EP1437-2BA20, which is incompatible with the legacy 6EP1437-2BA10. Cabinet cutout and DIN rail layout cannot be shared between them.