KEYENCE GS-11N5 Non-contact Safety Interlock Switch (GS Series Standard Type, NPN Output, 5m Pre-cabled)
Aplicație: Non-contact interlock detection for equipment safety guards/protective doors. Used together with GS series actuators (magnetic heads). Applied to machine tools, automated production lines and robot safety fencing.
✅ Model Code Explanation
GS: GS series non-contact safety interlock switch
11: Standard main unit model
N: NPN OSSD safety output (P stands for PNP)
5: 5m pre-fitted cable with bare wire ends (GS-11N10 is the 10m cable variant)
📋 Core Electrical & Sensing Specifications
- Alimentare electrică: DC24V ±20%, Clasă 2 alimentare electrică
- Ieșire: Dual OSSD NPN safety transistor outputs + 1 auxiliary non-safety AUX output (max. 50mA)
- Distanța de Sentire (with GS actuator)
Montare frontala: Sao(OFF→ON)=10mm; Sar(ON→OFF)=18mm
Montaj lateral: Sao(OFF→ON)=6mm; Sar(ON→OFF)=14mm
- Timp de răspuns
Detected → Not detected: 20ms +2ms ×(number of cascaded units −1)
Not detected → Detected: 30ms +25ms ×(number of cascaded units −1)
- Cascading: Până la 30 units in series
- Max. door actuation frequency: 3Hz
- Certificari de siguranta
EN ISO13849-1: PLe / Category4
IEC61508: SIL3; EN ISO14119 Type4 safety switch
- Protecţie: Reverse power polarity protection, protectie la scurtcircuit la iesire, protectie la supratensiune
🧵 Cable Pin Definition (8-core bare-end cable)
| Culoarea firului | Semnal | Descriere |
| Maro | Pin2 | DC24V pozitiv |
| Albastru | Pin7 | 0V GND |
| Negru | Pin5 | OSSD1 (Ieșire de siguranță 1, NPN) |
| Alb | Pin6 | OSSD2 (Ieșire de siguranță 2, NPN) |
| Red/Black | Pin8 | Intrare de siguranță 1 |
| Roșu/Alb | Pin4 | Intrare de siguranță 2 |
| Gri | Pin1 | AUX auxiliary output (non-safety, for PLC status feedback) |
| Light Blue | Pin3 | Nefolosit, must be individually insulated |
Note de cablare: Dual OSSD outputs connect to safety relay / safety PLC; AUX is only for status monitoring, MUST NOT be wired into safety circuit.
📌 Selection & Accesorii potrivite
GS-11N5 is only the switch body. GS series actuator (magnetic head) trebuie comandat separat, de ex. GS-A10, GS-A20. No mechanical contact between actuator and main unit; detection relies on magnetic field.
Peer models comparison:
GS-11N5: NPN, 5m cablu
GS-11N10: NPN, 10m cablu
GS-11P5: PNP, 5m cablu
GS-11P10: PNP, 10m cablu
⚠️ Installation & Ghid de întreținere
- The gap between main unit and actuator must stay within rated sensing range. Reserve clearance for vibration-prone sites to prevent false triggering.
- Do not install close to strong magnets to avoid magnetic interference.
- For cascaded configuration, total response time increases with series quantity; safety circuit assessment must include delay.
- Enclosure IP rating: potrivite pentru medii industriale, avoid continuous immersion.
- Troubleshooting priority: verifica alimentarea cu energie, cable breakage, actuator position offset first. Mismatch of dual OSSD channels usually indicates fault.
📎 Alternative Products
Similar non-contact safety gate switches: Schneider XCS-DMP, Pilz PSENmag, Omron D40A series. Note differences in safety level, OSSD type and cascading capability; direct replacement into safety circuit is not allowed.
GS-11N5 Troubleshooting Checklist (Indicator LED + Fenomen + Remediu)
GS-11N5 equipped with tri-color LED: Verde / Portocale / Roşu. Judge fault by LED status first.
Never short OSSD channels for testing. Lock-out & tag-out equipment before modifying safety circuits.
