PAXS: Strain Gauge / Load Cell input model 0000: 85–250 VAC AC power supply version DC variant: PAXS0010 (11–36 VDC) Basic Specifications Brand: Red Lion (now part of HMS Networks), Made in USA Form Factor: 1/8 Montare pe panou DIN (cutout size: 92×45 mm) Afişa: 5-LED roșu cu cifre, 0.56″ (14.2 mm), sunlight-readable; gamă: -19999 ~ 99999 ...

  • Detalii despre produs

PAXS: Strain Gauge / Load Cell input model

0000: 85–250 VAC AC alimentare electrică versiune

DC variant: PAXS0010 (11–36 VDC)

Specificații de bază

Marca: Red Lion (now part of HMS Networks), Fabricat in SUA

Factor de formă: 1/8 Montare pe panou DIN (cutout size: 92×45 mm)

Afişa: 5-LED roșu cu cifre, 0.56″ (14.2 mm), sunlight-readable; gamă: -19999 ~ 99999

Intrare: Strain bridge input; selectable range ±24 mV / ±240 mV; compatible with load cells, strain pressure transducers and torque sensors

Alimentare electrică: 85-250 VAC, 50/60 Hz, consumul de energie 11 W

Front Panel Protection: IP65

Certificari: UL, cUL, CE, RoHS, UKCA

Cod HS: 9030337000; ECCN: EAR99; 2-year factory warranty

Funcții cheie

  1. 16-point linearization correction for non-linear load cell calibration
  2. Front-panel keypad programming (DSP/PAR/F1/F2/RST); parameters stored in EEPROM with power-off retention
  3. Până la 3 plug-and-play optional expansion cards for field upgrades:

Relay setpoint card (alarma & control output)

Analog transmitter card (4-20 mA / 0-10 V)

Communication card: RS232 / RS485 Modbus, Profibus‑DP

  1. Custom engineering unit labels (kg, N, t, MPa, etc.)

Aplicații tipice

Weight monitoring, force measurement, presiune & torque monitoring; cântărire siloz, mașini de testare a materialelor, press-fit force monitoring.

Cross Reference for the Series

PAXS0000: AC-powered strain gauge meter (modelul actual)

PAXS0010: DC-powered strain gauge meter

PAXP0000: 4–20 mA process input meter

PAXI0000: Counter/frequency meter

PAXT0000: Thermocouple/RTD temperature meter

Piese de schimb & Alternative

Optional add-on cards: PAXCDS10, PAXCDC500, PAXCDL10, etc.

Înlocuire upgrade: New-generation PAX2S0000 (PAX2 series, dual-line color display with enhanced functions)

PAXS0000 Red Lion | On-Site Calibration with Standard Weights + Signal Source ADC Calibration + Lista de verificare pentru depanarea erorilor

Precondiții: 30-minute power warm-up; confirm PCB jumpers: input range (±24 mV / ±240 mV), excitation voltage (5 V / 10 V); complete sensor wiring (EXC+, EXC-, SIG+, SIG-, shield); parameter lock released (unlock first if locked)

Funcțiile tastaturii:

DSP = Back / Display Toggle | PAR = Confirm / Next Item | F1 = Up | F2 = Down | RST = Zero Reset

  1. Two-Point Field Calibration with Standard Weights (Recommended for Weighing & Force Measurement)

This is Scaling (Span & Zero Calibration), NOT internal ADC factory calibration.

9-FCS is ADC reference calibration, factory-set only; only re-calibrate after meter drift or mainboard replacement (access with CODE 48). Do NOT run this step for regular on-site weighing.

  1. Zero load: Ensure no weight on the platform, no mechanical binding; connect shield with single-point grounding; wait for stable reading.
  2. Press PAR repeatedly to enter the menu, open the INP input module, configure:

Interval de intrare (24 mV / 240 mV), excitation voltage, decimal point, unitate de inginerie

  1. Open the SCAL scaling menu

Zero (ZERO): Fără sarcină, press PAR to confirm zero; wait for —- and save the zero offset

Span (SPAN): Apply standard weights (≥70% full scale). Once stable, edit the displayed value to match the actual weight of the test weights, then press PAR to save span gain.

  1. Exit the SCAL menu; repeat zero-load and full-load testing 2~3 times. Re-calibrate if deviation is large.
  2. Opțional: LIN 16-point linearization calibration (for non-linear load cells or high-precision press-fit curve testing; input load and corresponding reading point by point)
  3. After calibration, set a security password to lock parameters against accidental changes.
  4. Internal ADC Reference Calibration (9-FCS, CODE = 48, Service Use Only)

Only perform this if the meter drifts, mainboard is replaced, or ADC reading is suspected inaccurate. Skip this step for normal field weighing.

  1. Enter menu 9-FCS, introduceți parola 48, press PAR to confirm.
  2. Select the active input range (±24 mV or ±240 mV).
  3. Zero point: Set signal source output to 0 mV across SIG+ and SIG-, press PAR and wait for —-.
  4. Full-scale point: Output the corresponding full-scale signal (20 mV for 24 mV range / 200 mV for 240 mV range; do not exceed full range). Press PAR and wait approx. 10 secunde.
  5. When NO appears, press PAR twice consecutively to exit the menu.
  6. Reconnect the load cell, then re-run the weight-based SCAL scaling calibration above.
  7. Restore Factory Defaults

Locate the dEF menu and confirm the reset.

⚠️ All calibration data, alarm settings and communication parameters will be erased; full re-calibration is mandatory after reset.

  1. Lista de verificare pentru depanarea erorilor (PAXS0000)
  2. Fără afișare

Verificați tensiunea de alimentare: 85-250 VAC; verify terminal voltage, live/neutral polarity and loose terminals

Check internal fuse on the meter

Distinguish from parameter lock (LOC): LOC only blocks parameter editing, not power-up display

Faulty power board; replace the meter

  1. LOC Locked, Cannot Enter Menu or Edit Parameters

Parameter security lock enabled; enter the unlock password

If password is lost: restore factory defaults (all calibration data will be lost)

  1. OL / UL Alarm (OL = Over Range; UL = Under Range)

Load cell overloaded, impacted, or load exceeds full scale

Broken excitation wire, open SIG+/SIGwire, open bridge circuit inside the load cell

Incorrect jumper selection (240 mV range selected while signal is only 24 mV, sau invers)

Short-circuit of load cell or damaged signal cable shorted to ground

Span value set too small during scaling

  1. Unstable Reading, Jitter & Drift (High-Frequency Fluctuation)

Shield wire missing; împământare în mai multe puncte; signal cable routed alongside power cables causing EMI interference

Oxidized or loose wiring terminals

Unstable excitation voltage; load cell creep or cell damage

Filter parameter FLT set too low (răspuns rapid); increase filter time

Mechanical binding on the weighing platform, tight limit stops, loose base mounting

Water ingress or dampness inside junction box

  1. Deriva Zero, Cannot Zero with No Load, Permanent Zero Offset

Auto zero tracking ZTRK disabled; enable zero tracking (do not set large tracking values for heavy force measurement, which will cancel out real load readings)

Uneven mounting or eccentric loading on the load cell

Moisture inside junction box causing unbalanced bridge resistance

Cold calibration without sufficient warm-up (temperature drift)

Fatigue damage of the load cell

  1. Incorrect Readings After Loading, Poor Linear Performance, Drift After Calibration

Calibration performed with insufficient test weight (mai puțin decât 70% FS), amplifying scaling error

Non-linear load cell; enable 16-point LIN linearization correction

Wrong excitation jumper (5 V / 10 V mismatch), leading to mV/V conversion error

Excessive cable resistance from long wiring without 6-wire remote sense compensation

Drifted bridge resistance due to damaged load cell

Interference from faulty expansion cards (transmiţător / communication card)

  1. Relay Output Card (PAXCDS10) Fails to Trigger

Incorrect setpoint (SP) and hysteresis (HYST) configurație

Wrong NO/NC output mode setting

Poor card contact; power off, remove and re-seat the expansion card, clean the slot contacts

Load voltage exceeds relay contact rating

  1. Inaccurate 4–20 mA Analog Output (PAXCDC500 Transmitter Card)

Analog zero & span must be calibrated separately, independent of weighing scaling; perform dedicated AO calibration

Loop load resistance exceeds max. 750 Oh; open circuit in current loop

Damaged analog output card; replace the card

  1. Modbus RS485 Communication Failure (PAXCDL10 Card)

Mismatched address, baud rate, parity and slave ID between meter and PLC

Lipsește rezistența de terminare; A/B signal wires reversed

Meter parameter locked; locked versions switch communication to read-only mode

Cross-check Modbus register addresses against the official manual

  1. Error Codes Err1 ~ Err4

Err1: ADC input fault → Run 9-FCS CODE48 reference calibration first; failure indicates mainboard hardware damage

Err2: Expansion card communication fault → Remove cards one by one and test individually; clean slot contacts

Err3: EEPROM memory checksum failure → Parameter corruption; restore factory defaults and re-program all settings

Err4: External digital input short-circuited

  1. Standard On-Site Troubleshooting Sequence
  2. Opriți; inspect all wiring, shielding and measure bridge resistance across EXC and SIG terminals with a multimeter
  3. Power on and warm up for 30 minute; check zero-load reading
  4. Verify jumper settings (excitation voltage & input range)
  5. Check filter and zero-tracking parameters
  6. Re-run two-point SCAL weight calibration
  7. If fault persists, perform 9-FCS ADC reference calibration
  8. If calibration still fails: replace load cell or swap the meter for testing

Notă importantă

Red Lion USA does not manufacture load cells. PAXS series meters only accept external strain bridge sensor signals. There are no original Red Lion load cell models.

  1. Red Lion Strain Gauge Meter Product List (PAXS Compatible Models)

PAX Series (1/8 DIN Panel Meters)

  1. PAXS0000: AC-powered strain gauge meter (your current model), 85-250 VAC
  2. PAXS0010: DC-powered strain gauge meter, 11–36 VDC
  3. PAX2S0000: New PAX2 color display model (replaces legacy PAXS)

LD Large-Display Strain Meters (Long-Distance Viewing)

  1. LD2SG5P0: 2.25″ digit strain gauge input
  2. LD4SG5P0: 4″ digit strain gauge input

FlexEdge DA Strain Input Modules (DA70/DA75 Controller Expansion)

  1. DAM00PDSG2RA0000: Dual-channel strain input module with relay output, for weight, force and pressure bridge sensors

Obsolete Discontinued Models

  1. IMS03162: Older strain panel meter (sfârşitul vieţii)
  2. Compatible Load Cell Models (Directly Matched with PAXS0000)

All listed models are mV/V strain bridge type, 350 Ω nominal bridge resistance, 2.0 mV/V nominal sensitivity, 4-sârmă / 6-conexiune prin cablu, compatibil cu 5 V / 10 V excitation from the PAXS meter.

  1. Mettler Toledo

SBC Cantilever (hopper & platform scale)

MT1041 Single-point (small bench scale)

MT1240 Single-point

SB Cantilever

0745 Column Load Cell

TSH Tension Load Cell

  1. Celtron (Vishay)

LSD Single-point

SQB Cantilever

STC S-type Tension/Compression (widely used for press-fit force testing)

HBB Cantilever

  1. Zemic

H3F Single-point bench scale

B3G S-type Tension/Compression

HM8 Column Load Cell

L6E Single-point

  1. HBM (Germania)

S40 S-type Tension/Compression

Z6FC3 Single-point Bench Scale

C16A High-capacity Column Cell for Silo Weighing

  1. Transcell

BSS S-type Tension/Compression

FSSB Single-point

CBS Cantilever

  1. Alternative interne rentabile

Bengbu Load Cells: S-type, cantilever, column, spoke type

Ningbo Keliu: SQB, BSS, DBS, PST series

III. Mandatory Selection Criteria for PAXS0000 Load Cells (Avoid Calibration Errors)

  1. Tip de semnal: mV/V strain bridge only; 4–20 mA transmitters require PAXP meter instead
  2. Bridge Resistance: Preferat 350 Oh; 120 Ω is also supported but limits parallel cell quantity
  3. Sensibilitate: Standard 2.0 mV/V; 1 mV/V or 3 mV/V can be set directly in meter scaling
  4. Tensiune de excitare: Match meter jumper (5 V / 10 V) with the cell rated excitation
  5. Cablaj: 6-wire remote sense recommended for long cable runs (zero drift suppression); 4-wire acceptable for short distances
  6. Full-Scale Output: Ensure full-scale mV output falls within meter range (±24 mV / ±240 mV)

Exemplu: 2 mV/V cell + 10 V excitation = 20 mV full output → select ±24 mV range (most common setup)

  1. Recommended Application Combinations (Field-Proven Solutions)
  2. Press-fit & force-testing fixtures: S-type cell (STC / B3G / S40) + PAXS0000 + PAXCDS10 relay card
  3. Small bench checkweigher: Single-point cell (L6E / MT1041) + PAXS0000
  4. Hopper & cântărire siloz: Cantilever SQB / column cell + PAXS0000; calculate total bridge resistance for multiple parallel cells