Transformator de curent Schneider 3CT-H1-100-C

Specificația completă a transformatorului de curent Schneider 3CT-H1-100-C (Dedicat pentru EOCR) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • Detalii despre produs

Full Specification of Schneider 3CT-H1-100-C Transformator de curent (Dedicat pentru EOCR)

  1. Interpretarea Codului Modelului
Segment de codSensDescriere
3CTSeria de produseThree-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1Cod specificațiePrimary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100Curent primar nominal100O (numerator of transformation ratio)
CMounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. Parametrii tehnici de bază
Categoria parametrilorCaietul de sarciniRemarcă
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
Clasa de precizieClasă 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10VAMax permissible secondary loop impedance 200mΩ
Gama de frecvente50/60HzGeneral industrial frequency
Tensiune nominală de izolațieAC 600VMaximum continuous operating voltage
Rezistenta la Tensiune2kV (50Hz, 1min)Insulation test standard between windings and earth
Rezistenta de izolare≥100MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
Dimensiunea de ansambluW150×H71×D55mmStructură compactă, space-saving installation
Tip de montareMontare pe panouCompatible with standard 35mm DIN rail
MaterialFlame-retardant engineering plasticCompliant with UL94 V0 standard
GreutateAproximativ. 0.58kgSingle unit weight
CertificareCE, ULConforms to international safety standards
Număr de ordine3CT-H1-100-CExclusive official Schneider order code
  1. Lista completă a modelelor (EOCR 3CT Series)
ModelRatioAperture ShapeBore SizeCurent nominalTip de montare
3CT-HS-75-C/Z75/5OCircularφ22mm75OC=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5OCircularφ25mm100OC=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5OPătrat30×30mm150OC=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5OPătrat35×35mm200OC=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5OPătrat45×45mm300OC=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5OPătrat55×55mm400OC=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
MarcaModelRatioPrecizieBurdenApertureCompatibilitate
Schneider

(SAMWHA)

3CT-H1-100-C100/5OClasă 110VAφ25mmPerfect match for EOCR
Siemens5SD7410-7100/5OClasă 110VAφ25mmUniversal type, adaptation test required
ABBCT-AR/100100/5OClasă 115VAφ25mmHigher burden capacity, EOCR compatible
ChintBH-0.66/100100/5OClasă 110VAφ25mmCost-effective domestic alternative
DeliciosLMZ1-0.66/100100/5OClasă 110VAφ25mmDomestic replacement, minor dimension difference

Note de înlocuire

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. Depanare & Întreţinere
Fenomen de eroareCauze posibileInspection StepsSoluții
No secondary outputCablaj greșit, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
Defecțiunea izolațieiDampness, insulation aging, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

Safety Rules

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. Aplicație & Cazuri

Scenarii aplicabile

EOCR motor protection system: Supracurent, undercurrent and phase loss protection

Distribuția energiei de joasă tensiune: Current monitoring and protection for circuits below AC 600V

Centru de control al motoarelor: Compact layout saves cabinet space

Industrial production lines: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400Hz) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

Typical Cases

Caz 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

Caz 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, economisire 50% spatiu de instalare, simplifying wiring and improving operational reliability.

  1. Selecţie & Installation Guidelines

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

Precauții de instalare

Keep correct S1(I+) and S2(eu-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

Maintenance Schedule

ArticolCicluStandard
Inspecție vizualăLunarNo crack, looseness or overheating mark
Terminal tighteningTrimestrialTorque range 2-3N·m
Test de izolareYearlyResistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 precizie, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.