ABB PSE210-600-70 Soft Starter - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

ABB PSE210-600-70 Soft Starter - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

PLC/

ABB PSE210-600-70 Soft Starter

PSE: ABB PSE series economical soft starter (tip compact, built-in bypass contactor) 210: Matched motor rated current 210 O (400 V, AC-53b duty) 600: Maximum withstand current of the main circuit: 600 O 70: Controlul tensiunii de alimentare: AC 100…240 V Series Positioning: The PSE model integrates a bypass contactor with no external bypass required. Compared ...

  • Detalii despre produs

PSE: ABB PSE series economical soft starter (tip compact, built-in bypass contactor)

210: Matched motor rated current 210 O (400 V, AC-53b duty)

600: Maximum withstand current of the main circuit: 600 O

70: Controlul tensiunii de alimentare: AC 100…240 V

Poziționarea în serie: The PSE model integrates a bypass contactor with no external bypass required. Compared with PSS and PSR series, it covers higher power ranges, suitable for fans, pompe de apa, belt conveyors and other standard loads.

Parametrii electrici cheie

Rated motor power: 110 kW @ 400 V

Curentul nominal de funcționare Ie: 210 O

Main circuit voltage: 208~600 V AC

Alimentare de control: AC 100~240 V (50/60 Hz)

Starting current limit: adjustable from 2×Ie to 5×Ie

Protectie la suprasarcina: adjustable electronic motor thermal overload protection

Bypass încorporat: Da; automatically switches to bypass operation after startup to reduce thyristor heating

Tip de montare: Montat pe perete

Funcții de protecție: Supracurent, pierdere de fază, supraîncălzire, phase sequence fault, suprasarcina motorului, thyristor failure, control supply loss

Aplicații tipice

Pompe de apă, centrifugal fans, belt conveyors and compressors.

Not applicable to frequent forward/reverse rotation or jogging operation. It suppresses starting inrush current, reduces grid voltage drop, and protects motors and mechanical equipment.

Selecţie & Ghid de înlocuire

  1. For heavy starting loads (de ex., fans started under full load), verify the starting current and select one size up if necessary.
  2. PSE has an integrated bypass; cabinet heat dissipation shall be designed based on continuous heat generation of the bypass contactor, not only thyristor power loss.
  3. Same-platform alternatives:

Aceeași serie: PSE210-600-70 (fixed model)

Upgrade series: PSTX series (PSTX210) with enhanced functions, built-in communication and advanced protection

  1. Comunicare: Basic PSE models have no native Modbus; an external communication module is required. PSTX models come with built-in Modbus RTU.

Depanare comună

Overheating alarm: Ventilatie insuficienta a dulapului, acumulare de praf, temperatura ambientala ridicata; burnt bypass contacts cause thyristors to remain energized continuously.

Overcurrent fault on startup: Excessively high current limit setting; blocaj mecanic; short circuit in motor insulation or power cables.

Phase loss alarm: Blown incoming fuses, loose main circuit wiring, damaged internal thyristors.

Bypass switching failure: Defective bypass contactor coil or auxiliary contacts.

Instalare mecanică & Cablaj

Cablaj: Three-phase power input L1/L2/L3; output terminals connect directly to the motor. Control terminals connect to start/stop signals and fault relay output.

Răcire: Răcire naturală cu aer; reserve upper and lower ventilation space; maintain gaps between multiple units installed side by side.

Enclosure rating: IP20 (indoor cabinet installation only).

Selection Schedule for ABB PSE210-600-70 (400 V, Motor Rated Current 210 O)

Nota: PSE210 has built-in bypass and integrated electronic motor overload protection. Upstream components only provide short-circuit protection, while motor overload protection is fully undertaken by the soft starter. System conditions: AC 400 V / 50 Hz, copper power cables, free air installation, ambient temperature 30~35 °C, standard fan/pump loads.

Soft starter rating: PSE210-600-70, Ie=210 A, maximum main circuit withstand current 600 O, built-in bypass contactor.

  1. Întrerupător cu carcasă turnată (MCCB, ABB SACE)

Funcţie: Protecție la scurtcircuit + electrical isolation. Long-time delay setting shall be higher than motor rated current; overload protection is assigned to the soft starter.

ArticolSpecificație recomandatăObservații
ModelT6N 630 TMA 3PABB OEM recommendation; dimensiunea cadrului 630 O, TMA thermal-magnetic trip; short-circuit breaking capacity 10 cel. Upgrade to T6H (20 cel) if prospective short-circuit current exceeds 10 cel.
Curent nominal In630 OCălătoria instantanee: 10×In to avoid tripping during current-limited soft start.
Setări de călătorieÎntârziere lungă: 250 O (adjustable range); Instantaneu: 10×ÎnDo not rigidly set to 210 O; retain sufficient margin for starting surge. Overload protection is undertaken by the PSE soft starter.
Alternativă internăNM1-630/3P 630 O, deplasare termomagneticăCost-effective option for budget-limited projects.
  1. Fuse Solution (Short-Circuit Protection without MCCB)

Suitable for upstream fuse protection inside the cabinet; gG general-purpose fuses. Verify I²t coordination to protect soft starter thyristors.

ABB PSE (Bypass încorporat)400 V PowerActualSchneider ATS22Siemens 3RW44Delta VSS2CHNT NJR2 (Bypass Version)DELIXI CDRAK3
PSE105-600-7055 kW105 OATS22C11Q3RW4435-6BC44VSS2-55NJR2-105CDRAK3-55
PSE142-600-7075 kW142 OATS22C14Q3RW4442-6BC44VSS2-75NJR2-142CDRAK3-75
PSE170-600-7090 kW170 OATS22C17Q3RW4444-6BC44VSS2-90NJR2-170CDRAK3-90
PSE210-600-70110 kW210 OATS22C21Q3RW4445-6BC44VSS2-110NJR2-210CDRAK3-110
PSE250-600-70132 kW250 OATS22C25Q3RW4446-6BC44VSS2-132NJR2-250CDRAK3-132
PSE300-600-70160 kW300 OATS22C32Q3RW4447-6BC44VSS2-160NJR2-300CDRAK3-160
PSE370-600-70200 kW370 OATS22C37Q3RW4454-6BC44VSS2-200NJR2-370CDRAK3-200

Brand Position Comparison

  1. Schneider ATS22: First choice for direct replacement. It has identical positioning, built-in bypass and matching protection functions. ATS48 / ATS480 have no built-in bypass; an external contactor must be fitted, which raises total cost.
  2. Siemens 3RW44: Bypass încorporat, direct counterpart to PSE. Basic 3RW40 models have no bypass and are prone to misselection. 3RW55 is the new generation with enhanced performance and higher price as an upgraded alternative.
  3. Eaton S811+: European equivalent with integrated bypass, widely adopted in overseas projects.
  4. Delta VSS2: Taiwanese economical model with built-in bypass, high cost-performance for retrofitting ABB PSE in domestic projects.
  5. CHNT NJR2 / DELIXI CDRAK3: Domestic economical options. Must select the built-in bypass variant; standard NJR2 requires an external bypass contactor.

Critical Notes for On-site Replacement (Engineering Compliance)

  1. Controlul aprovizionării: PSE accepts AC 100~240 V. ATS22 / 3RW44 support AC 110~230 V, which is fully compatible. Some domestic models only support AC 220 V and cannot be used if only 110 V control power is available.
  2. Starting Principle: PSE adopts two-phase thyristor control; ATS22 and 3RW44 use three-phase control. The difference in starting performance is negligible for pumps and fans; adjust ramp parameters on-site for heavy inertia loads.
  3. Comunicare: Only PSE models with suffix `-1` have native Modbus. Basic ATS22 units require an extra communication module; the same applies to Siemens models.
  4. Cabinet Dimensions: Mounting depth and cutout dimensions differ across brands; verify mechanical dimensions before retrofitting existing cabinets.
  5. Logica de protectie: Fault relay contact ratings and actuation logic are not identical. Rewire PLC control and fault alarm circuits accordingly.
  6. Heavy-duty Loads: For crushers and high-inertia belt conveyors, select one current size up instead of strictly matching the rated current in the table.

Higher-Grade Upgrade Alternatives

ABB PSE → ABB PSTX (same-brand upgrade, bypass încorporat, extended protection, native Modbus)

ABB PSE → Schneider ATS480 (no built-in bypass, advanced torque control)

ABB PSE → Siemens 3RW55 (bypass încorporat, funcții avansate de diagnosticare)

Prev:

Lasă un răspuns

Lăsaţi un mesaj