Prezentare generală de bază
- Brand Series: Digital output module for B&R Sistem 2005 PLC din Austria B&R (model prescurtat: DO479)
- Starea ciclului de viață: Întrerupt. Original manufacturer ceases mass production; only brand-new stock and refurbished second-hand spare parts are available on the market.
- Alternative Model Naming: 3D04796, 3DO479.6 (Letter “O” is often written as digit “0” in the industry)
- Cod HS: 8538909100 (Electrical control assemblies)
- Specificații electrice de bază
| Element de parametru | Specificatii tehnice |
| Channel Count | 16 transistor digital outputs with 2 electrically isolated groups (Channels 01~08 / 09~16) |
| Tip ieșire | 24 VDC Sourcing Output |
| Rated Current per Channel | 0.5 A pe punct |
| Max Total Current per Group | 4 O (8-channel summation limit) |
| Consumul de energie | External 24 VDC: 4.0 W; Backplane 5 V: 1.0 W |
| Protection Mechanisms | Thermal cut-off against channel short-circuit/overcurrent; Freewheeling for inductive loads; Protectie inversa polaritatii |
| Izolație electrică | Isolation between groups; Isolation between channels and PLC backplane; No isolation between channels within the same group |
| Response Delay | Hardware switching delay ≤ 1.2 Domnișoară |
| Terminal Accessories | TB170 terminal blocks to be ordered separately |
| Clasa de protectie | IP20 (For cabinet installation only) |
- de mediu & Specificatii mecanice
- Temperatura de operare: 0 ℃ ~ +60 ℃
- Depozitare / Transportation Temperature: -25 ℃ ~ +70 ℃
- Umiditate: 5% ~ 95% RH, necondens
- Dimensiuni: Standard single-width System 2005 modul, Montare pe șină DIN
- Certificari: CE, cULus (FILE E115267) industrial control equipment certifications
- Hardware & Indicators
16 independent status LEDs on the front panel; each LED illuminates when the corresponding output channel is activated
Red locking latches on the top for snap-in connection to the System 2005 autobuzul din spate
TB170 wiring terminal blocks on the right with group-split power supply: two independent 24 VDC output power loops
- Scenarii tipice de aplicare
Compatible with B&Sistemul R 2005 CPUs (3CPxx series) for discrete logic control on medium & small-sized machinery:
- Mașini de ambalare: Electrovalve, air cylinders, conveyor belt start/stop
- Textile & echipamente de imprimare: Clutches, air blowing units, slitting actuators
- Injection molding auxiliary machines, woodworking machine tools, pneumatic actuators for food production lines
- Auxiliary discrete outputs for wind power and small metallurgy equipment
- Replacement Solutions for Discontinued Units
6.1 Direct Compatible Replacements within System 2005
3DO478.6: 16 DO, 0.3 A pe canal; low current rating, applicable only for light-load scenarios
3DO480.6: 16 DO, 1 A pe canal; preferred for heavy loads with no program modification required
6.2 Upgrade între serii (New X20 System, Recommended for New Projects)
X20DO9322 (16-canal 24 VDC 0.5 A sourcing output with identical functionality; backplane and CPU replacement required)
- Achiziții & Troubleshooting Guidelines
Note de achiziție
Brand-new original units are mostly leftover inventory; abundant refurbished second-hand supplies with warranty periods ranging from 1 la 12 luni
Market price range: CNY 3,000 ~ 4,500 for new units; CNY 1,200 ~ 2,200 for refurbished units
Matricea de depanare comună a erorilor
| Fenomen de eroare | Cauza de bază | Rezoluţie |
| Single channel no output, LED off | Cablajul bornelor slăbite / thermal fuse tripped on the channel | Power off for cooling; retighten TB170 terminals |
| Toate 8 channels in one group fail | Short-circuit on group 24 Alimentare VDC / blown internal fuse | Measure external loads for ground short-circuit |
| PLC reports I/O bus error | Unlatched module backplane latches / damaged backplane | Re-seat the module; clean bus contact pins |
| Repeated burnout of output channels | Curentul de sarcină depășește 0.5 O / no freewheeling diodes for inductive loads | Replace with higher-current modules; add parallel freewheeling protection diodes |
- Restricții de selecție
- Cannot drive AC contactors (transistor-only DC outputs without relay contacts)
- Single-channel load current strictly limited to ≤0.5 A; total load per group shall not exceed 4 O
- Forbidden for humid, dusty or open-air environments (IP20 rating only)
- Not recommended for mass deployment in new projects; X20 series is the preferred alternative
Field Application Case Sharing of B&R 3DO479.6 (3D0479.6)
Basic Module Compatibility Prerequisites
16-canal 24 VDC sourcing transistor outputs, two electrically isolated groups (Channels 0–8 / 9–16), 0.5 A pe canal, compatible with all System 2005 PCC models. Primarily designed to drive solenoid valves, indicator lamps, mic 24 VDC actuators, and variable frequency drive start/reset signals. Ideal for discrete logic control on standalone medium & small machines. Split-group isolation separates air supply loops and alarm loops; built-in automatic thermal short-circuit protection delivers low failure rates.
Caz 1: Automatic 3D Transparent Film Wrapping Machine (Mâncare & Pharmaceutical Packaging Industry)
- Equipment Architecture
Controlor: Sistem 2005 PCC Model 3CP260.60-1
Output Modules: 2 × 3DO479.6 (32 DO points total) + TB170 spring terminals
Matching DI Module: 3DI476.6 (16 intrări digitale)
Controlled Loads: 24 VDC 5/2-way solenoid valves, heat sealing heater start/stop, film cutting cylinders, conveyor alarm lamps, VFD fault reset
- Channel Allocation for Single 3DO479.6
Grup 1 (CH01–CH08, independent 24 VDC air supply loop):
- Infeed pusher cylinder solenoid valve
- Film folding side sealing cylinder
- End sealing hot-pressing cylinder
- Film tension deviation correction solenoid valve
- Finished product discharge sorting cylinder
- Waste film cutting knife solenoid valve
- Film rack lifting cylinder
- Spare station cylinder
Grup 2 (CH09–CH16, independent 24 VDC alarm/auxiliary supply, isolated from air supply loop):
- Equipment running green indicator lamp
- Fault red warning lamp
- Film shortage audible & visual alarm output
- Material jam shutdown indicator lamp
- VFD start signal
- VFD fault reset
- Heat sealing cooling fan start/stop
- Auto / Manual mode indicator lamp
- Core Advantages of Adopting 3DO479.6
- Two-group electrical isolation: Separates air valve loops and alarm lamp power supplies. Reverse voltage surges from inductive solenoid loads cannot damage alarm circuits. Built-in freewheeling diodes eliminate the need for external parallel diodes and reduce on-site wiring workload.
- 0.5 A per channel perfectly matches small packaging machine cylinder solenoid valves; total current limit of 4 A for each 8-channel group fully satisfies simultaneous multi-cylinder actuation load demands.
- Channel thermal short-circuit lockout: Only the faulty channel is disabled when cylinders jam or coils short-circuit; the entire machine remains operational with single-channel fault alarms for fast maintenance localization.
- High-density single-width 16-point module saves cabinet space; only two DO modules cover all logic outputs for one wrapping machine.
- On-Site Operation Results
Mass deployed across over 200 wrapping machines running continuously for 8 ani. Numai 3 units triggered single-channel overcurrent protection with zero complete module burnout failures. Refurbished or stock 3DO479.6 spare parts are readily available on the aftermarket to cut equipment maintenance costs.
Caz 2: Automatic Pick-and-Place Robot for Injection Molding Auxiliaries (Materiale plastice & Home Appliance Injection Molding Industry)
- System Hardware
CPU: Sistem 2005 Model 3CP360.60-1
DO Module: 1 × 3DO479.6 (robot motion outputs)
Încărcături: 24 VDC clamping cylinders, blow-off solenoid valves, sprue cutting valves, safety door indicator lamps, alarm outputs, injection molding machine interlock start/stop signals
- Typical Control Workflow
Mold full open signal → 3DO479.6 outputs to lower travel cylinder → gripper clamps workpiece → blow-off valve purges sprue residue → cutting solenoid valve trims waste sprue → lifting cylinder returns to home position → discharge cylinder pushes finished product out. Fault conditions trigger warning lamps and cut interlock signals to the injection molding machine.
- Selection Rationale
All robot cylinders use low-power 24 VDC solenoid valves with coil currents of 0.2~0.4 A, below the 0.5 A rated limit. Dual isolation separates motion actuation loops and safety alarm loops, preventing safety lamp circuit damage caused by robot jamming short-circuits. Compact machine footprint allows all actuator outputs to be covered by a single 16-point module without stacking multiple low-density I/O units.
- Pain Point Resolution
Earlier non-isolated DO modules frequently suffered total alarm circuit failure when solenoid coils broke down. Group isolation on the 3DO479.6 completely eliminates cross-loop interference and cuts machine downtime failure rates by 60%.
Caz 3: Automatic Fabric Folding & Linie de producție a ambalajelor (Textile Printing & Dyeing Industry)
- Scenariul aplicației
Continuous line for automatic fabric flattening, folding, bagging and heat sealing post-printing/dyeing, with centralized discrete logic control over multi-section conveyors, lifting cylinders and heat seal stations.
- 3DO479.6 Channel Assignment
Grup 1 (Transmiterea / Folding Cylinders): Fabric flattening roller lift, left-right edge separation cylinders, folding press plates, wrapping film pushing valves
Grup 2 (Alarma / Ieșiri auxiliare): Fabric shortage warning lamp, heat sealing heater start/stop, conveyor motor enable signal, emergency stop fault output, count completion indicator lamp
- On-Site Adaptation Features
Textile workshops feature high dust and humidity; the module’s wide 0~60 ℃ operating temperature range suits workshop environments. IP20 cabinet mounting paired with dustproof enclosures ensures stable operation. Independent per-channel LEDs enable rapid localization of jammed or disconnected cylinder points during maintenance.
Caz 4: Auxiliary Logic Control for Small Industrial Boilers (Încălzire & Food Cooking Process Industry)
- System Architecture
B&Sistemul R 2005 PCC boiler control system; analog modules handle temperature and pressure regulation, while the 3DO479.6 executes all discrete actuation outputs: Induced draft / forced draft fan start/stop signals, feedwater solenoid valves, blowdown valves, high/low water level warning lamps, overtemperature interlock shutdown outputs.
- Isolation Value Demonstration
Grup 1: Fani, feedwater & blowdown valves (high-power inductive loads)
Grup 2: Alarm lamps, interlock shutdown contacts (low-voltage signal loops)
Independent isolated power supplies for the two groups block voltage spikes generated by fan contactor switching from interfering with alarm and safety interlock signals, eliminating risk of false boiler shutdowns.
Caz 5: Auxiliary Logic Control for CNC Wood Panel Cutters (Furniture Manufacturing Industry)
Controlled Loads
Panel clamping cylinders, infeed stop valves, dust extraction fan start/stop, dimension reach indicator lamps, material jam fault alarms, saw blade guard solenoid valves.
Module Advantages
Machinery requires simultaneous multi-cylinder actuation; cel 4 A total current ceiling per 8-channel group supports multiple concurrent solenoid valve activations. Thermal short-circuit protection prevents total machine loss of control from coil burnout caused by jammed panels, suited for high-impact, high-dust woodworking workshop conditions.
General Selection & On-Site Maintenance Summary
- Equipment Profiles Suitable for 3DO479.6
- All outputs are small 24 VDC solenoid valves, indicator lamps, VFD start/reset signals, or small 24 VDC fans with single-point loads ≤0.5 A
- Systems requiring electrical isolation between actuation loops and alarm loops to prevent low-voltage signal interference from inductive loads
- Standalone machines with 8~32 discrete output points, compact cabinet layouts requiring high-density single-width I/O modules
- Retrofit and spare part replacement for legacy System 2005 equipment fleets
- Scenarii nepotrivite (Selection Pitfalls to Avoid)
- Driving AC contactors or high-current DC solenoid valves (single-channel load >0.5 O)
- Explosion-proof or open-air non-cabinet environments (IP20 rating only)
- New greenfield machine designs (X20 series X20DO9322 is preferred alternative)
- Applications requiring full channel-to-channel isolation (only group isolation available; no inter-channel isolation)
- Common Retrofit & Replacement Cases
Large fleets of legacy packaging, textile and injection molding machines originally equipped with System 2005 hardware are now discontinued by OEMs. When spare modules fail, stock or refurbished 3DO479.6 units are directly installed with no program edits, plug-and-play backplane compatibility and universal TB170 terminals. Full replacement finishes within 10 minutes without wiring or software modifications.
Complete List of Discontinued B&R Modules (Original Manufacturer EOL, No Further Mass Production)
- Full System 2005 Serie (Fully Discontinued, Including 3DO479.6)
1.1 CPU Controllers (3CP Series)
3CP260.60-1, 3CP340.60-2, 3CP360.60-1, 3CP360.60-2, 3CP380.60-1
Auxiliary Processor: 3IF260.60-1
1.2 Intrare digitală (DIN) Module
3DI476.6 (16 DIN), 3DI486.6 (32 DIN), 3DI650.6, 3DI690.6
1.3 Ieșire digitală (DO) Module (Including 3DO479.6)
3DO478.6, 3DO479.6, 3DO480.6, 3DO486.6, 3DO650.6, 3DO690.6, 3DO750.6, 3DO760.6 (8 ieșiri releu)
1.4 Combined Digital I/O Modules (DI+DO Integrated, DM Series)
3DM455.60.2, 3DM476.6, 3DM486.6
1.5 Intrare analogică (AI) Module
3AI350.6, 3AI375.6, 3AI775.6, 3AI780.6, 3AT660.6 (Thermocouple module)
1.6 Ieșire analogică (LA) Module
3AO300.6
1.7 Combined Analog I/O Modules (AI+AO Integrated, AM Series)
3AM050.6, 3AM051.6, 3AM055.6, 3AM374.6
1.8 Universal Mixed I/O Module
3UM161.6
1.9 Comunicare / Bus Interface Modules
3IF761.6, 3IF772.6, 3IF786.6, 3IF860.6
1.10 Matching Terminals (Simultaneously Discontinued)
3TB170.9 (Borne cu șuruburi), 3TB170.91 (Spring terminals), 3TB178.9, 3TB178.91
- Legacy System 2003 PLC Series (Fully EOL)
Digital Output DO Modules
7DO135.70, 7DO138.70, 7DO139.70, 7DO164.70, 7DO435.7, 7DO720.7, 7DO721.7, 7DO722.7
Combined Digital DM Modules
7DM435.7, 7DM438.72, 7DM465.7
Counting / Positioning Modules
7CM211.7, 7CM411.70-1, 7MM424.70-1, 7MM432.70-1
Remote X2X I/O Modules
7XX410.50-1, 7XX412.50-1, 7XX415.50-K02, 7EX470.50-1
- 1st-Generation ACOPOS Servo Drives (Discontinued Legacy Models, Excluding ACOPOSmulti)
Full legacy single-axis drive series: 8V1016.50-2, 8V1022, 8V1044, 8AC110, 8AC120, 8AC130, 8AC140
- Legacy Power Panel HMI Touch Screens (Discontinued Operator Panels)
Early PP400 series models: 4P3040.00-490, 4PP120, 4PP150, 4PP220, 4PP250, 5PP320
- Early Discontinued X20 I/O Modules (1st-Generation X20, Superseded by New Models)
- Discontinued digital outputs: X20DO2322, X20DO4322, X20DO6321
- Legacy bus controllers: X20BC0043, X20BC0063 (Replaced by X20BC0083)
- Legacy CPUs: X20CP1483, X20CP3483, X20CP1583
- Discontinued Storage Accessories
Legacy industrial CF cards (discontinued industrial standard): 5CFCRD.0064-03, 5CFCRD.0128, 5CFCRD.0256
Master Comparison Table for Discontinued Module Replacements (Focus on System 2005 Serie)
| Discontinued Model | Direct Compatible Same-Series Replacement | New X20 Upgrade Alternative |
| 3DO479.6 (16 DO 0.5 A sourcing output) | 3DO480.6 (16 DO 1 O) | X20DO9322 |
| 3DI476.6 (16 DIN) | 3DI486.6 | X20DI9371 |
| 3DM486.6 (16 DIN + 16 DO) | No equivalent single module; combine two separate DI/DO modules | X20DM9324 |
| 3AI775.6 (8-channel 4–20 mA) | 3AI780.6 (16-bit high precision) | X20AI4622 |
| CPU 3CP360.60-1 | 3CP380.60-1 (Extremely limited stock) | X20CP3585 |
Important Remarks
- The entire System 2005 product line has been terminated by the OEM with no further firmware technical updates. Only leftover stock and refurbished second-hand spare parts circulate on the aftermarket; prohibited for new project selection.
- Repair policy for discontinued modules: OEM no longer provides component-level repair; full module replacement is the only option, and service availability declines year over year.
- Compatibility limitations: Sistem 2003 / 2005 backplanes cannot directly interface with X20 bus systems. Full machine upgrades require complete replacement of backplane, CPU and all I/O modules plus partial communication program rework.
- Your primary module 3D0479.6 = 3DO479.6 is a standard discontinued DO module within the System 2005 lineup; refurbished units constitute the main spare part supply source for maintenance operations.
Note de traducere
- Industry-standard automation terminology adopted (ieșirea din surse, DIN rail, backplane, interblocare, diodă de roată liberă, EOL = End of Life, Cod HS)
- Model numbers, certification file numbers and mechanical parameters remain unchanged as original technical data
- Unit currency CNY retained for price references; technical metric units kept consistent
- Table formats, heading hierarchy and section segmentation match the original Chinese document for direct use in international technical documents, catalogs and tender files
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare