Part Code: 3BSE008510R1
Internal Model: DO810
Seria de produse: ABB S800 I/O Distributed I/O, compatible with 800xA DCS / AC800M Controllers
Tip: 16-channel 24VDC Sourcing Digital Output Module
- Specificații electrice de bază
| Element de parametru | Caietul de sarcini |
| Total Channels | 16 channels divided into 2 isolated groups (8 canale pe grup) |
| Tensiune de ieșire | 10~30VDC, rated at 24VDC |
| Continuous Current per Channel | 0.5O (500mA) |
| Isolation Class | Optocoupler isolation between groups, isolation withstand voltage 50V |
| Tip de unitate | High-side Transistor Output (Aprovizionare) |
| Compatible Loads | Solenoid Valves, Indicator Lights, Small Relays, 24V Actuators |
| Protecții încorporate | Protecție la scurtcircuit, protectie la supratensiune, over-temperature current limiting, freewheeling suppression for inductive loads |
| Funcții de diagnosticare | Loop voltage monitoring for each group; channel faults uploaded to the controller via ModuleBus; individual LED status indicators per channel |
| Temperatura ambiantă | Operațiunea: 0~+55℃; Depozitare: -25~+70℃ |
| Clasa de protectie | IP20 (for cabinet installation only) |
| Greutate netă | 0.2kg |
| Dimensiuni generale | 56.3(W) × 90(H) × 97.5(D) mm |
- Matching Terminal Units (Mandatory for Use)
The module cannot be wired independently and requires selection of the following TU terminal bases:
TU810 / TU812 / TU814 / TU830 / TU833
Supports hot swapping; online module replacement without system shutdown
- Hardware Structure & Caracteristici funcționale
- Dual Isolated Group Design
The 16 channels are split into Group 1 (Channels 1–8) and Group 2 (Channels 9–16). The two groups feature independent isolated power supplies; a short circuit in one group will not disrupt outputs of the other group.
- Independent Channel-level Protection
Each channel is equipped with current limiting and over-temperature shutdown functions. The faulty channel cuts off automatically upon short circuit while all other channels remain operational with fault feedback signals.
- Loop Voltage Monitoring
Power supply detection inputs are configured for each group. The controller receives fault alarms in case of on-site 24V power loss to prevent misoperation.
- Industrial EMC Anti-interference Performance
Built-in filters and surge absorbers for deployment in high electromagnetic interference sites such as chemical plants, power plants and metallurgical facilities.
- Hot Swap Compatibility
The S800 I/O bus supports live insertion/removal, enabling maintenance without system shutdown.
- Typical Application Industries
Industria Energiei: Auxiliary control of thermal/hydropower units, coal conveying, ash removal, water treatment solenoid valves, belt start/stop control
Industria Petrochimică: Reactor feed valves, explosion-proof fans, on-site indicator lights, interlock actuators
Intelligent Manufacturing: Masini-unelte, linii de producție de ambalare, cylinder & solenoid valve control for automated production lines
Municipal Environmental Protection: Pump station valves, dust removal equipment, sewage chemical dosing systems
Wind Power, Clădire HVAC, Marine Automation Control
- Înlocuire echivalentă & Instrucțiuni de compatibilitate
- Fully equivalent model: 3BSE008510R0001 (long coding version with identical hardware)
- Comparison of alternative DO modules within the same series:
DO810 (3BSE008510R1): 16×0.5A 24V sourcing output, general-purpose model
DO820: 8-channel high-current output (2A pe canal), suitable for high-power loads
DO840: Relay dry contact output, compatible with mixed AC & DC loads
- Compatibilitatea sistemului: Only compatible with ABB AC800M Controllers + S800 I/O Stations; incompatible with third-party PLCs
- HS Customs Code
HS CODE: 8538903000 (Parts of Electrical Control Equipment)
- Matricea de depanare comună a erorilor
| Fenomen de eroare | Cauza de bază | Soluţie |
| Single channel LED off with no output | Scurtcircuit de sarcină / suprasarcina, damaged channel driver | Disconnect the load for testing; replace the faulty channel or entire module if damaged |
| No output for all 8 channels in one group | Loss of 24V power supply to the group, loose wiring on TU base | Inspect power supply to terminal unit and fasten wiring terminals |
| Controller reports ModuleBus communication fault | Poor contact of I/O bus, loosely inserted module | Re-insert the module and inspect backplane bus terminals |
| Frequent shutdown triggered by over-temperature protection | Multiple channels operating at full load simultaneously, ambient temperature exceeding 55℃ | Distribute loads and install cooling fans inside the cabinet |
Full Practical Application Cases of ABB DO810 (3BSE008510R1)
Module Positioning: S800 I/O 16-channel 24VDC sourcing digital output module paired with AC800M / 800xA DCS. It drives solenoid valves, relee mici, on-site indicator lights, fan and pump start/stop contacts, with built-in group isolation, short-circuit diagnosis and hot-swap functions, ideal for mass discrete point control in process industries.
Caz 1: Auxiliary Control System for Thermal Power Boilers (300MW Domestic Thermal Power Plant)
Project Overview
The unit is equipped with three sets of auxiliary control DCS for coal conveying, ash removal and chemical water treatment. The complete system adopts ABB 800xA + AC800M Controllers, with remote S800 I/O stations deployed in coal bunker rooms, electrostatic precipitator workshops and chemical water treatment buildings. DO810 (3BSE008510R1) modules are used in bulk quantities.
