Serie: Altistart 48, Controlul cuplului Soft Starter (Controlul cuplului TCS, ideal for pumps & fans to eliminate water hammer)
✅ Definiția codului modelului
ATS48 = Altistart 48 soft starter series
D62 = Rated current 62A (line connection); equivalent 107A for motor delta terminal connection
Q = Main circuit voltage version: AC 230~415V (Y version: 208–690V)
📌 Core Electrical Parameters
Tensiunea circuitului principal: Three-phase AC 230–415V
Curent nominal: 62O (line connection) / 107O (motor delta terminal connection)
Power rating at 400V:
Line connection (taxă standard): 30kW; sarcina grea: 22kW
Delta connection (taxă standard): 55kW; sarcina grea: 45kW
Alimentare de control: 110–230V AC
Start mode: Controlul cuplului TCS, max current limit 5×In (factory default 4×In)
Stop mode: Free coasting (implicit) / torque ramp soft stop (0.5~60s, preferred for pumps)
Pierdere de putere: 201W under standard duty; 153W under heavy duty
Clasa de protectie: IP20, montaj în dulap
Comunicare: Built-in Modbus-RTU (RJ45, RS485; baud rate: 4800/9600/19200bps); expandable to Profibus, DeviceNet via external gateway
Terminale I/O:
2 logic outputs LO1/LO2
3 ieșiri releu: R1 (vina), R2 (end of start), R3 (motor energized)
1 analogue output AO: selectable 0–20mA / 4-20mA
Dimensiuni (L×A×D): 190 × 290 × 235 mm; Greutate netă: 8.3kg
Standarde: IEC/EN 60947-4-2; Certificari: CCC, CE, UL, CSA etc.
🧩 Recommended Replacement Model
Direct OEM replacement: ATS480D62Y (New Generation Altistart 480)
62Un curent nominal, voltage range extended to 208–690V; control supply fixed at 110–230V AC; fully compatible with ATS48 functions, with built-in bypass logic and dual configuration. This is Schneider’s official upgrade solution.
Nota: ATS48Q series is replaced by ATS480Y series. Hardware terminals and program parameters differ; verify drawings and program before cabinet retrofit.
📦 Customs HS Code Reference
Primary declaration code: 84798997 (soft starter controller, widely used for export spare parts)
Alternative code used by some customs brokers: 85044090
Confirm with local customs before declaration.
🛠️ Aplicații tipice & Ghid de selecție
Suitable for centrifugal pumps, fani, compresoare, transportoare; mainly used to eliminate water hammer and mechanical shock.
Taxa standard: Pompe, fani obișnuiți; S1 duty cycle
Greutate: Concasoare, pornire-oprire frecventă, high-inertia loads. Select one size higher or adopt delta connection.
External bypass contactor is recommended to avoid continuous heating after bypass.
⚠️ Common Fault Troubleshooting (ATS48 Series General)
PHF: Pierdere de fază / dezechilibru de fază
PIF: Eroare de secvență a fazelor
DCF: Supracurent, scurtcircuit la ieșire, thyristor damage, bypass contactor sticking
InF / 5d2: Internal fault; if power cycle reset fails, repair is required
USF: Control supply loss
Use Schneider PowerSuite software to upload parameters and read the latest 5 înregistrări de erori.
📋 Adjacent Models in the Same Series (Q version, 230–415V)
ATS48D62Q → ATS480D62Y Retrofit Comparison List
Key conclusion: Power main circuit, mounting hole positions and relay terminals are fully interchangeable with existing wiring. The biggest risk is the control supply voltage: ATS48D62Q accepts 220–415V AC, while ATS480D62Y only supports 110–230V AC. If the original control power is taken from 400V line, a control transformer must be added.
- Terminale principale de alimentare (L1/L2/L3, T1/T2/T3, Bypass)
| Articol | ATS48D62Q | ATS480D62Y | Retrofit Instruction |
| Line input terminals | L1, L2, L3 | L1, L2, L3 | Same position, cable size and torque; reuse existing cables directly |
| Motor output terminals | T1, T2, T3 | T1, T2, T3 | Delta terminal connection is also supported; rated current remains 62A, equivalent 107A in delta connection |
| Bypass terminals | Built-in bypass wiring terminals | Built-in bypass wiring terminals | Bypass contactor wiring is compatible; ATS480 has enhanced bypass logic in parameters |
| Tensiunea circuitului principal | 230–415V AC | 208–690V AC | Wider voltage range for ATS480; fully workable on 400V systems; same unit for 690V applications |
| Dimensiuni de montaj | 190×290×235mm | Same width & înălţime, slightly deeper depth | Mounting holes match perfectly for direct in-place installation; check rear cabinet clearance |
- Control Terminal Mapping (Critic)
| ATS48D62Q Terminal | Funcţie | Corresponding ATS480D62Y Terminal | Observații |
| CL1 / CL2 | Alimentare de control | CL1 / CL2 | ⚠️Major difference: ATS48Q: 220~415V AC; ATS480: only 110~230V AC. If control power is taken from L1-L2 (400V), add a control transformer to step down to 220V. |
| STOP | Stop input | STOP | 2-sârmă / 3-wire control logic remains compatible |
| RUN | Run input | RUN | |
| LI3 | Programmable DI3 | DI3 | Renamed, aceeași funcție |
| LI4 | Programmable DI4 | DI4 | Renamed, aceeași funcție |
| R1A-R1C | Releu 1 (vina / programabil) | R1A-R1C | Normally open contact, default fault output. Max contact voltage for ATS480 is limited to 230VAC; evaluate original 400V relay circuits. |
| R2A-R2C | Releu 2 (end of start) | R2A-R2C | Commonly used for bypass drive; direct wiring reuse |
| R3A-R3C | Releu 3 (motor energized / programabil) | R3A-R3C | |
| AO1 / COM | Analogue output 0–20/4–20mA | AQ1 / COM | Renamed, functie identica |
| LO1, LO2 | Logic outputs | DQ1, DQ2 | Original LO1/LO2 → DQ1/DQ2; 24V active output requires external 24VDC supply |
| — | PTC motor temperature sensing | PT1/PT2/PT3 | ATS48 has no native PTC input; ATS480 adds built-in PTC/PT100 temperature sensing |
I/O Power Supplement: Digital inputs and DQ logic outputs on ATS480 require external 24VDC. The unit has built-in 24V terminals to power DI directly, consistent with ATS48 power supply scheme.
- Communication Interface Differences
| Articol | ATS48D62Q | ATS480D62Y |
| Onboard communication | Modbus RTU (RJ45 RS485) | Modbus RTU with extended baud rate: 1200~256000bps |
| Fieldbus expansion | External communication cards: Profibus, DeviceNet | Modular communication cards: Profinet, EtherNet/IP, Modbus TCP etc. |
| Software | PowerSuite | SoMove (Use the migration tool to convert parameter files; PowerSuite projects cannot be downloaded directly) |
| Addressing | Slave address 1–247 | Same address range; but Modbus register mapping not 1:1; verify PLC program register addresses |
⚠️ Important: PLC Modbus read/write programs cannot be copied directly. Some status words, fault codes and parameter indexes are changed. Simple start-stop & current reading can be adapted quickly; always verify registers for custom protection settings.
- Parameter Menu & Orientări privind migrația
- Core start parameters remain compatible (TCS torque control retained, critical for pumps & fani)
Initial voltage, ora de începere, opri timpul, limita curentului, oprire moale, current protection, motor thermal overload; parameter definitions are nearly identical.
- Menu structure revised:
ATS48: SEF, PRO, DRC, IO, POLIŢIST, CINA
ATS480: New tree menu with revised naming; no identical menu codes
- Recommended migration method:
Use the built-in ATS48→ATS480 conversion tool inside SoMove. Upload ATS48 parameter files, auto-convert then download to ATS480.
Avoid manual parameter entry, which easily omits protection settings, relay assignments and analogue calibration.
- Factory security update: ATS480 initializes on power-up, requiring language setup and security password; new encryption & firmware security policies added.
- Fault codes: Basic faults (PHF, USF) keep the same meaning; intern & communication fault codes are updated.
- Relay Contact Voltage Risk (Capcană comună)
ATS48 relay contacts: Max 400VAC
ATS480 on-board relay contacts: Max 230V AC only
👉 If R1/R2/R3 directly drive 400V contactor coils: Direct wiring is NOT allowed!
Soluţie: Add 220V intermediate relay isolation before driving 400V contactors.
- Delta Connection Compatibility
Both models support motor delta terminal connection (internal delta) to raise rated current; wiring topology is identical. Current conversion formula unchanged: Line In ×1.732 ≈ Delta equivalent current. ATS48D62Q and ATS480D62Y both have 62A main current, equivalent 107A in delta connection; power rating remains the same.
- On-site Retrofit Checklist (Follow in sequence)
CL1/CL2 control supply: Confirm voltage is 110–230V AC. If original power is 400V, install a control transformer.
Relay output loop: Check contactor coil voltage. Add intermediate isolation relays for 400V coils.
Power cables, bypass cables & împământare: Reuse directly; keep tightening torque unchanged.
DI/DO/AQ terminal one-to-one mapping; add PTC temperature wiring if needed.
Comunicare: Convert parameters via SoMove; verify Modbus registers and fault codes in PLC program.
2-wire/3-wire control: ATS480 auto-detects wiring mode; no extra control mode setting required.
Cabinet depth clearance: Ensure cabinet door & cable trunking do not collide with the new unit.
Remote keypad: Old VW3G48101 keypad is incompatible; replace with ATS480 remote keypad kit.
- Summary of Incompatibilities
- Control supply voltage range (highest risk item)
- Max AC voltage rating of relay contacts
- Software tool change: PowerSuite → SoMove; parameters must be converted
- Maparea registrului Modbus & fault codes are not fully consistent
- Newly added PTC temperature sensing, cyber security and dual-motor configuration functions
Schneider Altistart 48 (ATS48) Lista completă a modelelor
Series Note: ATS48 is discontinued (Last order date: 31 Dec 2023; service support until 31 Dec 2030). TCS torque-controlled soft starter, optimized for pump/fan water hammer suppression.
Definiția sufixului
Q: Three-phase 230~415V AC; supports internal delta terminal connection
Y: Three-phase 208~690V AC; delta connection is NOT permitted
Prefix breakdown: D (putere redusă), C (putere medie), M (putere mare)
- ATS48 Q Version (230–415V, delta connection supported, most popular for export)
| Model | Curent nominal (O) | 400V Standard Duty (Line Connection) kW | 400V Standard Duty (Delta Connection) kW | Dimensions W×H×D mm |
| ATS48D17Q | 17 | 7.5 | 15 | 160×275×190 |
| ATS48D22Q | 22 | 11 | 18.5 | 160×275×190 |
| ATS48D32Q | 32 | 15 | 22 | 160×275×190 |
| ATS48D38Q | 38 | 18.5 | 30 | 160×275×190 |
| ATS48D47Q | 47 | 22 | 45 | 160×275×190 |
| ATS48D62Q | 62 | 30 | 55 | 190×290×235 |
| ATS48D75Q | 75 | 37 | 55 | 190×290×235 |
| ATS48D88Q | 88 | 45 | 75 | 190×290×235 |
| ATS48C11Q | 110 | 55 | 90 | 190×290×235 |
| ATS48C14Q | 140 | 75 | 110 | 200×340×265 |
| ATS48C17Q | 170 | 90 | 132 | 200×340×265 |
| ATS48C21Q | 210 | 110 | 160 | 320×380×265 |
| ATS48C25Q | 250 | 132 | 220 | 320×380×265 |
| ATS48C32Q | 320 | 160 | 250 | 320×380×265 |
| ATS48C41Q | 410 | 220 | 315 | 400×670×300 |
| ATS48C48Q | 480 | 250 | 355 | 400×670×300 |
| ATS48C59Q | 590 | 315 | 450 | 400×670×300 |
| ATS48C66Q | 660 | 355 | 500 | 400×670×300 |
| ATS48C79Q | 790 | 400 | 560 | 770×890×315 |
| ATS48M10Q | 1000 | 500 | 710 | 770×890×315 |
| ATS48M12Q | 1200 | 630 | 800 | 770×890×315 |
- ATS48 Y Version (208–690V, line connection only, delta connection forbidden)
Model numbering matches the above list exactly; only suffix changes to Y:
ATS48D17Y / D22Y / D32Y / D38Y / D47Y / D62Y / D75Y / D88Y
ATS48C11Y / C14Y / C17Y / C21Y / C25Y / C32Y / C41Y / C48Y / C59Y / C66Y / C79Y
ATS48M10Y / M12Y
Y version covers up to 690V, suitable for mining & overseas 660V systems. Nominal current is identical to the same code Q model; delta terminal current expansion is not supported.
- OEM Upgrade Mapping (ATS48 → ATS480, Referință cheie)
Regulă: ATS48□□Q / ATS48□□Y → ATS480 same code + suffix Y
Exemple:
ATS48D62Q → ATS480D62Y
ATS48C41Q → ATS480C41Y
ATS48M12Y → ATS480M12Y
ATS480 only has Y suffix, voltage 208–690V, fixed control supply 110–230V AC; no Q version, no Q/Y split anymore.
- Dimension Group Summary (For cabinet retrofit verification)
- D17~D47: 160 × 275 × 190
- D62~C11: 190 × 290 × 235
- C14~C17: 200 × 340 × 265
- C21~C32: 320 × 380 × 265
- C41~C66: 400 × 670 × 300
- C79~M12: 770 × 890 × 315
- ATS48 Exclusive Accessories List
VW3G48101: Local keypad (model vechi, NOT compatible with ATS480)
VW3A4810: Modbus terminal kit (Modbus built-in; no extra card required for most cases)
VW3A4820: Profibus DP communication expansion card
VW3A4830: DeviceNet communication expansion card
VZ3V481 / VZ3V482 / VZ3V483 / VZ3V484 / VZ3V485: Cooling fan spare parts (split by power range)
- Memento-uri de selecție a tastelor
- Delta connection only available on Q suffix units. Equivalent current ≈ nominal current ×1.732. Restricții: partial soft-stop functions are limited; dual-motor switching is not supported.
- For heavy-duty loads (concasoare, pornire-oprire frecventă), select one power rating higher.
- Software difference: ATS48 uses PowerSuite; ATS480 uses SoMove. Parameter files cannot be imported directly and must be converted.
- Control supply difference: ATS48 Q/Y supports 110–415V AC; ATS480 only accepts 110–230V AC (the biggest retrofit risk).
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor


















NH42-63-318x560.png)



