Schneider PM750MG Multifunction Power Meter

Întrerupt (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement. Model Code Explanation PM750: High-end multifunction power monitor of PM700 series MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging Core Functions ...

  • Detalii despre produs

Întrerupt (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement.

Codul modelului Explicația

PM750: High-end multifunction power monitor of PM700 series

MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging

Funcții de bază

  1. True RMS full electrical measurement: 3-fază / single-phase voltage, actual, putere activă/reactivă/aparentă, factor de putere, frecvenţă; phase-wise & total active energy kWh, reactive energy kvarh, demand / peak demand, maxim & minimum value recording.
  2. Power quality: Total Harmonic Distortion (THD), harmonic analysis up to 15th order, sampling rate 32 samples per cycle.
  3. Interfață I/O: 2 intrări digitale (DIN), 1 static digital output (DO). DO configurable for pulse output (energy pulse), alarm output or remote control. DI for status acquisition or demand synchronization trigger.
  4. Funcție de alarmă: 15 groups of user-defined threshold alarms (supratensiune, subtensiune, supracurent, power limit violation, etc.), local indication + alarm report via communication.
  5. Comunicare: RS485, Modbus RTU protocol, up to 19200bps, compatible with PLC, SCADA and energy management systems.
  6. Afişa: LCD cu iluminare din spate, 6-line display, panel cutout mounting.

Specificații electrice cheie

ArticolSpecificații
Measuring VoltageLine-to-line: 10~480V AC; Phase-to-neutral:10~277V AC, 45~65Hz
Intrare curentăCT secondary 0.005~6A (5A/1A CT both supported)
Alimentare electricăAC:115~415V; DC:125~250V; Power consumption ≤5VA
PrecizieCurrent ±0.4%; Voltage ±0.3%; Power ±0.5%; Active energy Class 0.5S (IEC62053-22)
DIN12~36VDC, nominal 24VDC, 2.5izolare kV
DOStatic transistor output, supports pulse / alarm mode

Aplicație tipică

LV/MV switchgear, factory power distribution room, distribuția de energie a clădirii, computer room incoming cabinet. Used for power monitoring, energy consumption statistics, power quality monitoring and status acquisition; commonly used as spare parts for legacy project retrofits.

OEM Replacement Models (Cheie)

PM750MG → METSEPM5330 (RS485 Modbus); For Ethernet version: METSEPM5340 (Modbus TCP)

PM53 series is upgraded replacement for PM750, full & enhanced function coverage, identical panel cutout size for direct mounting. Modbus register addresses are incompatible, reconfigurare necesară. High-end alternative: PM8240/PM8243.

Lista de verificare comună pentru depanare

  1. No current / reversed current reading: CT S1/S2 reversed; CT secondary shorting link not removed; CT ratio not configured in meter.
  2. Modbus communication failure: Missing termination resistor, A/B wire reversal, mismatched address/baud rate; unstable meter supply.
  3. DO no action: Verify DO mode configuration (pulse/alarm) and polarity of external circuit.
  4. Abnormal harmonic reading: Cabluri slăbite, insufficient PT/CT accuracy, heavy distortion on load side.

Note suplimentare

Dimensiunea decupajului: 92×92mm, panel flush mounting

Standarde: IEC 62053, ANSI C12.20; compatible with 3P3L /3P4L / single-phase systems

Second-hand spare note: LCD backlight aging, damaged RS485 transceiver chip, parameter loss due to internal battery depletion.

  1. PM750MG Modbus RTU Register Summary (Holding Registers, 4xxxx, 16pic; Energy values as 32bit, ocupa 2 consecutive registers)

Protocol Notes: Modbus RTU, register starts at 40001 (Schneider standard). Some software uses 0-based addressing (40000), pay attention to offset. For float /32bit unsigned integer, high word first. Energy registers come with multiplier register; readings must be multiplied by multiplier factor.