- LED Status Definition
| Stare LED | Sens |
| Solid Green | Normal: actuator detected, door closed, dual OSSD channels conductive |
| Solid Orange | Power OK, actuator not detected (door open), OSSD cut off |
| Solid Red | Internal fault / OSSD channel mismatch / scurtcircuit, safety circuit locked |
| Flashing Red | Cascading circuit fault / wrong safety input wiring |
| No LED | Fără alimentare, broken power wire, reverse polarity |
- Step-by-step Troubleshooting (de la simplu la complex)
2.1 Power Check (priority when no LED)
- Measure Brown(24V+) and Blue(0V), confirm DC24V within 19.2~28.8V
- Check reverse polarity. Built-in reverse protection prevents burnout but unit will not operate.
- Inspect cable root for bending damage (5m cable model most prone to wire breakage at root).
- Confirm Class2 power supply with sufficient capacity and no voltage drop.
2.2 Sensing Gap & Actuator (solid orange LED, door closed but no detection)
- Confirm actuator is GS series (GS-A10 / GS-A20). Other brand magnetic heads cannot be used.
- Montare frontala: gap ≤10mm for activation; >10mm cannot trigger; >18mm permanently off.
- Montaj lateral: Sao=6mm, Sar=14mm, stricter gap requirement.
- Check loose mounting brackets, vibration shift, deformed metal cover squeezing main unit/actuator.
- Check nearby strong magnets, inverters or high-current cables causing magnetic interference.
2.3 Safety Input Wiring (Most common pitfall for non-cascaded use)
For GS-11N5 (NPN), when not cascaded, the two safety inputs must be shorted to 0V (Sârmă albastră)
Red/Black (Safety Input1) and Red/White (Safety Input2) short to 0V;
✘ Wrong: floating / connected to 24V → red fault LED.
Cascading: OSSD outputs of previous GS connect to safety inputs of next unit, channel-to-channel matching.
2.4 OSSD Dual Channel Fault (Solid Red LED)
Simptom: OSSD1 and OSSD2 status mismatch, safety relay reports channel error
- Disconnect load and measure Black(OSSD1) and White(OSSD2) separately.
- Check OSSD cable short to ground or inter-wire short; OSSD short-circuit protection triggers latch-up.
- Wiring resistance limit: total loop resistance ≤2.5Ω; long/thin cables may trigger fault.
- Capacitive load limit: max. 2.2μF; parasitic capacitance of long cables may cause timing mismatch between channels.
- Check cross-wiring between safety relay / safety PLC channels. OSSD1 and OSSD2 must not be swapped.
2.5 AUX Auxiliary Output (Status feedback only, non-safety)
Gray AUX follows door state, only for PLC monitoring, must not be inserted into safety circuit
Door closed: AUX ON; Door open: AUX OFF
AUX abnormality does not affect OSSD safety function, only status indication.
- Quick Fault Reference Table
| Fenomen de eroare | Cauza probabilă | Remediu |
| Door fully closed, orange LED remains, safety circuit open | Gap exceeds Sao, mounting offset, wrong actuator | Adjust gap, fasten bracket |
| Red LED on at power-up, cannot reset | Wrong safety input wiring (NPN not shorted to 0V); OSSD short | Check Red/Black & Red/White wiring; disconnect load to retest OSSD |
| Intermittent safety fault, random tripping | Cable root breakage; gap drift under vibration; cable voltage drop | Replace cable; reinforce mounting; increase wire gauge |
| Cascaded units, downstream unit red LED | Wrong cascading wiring; excessive total response time | Disconnect cascade one by one to locate faulty unit; evaluate total safety delay |
| Normal briefly after power cycle, fault soon recurs | Hidden short in output loop; excessive cable parasitic capacitance | Scurtați lungimea cablului, add termination to reduce capacitance |
- Criteria for Main Unit Damage Replacement
Replace GS-11N5 if any condition below is met:
- Putere, wiring and actuator are fully verified correct, red LED latched and cannot reset.
- Actuator within qualified sensing distance, green LED fails to light up.
- OSSD channel mismatch persists even after all external loads disconnected.
⚠️ Safety Precautions
- Shut down equipment and cut off power before safety circuit test.
- Do not short OSSD safety outputs for commissioning.
- Perform full safety function verification after switch replacement.
- Max. 30 units for cascading; longer chain brings larger response delay, which must be included in safety assessment.
GS-11N5 Wiring Example for Safety PLC
Condiție prealabilă: GS-11N5 is NPN OSSD dual safety output. This case: single unit, non-cascaded, widely used for safety gates on automated lines.
Safety PLC examples: KEYENCE KV-S04 / Pilz PNOZmulti / Siemens F-PLC. Principle is universal, terminal numbers vary by brand.
⚠️ Important: OSSD is safety transistor output, NEVER short OSSD for testing. Lock-out & tag-out before modifying safety circuit.
- GS-11N5 Cable Assignment (O singură unitate, non-cascaded)
| Culoarea firului | Semnal | Wiring Target | Observații |
| Maro | DC24V+ | 24V Power Positive | Main unit power supply |
| Albastru | 0V(GND) | 24V Power Negative | Main unit power supply |
| Negru | OSSD1 (Safety Channel1 NPN) | Safety PLC Safety Input CH1 | NPN: pulled to 0V when door closed |
| Alb | OSSD2 (Safety Channel2 NPN) | Safety PLC Safety Input CH2 | Dual independent channels, connect to two separate safety inputs |
| Red/Black | Safety Input1 | Short to Blue(0V) | Mandatory for non-cascaded use; floating wire triggers red fault LED |
| Roșu/Alb | Safety Input2 | Short to Blue(0V) | Mandatory for non-cascaded use |
| Gri | AUX Auxiliary Output | Standard PLC Digital Input (non-safety point) | Door status monitoring only, must not connect to safety circuit |
| Light Blue | Nefolosit | Insulate separately, nicio conexiune | Do not ground or connect to 24V |
NPN OSSD Characteristics:
✅ Door closed (actuator in place): OSSD1 & OSSD2 turn ON → Black & White ≈0V
✅ Door open: OSSD1 & OSSD2 OFF → high impedance, near 24V
- Safety PLC Side Wiring Logic (Dual-channel Safety Input)
Two common safety PLC input types:
Tip A: Sourcing safety input (High level active)
GS-11N5 NPN OSSD cannot directly drive sourcing safety input
✅ Solution: Pull-up resistors (2.2kΩ /0.5W recommended) on Black & White wires to DC24V.
When door closed, OSSD pulls signal low. PLC detects consistent low level on both channels as safe state.
Tip B: Sinking safety input (Low level active, recomandat)
Direct connection for GS-11N5, no extra resistors needed
Safety PLC internal: safety input terminals pulled up to 24V
Black OSSD1 → Safety Input CH1
White OSSD2 → Safety Input CH2
Door closed: OSSD ON, CH1 & CH2 pulled to 0V, dual-channel consistent, safety circuit enabled
Door open: OSSD OFF, CH1 & CH2 return to 24V, safety circuit de-energized
- AUX Auxiliary Output Wiring (Standard PLC)
Gray AUX (NPN):
AUX emitter internally connected to 0V; collector requires external 24V pull-up to standard PLC DI
Standard DI wiring: 24V → DI terminal; Gray wire to DI common
Door closed: AUX ON → DI ON; Door open: AUX OFF → DI OFF
Utilizare: HMI door status display, alarm indication; must not be used for safety stop logic
- Cascading Overview (Multiple GS-11N5 in series to Safety PLC)
Used for multiple safety doors in series detection, max. 30 unitati
- OSSD1 (Negru) of previous GS → Safety Input1 (Red/Black) of next GS
- OSSD2 (Alb) of previous GS → Safety Input2 (Roșu/Alb) of next GS
- Last GS-11N5: OSSD1 & OSSD2 connect to dual safety inputs of safety PLC
- Safety Inputs of first GS shorted to 0V
Nota: Total response time accumulates in cascade; safety evaluation must calculate total delay. Any door open will cut off OSSD for the whole chain.
- Safety PLC Program Configuration Points
- Channel Mode: Set as Dual-channel safety input, enable cross monitoring for channel discrepancy
- Discrepancy tolerance time: 20~50ms typically, do not set excessive value
- Fault action: Channel mismatch → safety stop, latch fault, reset signal required
- Do not use AUX signal for safety stop logic; use only for diagnostic alarm
- After program download, full function test: door closed allow run, door open immediate stop, single wire break triggers safety fault
- Site Commissioning Checklist
- Pre-power check: Red/Black & Red/White shorted to 0V (single unit), Light Blue insulated
- LED test: Actuator near → solid green; actuator removed → solid orange; no red LED
- PLC signal: CH1 & CH2 go low simultaneously when door closed; high when door open
- Fault simulation: Disconnect Black or White wire individually; PLC must detect channel mismatch and trigger safety fault
- Cable parasitic capacitance: Use shielded cable for wiring >20m, shield grounded at single end to prevent false OSSD action
- Common Pitfalls
- ❌ Red/Black & Red/White floating for single unit: immediate red latch-up, frequent beginner wiring mistake
- ❌ AUX Gray wire connected to safety PLC safety channel: safety certification invalid, major hazard
- ❌ NPN OSSD directly to sourcing safety input: reversed logic, cannot work properly
- ❌ Safety PLC set to single channel mode: loss of cross-channel fault detection, safety rating downgraded
KEYENCE GS Series Safety Gate Switch Full Model List
GS series is divided into three categories: GS-10 Non-locking non-contact magnetic safety switch (GS-11N5 belongs to this group), GS-50 Solenoid locking (Power-to-release), GS-70 Solenoid locking (Power-to-lock)
Model coding rule:
N = ieșire NPN; P = ieșire PNP
5 = 5m bare cable; 10 = 10m bare cable; PC = M12 connector (0.3m short pre-cable)
11=Standard; 10=Basic; 13=High-function; 51/71=Locking standard; 53/73=Locking high-function
- Non-contact Type (No solenoid lock, magnetic safety switch GS10 Series)
Only for door position detection, no locking function; PLe / Cat4 / SIL3, până la 30 cascaded units
| Model | Tip | Ieșire | Cable Style | Descriere |
| GS-10PC | Tip de bază | PNP | M12 Connector | Model de bază, simplified function, no EDM |
| GS-11N5 | Tip standard | NPN | 5m bare cable | Your target model, 8-core bare wire |
| GS-11N10 | Tip standard | NPN | 10m bare cable | NPN,10m cablu |
| GS-11P5 | Tip standard | PNP | 5m bare cable | PNP,5m cablu |
| GS-11P10 | Tip standard | PNP | 10m bare cable | PNP,10m cablu |
| GS-11PC | Tip standard | PNP | M12 Connector | M12 connector version |
| GS-13P5 | High-function | PNP | 5m bare cable | Support EDM external device monitoring, resetare manuală |
| GS-13PC | High-function | PNP | M12 Connector | High-function, conector M12 |
- Solenoid Lock GS-50 Series (Power-to-release: Locked when powered, unlocked on power loss)
Locking logic: Keep energized to hold lock; door releases automatically upon power failure. Suitable for safety guard doors, safety chambers.
| Model | Tip | Ieșire | Cable Style |
| GS-51N5 | Locking Standard | NPN | 5m bare cable |
| GS-51N10 | Locking Standard | NPN | 10m bare cable |
| GS-51P5 | Locking Standard | PNP | 5m bare cable |
| GS-51P10 | Locking Standard | PNP | 10m bare cable |
| GS-51PC | Locking Standard | PNP | M12 Connector |
| GS-53PC | Locking High-function | PNP | M12 Connector |
- Solenoid Lock GS-70 Series (Power-to-lock: Lock only when energized)
Unlocked when power off; coil must be energized to engage lock. Suitable for robot safety doors.
| Model | Tip | Ieșire | Cable Style |
| GS-71N5 | Locking Standard | NPN | 5m bare cable |
| GS-71N10 | Locking Standard | NPN | 10m bare cable |
| GS-71P5 | Locking Standard | PNP | 5m bare cable |
| GS-71P10 | Locking Standard | PNP | 10m bare cable |
| GS-71PC | Locking Standard | PNP | M12 Connector |
| GS-73PC | Locking High-function | PNP | M12 Connector |
- Matching Actuators (Magnetic head, mandatory for GS main unit)
| Model | Nume |
| GS-A10 | Standard Actuator |
| GS-A20 | Long Sensing Distance Actuator |
- Suporturi de montare & Accesorii
GS-B01, GS-B11, GS-B21, GS-B31, GS-B41, GS-B33, GS-B43
- Alte accesorii
GS-T01: Test Tool
✅ Quick Selection Guide
- Only door detection, no locking → GS-10 series (GS-11N5/GS-11P5)
- Lock required, auto unlock on power loss → GS-50 series
- Lock required, lock only when powered → GS-70 series
- High-function models (GS-13/53/73): support EDM external diagnostic, resetare manuală; GS11/51/71 standard versions do not support EDM.
Remarcă: GS models with SO suffix (GS-10PCSO / GS-11PCSO / GS-51PCSO / GS-71PCSO) are special custom versions, rarely used in general projects.
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor



















NH42-63-318x560.png)



