Neles ND9106HNT/K05 REV 2.0 Intelligent Valve Positioner - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

 Neles ND9106HNT/K05 REV 2.0 Intelligent Valve Positioner - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

ŞtiriȘtiri comerciale

Neles ND9106HNT/K05 REV 2.0 Intelligent Valve Positioner

Neles ND9106HNT/K05 REV 2.0 Intelligent Valve Positioner

Neles ND9106HNT/K05 REV 2.0 Intelligent Valve Positioner

Marca: Neles (formerly Metso, now Valmet), ND9000 series, single-acting HART smart valve controller. REV 2.0 denotes the hardware and firmware revision; ND9106HNT/K05 is the complete order part number.

  1. Codul modelului Explicația

ND9106: ND9100 series, designed for single-acting actuators (spring return cylinder), compatible with rotary and linear stroke valves

H: protocol HART (HART7), 4–20mA loop-powered

N: Basic Hall-effect valve position feedback

T: Flameproof housing Ex d IIC T6 (distinguished from HE1 intrinsically safe version)

/K05: K05 mounting accessory kit, including valve mounting bracket and feedback linkage assembly

REV 2.0: Mainboard hardware revision, underlying firmware V2.0. Older REV1.x versions differ in diagnostic algorithms

Distincţie: ND9206 is the double-acting version; ND9103 is the basic short-stroke model; ND9106HNT is the single-acting flameproof type.

  1. Specificații tehnice de bază
ArticolCaietul de sarcini
Input Signal4–20mA DC, HART7, two-wire loop powered
Actuator TypeSingle-acting spring return; rotary stroke 0~95°, linear stroke 3~120mm
Air Supply Pressure1.4 ~ 8 bar (0.14~0.8 MPa) instrument air
Precizia poziționării±0,2% FS, low hysteresis
Protecție împotriva exploziilorATEX / IECEx Ex d IIC T6, ignifugă
Clasa de protectieIP66 / NEMA4X
Temperatura de operare-40℃ ~ +85℃
Valve Position DetectionNon-contact Hall sensor, fara uzura mecanica
SIL CertificationSIL2 (full loop assessment required)
Air ConnectionG1/4; Electrical port M20×1.5
Static Air ConsumptionExtremely low, steady state <0.05 NL/min
GreutateAproximativ. 2.7 kg
  1. Funcții de bază
  2. One-touch auto-calibration: Automatically identifies valve stroke and friction, supports fast on-site auto-tuning; remote configuration via HART communicator or FieldCare
  3. Valve diagnostic functions: Valve stroke curve, friction diagnosis, seat differential pressure and temperature monitoring, înregistrarea evenimentelor, enables predictive maintenance; EDDL/DTM compatible
  4. Piezoelectric pilot valve: Fast dynamic response and low static air consumption to save instrument air over long-term operation
  5. Local LCD with pushbuttons: On-site viewing of valve position and alarms, configuration of direct/reverse action and flow characteristics (linear / equal percentage / quick open); local access lock available
  6. Configurable fail position: Valve can be set to hold, fully open or fully closed upon loss of air or power (dependent on single-acting spring return design)
  7. Scenarii tipice de aplicare

Flameproof hazardous areas in petrochemical, refining, power plant and coal chemical industries. Suitable for spring return single-acting control valves, butterfly valves and ball valves; applied for control loop operation plus on-line valve diagnostics.

  1. Instalare & Ghid de punere în funcțiune
  2. Instalare: K05 kit includes mounting bracket, installation complies with VDI/VDE3845. Minimize clearance of feedback linkage to avoid backlash error
  3. Alimentare cu aer: 5μm filtration, uscat, oil-free and water-free instrument air
  4. Cablaj: Flameproof construction; cable entry sealing must comply with flameproof standards; intrinsically safe safety barrier is not required
  5. Calibration procedure: Supply air → connect 4-20mA signal → trigger Auto Tune locally. After tuning completion, verify 4mA/20mA end points and hysteresis
  6. Comunicare: Match HART loop load; read valve diagnostic data via FieldCare software
  7. Common Troubleshooting Checklist
  8. Valve oscillation: Excessive PID gain or high actuator friction. Reduce positioner gain and appropriately increase dead band
  9. Valve position fails to follow setpoint: Insufficient air supply, blocked piezo pilot valve or loose feedback linkage
  10. Unstable HART communication: Mismatched loop load or incorrect cable shielding earthing
  11. Calibration failure: Stroke exceeds positioner range, jammed feedback mechanism or fluctuating air supply
  12. REV version differences: REV2.0 fixes false diagnostic alarms present in early REV1.x versions; REV1 firmware cannot be directly flashed onto REV2 hardware
  13. Comparație de serie & Selectare alternativă
ModelActuator TypeProtecție împotriva exploziilorObservații
ND9106HNT/K05Single-actingFlameproof Ex dCurrent model for spring return valves
ND9106HN1/K05Single-actingIntrinsically safe Ex iaZonă 0 ESTE, safety barrier required
ND9206HE8Cu dublă acțiuneIgnifugăNo spring return cylinder
ND9103HNTSingle-actingIgnifugăBasic version with reduced diagnostic functions