Versiune de firmware: V3.050 (common firmware for PM700 series)

Modbus Address(4xxxx)Data TypeNumeDescriere
40001UINT16V1 Phase VoltagePhase voltage, multiplier register 40013
40002UINT16V2 Phase Voltage
40003UINT16V3 Phase Voltage
40004UINT16V12 Line Voltage
40005UINT16V23 Line Voltage
40006UINT16V31 Line Voltage
40007UINT16I1 Phase A CurrentActual, multiplier register 40014
40008UINT16I2 Phase B Current
40009UINT16I3 Phase C Current
40010UINT16Frequency Hz
40011UINT16Total Active Power kWPower multiplier 40015
40012UINT16Total Reactive Power kvar
40013UINT16Voltage Multiplier (10^n)de ex. value=2 → ×100
40014UINT16Current Multiplier (10^n)
40015UINT16Power Multiplier (10^n)
40016UINT16Total Power FactorRange 0~1000, divide by 1000
4,002,040,021UINT32Total Active Energy kWh40020=High word,40021=Low word; multiplier 40108
4,002,240,023UINT32Total Reactive Energy kvarh
4,002,440,025UINT32Total Apparent Energy kVAh
40030UINT16Phase A THDCurrent total harmonic distortion
40031UINT16Phase B THD
40032UINT16Phase C THD
40040UINT16DI StatusBit0=DI1,Bit1=DI2
40041UINT16DO StatusBit0=DO1
40045UINT16Alarm Status WordAlarm mask
40108UINT16Energy Multiplier (10^n)Energy reading ×10^n, Important!

Energy Calculation Example: 40020=0012, 40021=ABCD; 40108=2 → 0x0012ABCD ×10² = 1254860 ×100 = 125486000 Wh = 125486 kWh

Harmonics: 1~15th harmonic magnitudes, registers start at 40050, per-phase harmonic amplitude.

Communication Basic Parameters (PM750MG)

Protocol: Modbus RTU

Rata baud: 2400/9600/19200

Paritate: Nici unul / Ciudat / Chiar; Stop bit:1

Slave address: 1~247

RS485 Terminals: O, B; 120Ω termination resistor at bus end

  1. PM750MG vs METSEPM5330 Function & Wiring Migration Comparison Table
ArticolPM750MG (Old Meter)METSEPM5330 (Replacement Meter)Migration Notes
Cutout Size92×92mm92×92mmIdentical panel cutout, direct mounting
Alimentare electricăAC115~415V / DC125~250VAC100~415V / DC110~250VPower circuit can be reused directly
Tensiune de intrare10~480V line voltage10~480V line voltagePT secondary wiring unchanged; support 3P3L/3P4L
Intrare curentăCT secondary 0.005~6ACT secondary 0.005~6ACT S1/S2 wiring unchanged, CT ratio must be reconfigured on new meter
DIN2DIN (24VDC)2DIN (24VDC)External DI wiring can be kept
DO1-channel static transistor output2-channel relay DO⚠️Major difference! PM750MG uses transistor DO; PM5330 is dry contact relay. Original DO pulse/alarm circuit needs redesign, higher load capacity.
Harmonic MeasurementUp to 15th harmonicUp to 31st harmonicPM5330 enhanced power quality capability
Alarm Groups15 grupuri35 grupuriAlarm logic can be migrated, register addresses for alarms are fully different
ComunicareRS485 Modbus RTURS485 Modbus RTUPhysical A/B wiring unchanged. Register mapping is fully incompatible! PLC/SCADA program must be rewritten, old register addresses cannot be reused.
Energy TariffSingle tariff4 tariffsSupport time-of-use metering
PrecizieActive energy Class 0.5SActive energy Class 0.5SSame accuracy class
Înregistrarea datelorMax & Min valuesMax & Min + Event logPM5330 supports event logging

Retrofit Risk Checklist (Mandatory for Site Replacement)

  1. DO circuit modification: PM750MG transistor output cannot drive heavy load. PM5330 uses relay. If original DO sends pulse to acquisition module, verify dry-contact pulse compatibility with acquisition device.
  2. Host software program reconstruction: Register address, data arrangement and multiplier logic are all different. All tags for PLC / KingView / ForceControl / SCADA must be reconfigured; old program cannot be copied directly.
  3. Parameter re-entry: Raportul CT, Raportul PT, system type (3P3L/3P4L), pragul de alarma, Modbus address and baud rate all require manual setup. Parameters from PM750MG cannot be imported into PM5330.
  4. Real-time clock: PM750MG internal battery loses parameters on power loss; PM5330 retains parameters after power loss, only clock resets.

III. Terminal Wiring Comparison

PM750MG Terminal Layout

  1. L1 L2 L3 N Voltage Input
  2. CT1 CT2 CT3 Current Input
  3. Terminale de alimentare
  4. DI1 DI2 COM
  5. DO+ DO(tranzistor)
  6. RS485 A B

METSEPM5330 Terminal Layout

  1. L1 L2 L3 N Voltage
  2. CT1 CT2 CT3 Current
  3. Putere
  4. DI1 DI2 COM
  5. DO1, DO2 (Releu, independent dry contact)
  6. RS485 A B

Voltaj, actual, DI and RS485 cables may remain untouched; DO wiring must be rewired.

  1. On-site Replacement Procedure
  2. Power off and confirm safety; record original PM750MG parameters (CT/PT ratio, system type, alarm settings, parametri de comunicare).
  3. Remove old meter, keep voltage, CT, DI and RS485 cables.
  4. Install METSEPM5330, connect voltage, CT, DI and RS485; rework DO wiring separately.
  5. Power up, configure CT/PT ratio, system wiring type, Adresa Modbus, baud rate and alarm thresholds.
  6. Verify real-time measurements: Voltaj, actual, putere; confirm CT polarity is correct.
  7. Modify PLC / SCADA Modbus program, debug communication.
  8. Compare accumulated energy readings, run continuous test to verify metering accuracy.

Schneider PowerLogic PM700 Series Full Model List (All discontinued)

Series basics: 92×92mm panel mounting, True RMS measurement, THD, min/max logging. Definiția sufixului

MG: With RS485 Modbus RTU communication

CA: North American ANSI version (rarely used in China; Chinese projects prefer models without CA suffix)

P: 2-channel solid-state pulse output

Lista completă a modelelor

  1. PM700 Base model, nicio comunicare, fără ieșire de impuls
  2. PM700CA North American base version
  3. PM700MG Base measurement + RS485 Modbus
  4. PM700MGCA NA version + Modbus
  5. PM700P Base model + 2 solid-state pulse outputs, nicio comunicare
  6. PM700PCA NA version with pulse output
  7. PM700PMG Base + pulse output + RS485 Modbus
  8. PM700PMGCA NA version, puls + Modbus
  9. PM710 Base measurement + RS485 Modbus, no DI/DO
  10. PM710CA NA PM710
  11. PM710MG Mainstream domestic PM710 (Modbus)
  12. PM710MGCA NA PM710MG
  13. PM750 Top tier, RS485 Modbus, 2DI+1DO, alarm function
  14. PM750MG Most common domestic model (target model, Modbus version)
  15. PM750CA NA PM750
  16. PM750MGCA NA PM750MG

Comparison of 4 Modele de bază (Common for China Projects)

ModelConfigurație de bazăAplicație
PM700Basic electrical +THD/min-max, No comms, no pulseLocal display only, no SCADA connection
PM700PBasic electrical +THD, 2 pulse outputs, No commsEnergy pulse acquisition, no network
PM710MGBasic electrical +THD, RS485 Modbus, No DI/DORemote power acquisition, no status points needed
PM750MGFull electrical +THD+15th harmonic, RS485 Modbus, 2DI+1DO+threshold alarmsMonitorizarea puterii, remote status acquisition, ieșire de alarmă (largest installed base in China)

Întreruperea & Replacement Summary

APAC discontinuation date: 2015-04-30; Americas:2015-08-30. No new original production, only surplus / second-hand spare parts.

PM700 / PM700P / PM710 → METSEPM51xx (PM5100 series)

PM750 / PM750MG → METSEPM53xx (METSEPM5330 RS485; METSEPM5340 Ethernet TCP)

Observații suplimentare

  1. This series does NOT have PM720/PM730/PM740. Many documents are misleading. PM700 series only has four base platforms: PM700, PM700P, PM710, PM750.
  2. CA suffix = North American ANSI variant, differs in wiring logic & tensiune nominală. Avoid CA-suffix spares for China retrofits.
  3. All models share identical 92×92mm cutout and panel appearance; only internal I/O and communication hardware differ.