Application Points of DO810
- Coal conveyor interlock: Conveyor start/stop solenoid valves, deviation/pull-cord alarm indicator lights, limit solenoid valves for tripper cars
- Electrostatic precipitator system: Anode & cathode rapping coils, ash hopper unloading solenoid valves, high/low level indicator lights
- Boiler chemical dosing & water purification: Sampling valves, flushing solenoid valves, coils of chemical dosing pump control relays
Realized Selection Advantages
- High integration with 16 canale; one single module covers 8 dual isolated loop groups to reduce the number of I/O stations and save cabinet space
- Independent isolated power supply per group; short circuit of a single solenoid valve only locks the 8 channels within the corresponding group without triggering full coal conveyor interlock shutdown
- Channel short-circuit and 24V loop power loss signals are transmitted to the 800xA monitoring screen in real time for fast fault location by operators
- Hot swap support enables replacement of faulty modules without unit shutdown, avoiding load derating
Configuration Quantity
6~12 pieces of DO810 equipped with TU810 terminal bases per auxiliary control station, driving 24V on-site solenoid valves and indicator lights with load ≤0.5A.
Caz 2: DCS Project for 1 Million Ton/Year Coking & Coal Chemical Plant (Plateau Coal Chemical Plant in Qinghai)
Contextul proiectului
Distributed control system built with AC800F + S800 I/O for coking byproduct recovery, desulfurization, ammonia distillation and crude benzene rectification units. DO810 modules are extensively installed in on-site explosion-proof cabinets.
Control Scenarios
- Process pneumatic shut-off valves and regulating valve solenoids
- High/low level interlock vent valves and reflux valves for towers
- On-site explosion-proof audible & visual alarm lights, local control column indicator lights
- Drive of intermediate relays for circulating water pump and fan control loops
Solutions to On-site Pain Points
Coal chemical sites feature heavy dust, numerous inverters and strong electromagnetic interference:
Optocoupler isolation between groups plus built-in surge absorbers eliminate valve misoperation caused by inverter interference; independent channel current limiting prevents module backplane burnout in case of short circuits from medium leakage.
Project Highlight
The module’s wide operating and storage temperature range fits the plateau low-temperature environment (minimum -15℃ in winter) without additional heating devices.
Caz 3: Large Municipal Sewage Treatment Plant (50,000 m³/d Municipal Sewage Plant)
Control Scope
Full-process automatic control of coarse screens, fine screens, rezervoare de aerare, sedimentation tanks, sludge dewatering workshops and chemical dosing rooms.
Load List of DO810
- Screen washing solenoid valves, scraper direction switching valves
- Start/stop relays for PAC/PAM chemical dosing metering pumps
- Solenoid valves for electric butterfly valves on aeration air ducts
- Indicator lights for liquid level and dissolved oxygen over-limit alarms, local running indicator lights
Application Values
- Dense measuring points in chemical dosing rooms; one DO810 module covers 16 dosing valves to drastically cut wiring workload
- 24-hour continuous sewage treatment operation with channel-level fault diagnosis, eliminating manual line-by-line inspection
- Remote I/O cabinets installed adjacent to aeration tanks to shorten cable routing lengths from the central control room
Caz 4: Automated Automotive Component Assembly Production Line (Intelligent Manufacturing Line)
Line Requirements
Engine valve assembly line including loading, clamping, inspection and unloading stations. Local AC800M PLC controls cylinders, indicator lights and sorting solenoid valves.
Application Methods of DO810
- Drive production line cylinder solenoid valves (24VDC, single coil current 0.3~0.4A, matching the 0.5A channel capacity)
- Three-color OK/NG status indicator lights at stations, emergency stop reset indicator lights
- Sorting diverter valves, silo replenishment solenoid valves
Advantages vs Traditional Schemes
The original design adopted 8-channel DO modules requiring 3 pieces per line. Switching to DO810 covers 16 channels with one module, halving the number of cabinet I/O modules, reducing cabinet volume by 30% and shortening commissioning hours.
Caz 5: Tank Farm Interlock Control System for Refinery (800,000 Ton Product Oil Tank Farm)
Control Points
Tank farm emergency shut-off valves, nitrogen sealing valves, high-level interlock vent valves, on-site explosion-proof indicator lights, fire sprinkler solenoid valves
Utilized Safety Features
- Group isolation design of the module separates feed valves and vent valves into different channel groups; single loop faults will not trigger false full-tank interlock actions
- Real-time 24V output power monitoring; SIS alarms triggered immediately upon cable breakage or power loss
- Compliant with IP20 installation standards for refinery explosion-proof cabinets and usable with intrinsic safety isolation terminals
Caz 6: Circulating Turbid Water Treatment Station for Steel Plants (Circulating Water Supporting Rolling Mills)
Controlled Equipment
Cooling tower fan start/stop, filter backwashing solenoid valves, blowdown valves, water quality dosing valves, local running indicator lights
On-site Adaptation Advantages
Rolling mill workshops have high water vapor and slight condensation. DO810’s wide-temperature and moisture-proof circuit design ensures long-term stable operation. Multiple channels centrally control multiple groups of filter backwashing valves to simplify interlock logic programming.
Selecţie & Application Summary of DO810 (3BSE008510R1)
Scenarii de aplicație recomandate
- Process sections with concentrated numerous small 24VDC loads (electrovalve, lumini indicatoare, relee mici)
- Safety interlock systems requiring loop fault diagnosis and group isolation to prevent interlock failure
- On-site remote I/O stations with limited cabinet space demanding high I/O density
- Systems requiring online maintenance and hot-swap modules without shutdown
Scenarii nerecomandate
- Single-channel load exceeding 0.5A for high-power contactors/fans (adopt DO820 2A high-current module instead)
- 220V AC contact loads (adopt DO840 relay output module instead)
- Zonă 0 / Zonă 1 intrinsic safety explosion-proof areas requiring matched isolated safety barriers
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare