Harmony RM22-L Level Control Relay (Conductive Electrode Liquid Level Monitoring)
Interpretarea modelului: RM22 series modular control relay; LG = liquid level single detection; 11 = 1 contact de schimbare (C/O); MR = power supply 24~240V AC/DC; MT version for 380~415V AC power supply
✅ Funcții de bază
Designed for conductive liquids (apă, canalizare, etc.) for automatic liquid level control. Two operating modes available:
- Fill Mode (Aprovizionare cu apă) : When liquid level falls below Min electrode → relay energizes, starts fill pump; when liquid level reaches Max electrode → relay de-energizes, stops pump.
- Drain Mode (Sump Pumping) : When liquid level reaches Max electrode → relay energizes, starts drain pump; when liquid level drops below Min electrode → relay de-energizes, stops pump.
It adopts resistance probe detection, judging liquid level based on liquid conductivity, not float switch. Adjustable detection sensitivity.
📋 Electrical Specifications
Tensiune de alimentare: 24~240V AC/DC (universal pentru AC & DC), 50/60Hz; operating range 20.4~264V
Consumul de energie: AC 5VA / DC 1.5W
Output contact: 1 changeover contact 1C/O (11-12 în mod normal închis, 11-14 deschis în mod normal), AC-15/DC-13, 8A@250VAC
Power-on delay: 0.6s
Probe circuit: Max. 12V AC at electrodes, electrode current ≤1mA; maximum probe cable length 1000m
Sensibilitate: St standard sensitivity 5kΩ~100kΩ, continuously adjustable via potentiometer
Montare: DIN rail, width 22.5mm
Protecţie: Sealing transparent protective cover to prevent on-site misadjustment; built-in diagnostic test button + status LED indicator
📌 Definiția terminalului
| Terminal | Descriere |
| A1,A2 | Relay working power supply |
| Min | Low liquid level electrode |
| Max | High liquid level electrode |
| C | Common reference electrode (reference pole) |
| 11 | Contact common terminal |
| 12 | Normally closed NC |
| 14 | Normally open NO |
Notă de cablare: 3 electrodes inside tank: C common pole, Min minimum liquid level, Max maximum liquid level. Only applicable to conductive liquids; not for insulating oil and other non-conductive media.
🛠️ Aplicații tipice
Aprovizionare cu apă & drainage tanks, sewage pools, turnuri de racire, water purification equipment, automatic pump start/stop, DIN rail mounting inside control cabinet.
⚠️ Model Differentiation & Referință de înlocuire
- RM22LG11MR: 24~240V AC/DC, single changeover contact
- RM22LG11MT: 380~415V AC power supply version
- RM22LA32MR: Dual-contact version, two-channel output
Înlocuire moștenire: RM35LM series (întreruptă, replace with RM22LG for new projects)
Principiul de funcționare al Schneider RM22LG11MR
Principiul de bază: AC resistive conductive liquid level detection (Tipul de conductivitate)
A low-voltage AC sensing signal is applied between electrodes. The device measures liquid resistance between two electrodes and compares it with the sensitivity threshold set on the front panel. The internal circuit drives output relay action.
Semnal AC de joasă tensiune pe partea sondei pentru a evita coroziunea electrolitică a electrozilor cauzată de DC.
- Circuit de detectare
Releul emite semnal de detectare AC de joasă tensiune (aprox.12V AC, curent <1mA) intre C (electrod comun), Min (nivel scăzut), Max (nivel înalt).
Electrodul scufundat de lichid → lichidul conductiv formează calea între C și electrod, rezistență scăzută;
Electrodul expus deasupra lichidului → circuit deschis, rezistenta extrem de mare;
Potențiometrul stabilește pragul de sensibilitate (5kΩ~100kΩ) : Rezistența măsurată < prag → lichid detectat; rezistență>prag → nu a fost detectat niciun lichid.
👉 Valabil doar pentru lichide conductoare. Nu se aplică pentru ulei, apă ultrapură (conductivitate foarte scăzută) și lichide izolante.
- Două moduri de operare (3-control punctual al nivelului de lichid cu logica memoriei histerezis)
1) Fill Mode (Machiaj cu apă)
Nivelul lichidului sub electrodul min: C-Min circuit open → internal relay energizes, 11-14 NU se inchide, starts fill pump.
Liquid level rises, submerges Min but not reaching Max: C-Min conductive, internal memory holds status, pump keeps running.
Liquid level reaches Max electrode: C-Max conductive → relay resets, 11-14 se deschide, pompa se opreste.
If liquid level drops but remains above Min, pump will not start. Two-point start/stop prevents frequent pump cycling.
2) Drain Mode (Sump Drainage)
Liquid level reaches Max electrode: C-Max conductive → relay energizes, 11-14 NU se inchide, starts drain pump.
Liquid level falls, leaves Max but still higher than Min: memory holds status, pump keeps draining.
Nivelul lichidului sub electrodul min: C-Min open → relay resets, pompa se opreste.
- Single Level Mode (Opțional, 2 electrozi)
Use only C+Max or C+Min for single-point alarm / controla. Small delay can be enabled to suppress false triggering caused by liquid wave and foam.
- Semnal intern & Ieșire
- A1/A2 supplies power to relay (24~240V AC/DC wide range), circuitul de alimentare este izolat electric de circuitul de măsurare al sondei;
- Circuitul de măsurare dobândește continuu rezistență între electrozi;
- Unitatea logică judecă starea în funcție de modul și semnalele electrozilor, conduce 1 contact de schimbare (1C/O, 11 comun,12 NC,14 NU);
- LED-ul panoului frontal indică starea ieșirii; butonul de testare încorporat simulează starea pentru punerea în funcțiune a buclei.
- Caracteristici cheie de design
- Detecție AC: Nicio tensiune DC aplicată electrozilor, previne electroliza, generarea de bule, coroziunea electrodului și detartrarea accelerată.
- Prag de rezistență reglabil: Adaptați la canalizare / apă curată cu conductivitate diferită prin butonul de sensibilitate.
- Logica memoriei histerezis: Necesită recunoașterea nivelului ridicat & puncte de nivel scăzut, evită comutarea frecventă a releului cauzată de fluctuații minore de lichid.
- Lungimea maximă a cablului electrodului de până la 1000 m. Atenție la interferența capacității rătăcite pentru cablurile lungi; declanșarea falsă tinde să apară în condiții de setare de sensibilitate ridicată.
- Corespondența defectelor bazată pe principiu
Scalare electrodului → rezistența echivalentă a lichidului crește peste prag → lichid prezent, dar dispozitivul nu raportează lichid;
Stratul de spumă conductivă → electrodul nu atinge nivelul real al lichidului, dar circuitul conduce → detectarea nivelului de lichid fals;
Contact slab al electrodului C → referința de măsurare pierdută, detectarea nivelului de lichid este invalidă.
Depanare pentru Schneider RM22LG11MR
Metoda de pre-diagnostic: Butonul de testare T de pe panoul frontal. Apăsați T când este pornit pentru a comuta starea ieșirii releului, pentru a distinge defecțiunea unității sau electrodul extern / defecțiune de cablare.
Vina 1: Niciun răspuns după pornire, LED-ul de alimentare stins
Simptom: Tensiune de alimentare A1/A2 normală, fara LED-uri, nu transmite nicio acțiune
Cauze
- Cablaj A1/A2 slăbit, contact slab terminal; polaritate greșită pentru alimentarea DC
- Input voltage out of 24~240V AC/DC operating range
- Internal power circuit damaged (lightning surge, transient overvoltage, scurt-circuit)
Soluții
- Opriți, measure voltage at A1/A2, tighten terminals; check polarity for DC supply
- Verify supply within rated range; check upstream MCB and fuse
- Replace unit if LED still off with correct supply voltage
Vina 2: Relay does not act when electrode submerged (liquid detected but no response)
Simptom: Liquid covers Max/Min electrode, relay status unchanged, pump does not start/stop
Cauze
- Electrode covered by scaling / sludge, liquid equivalent resistance exceeds sensitivity threshold
- Poor contact of C common electrode (cel mai frecvent), measurement reference lost
- Broken electrode cable, loose wiring at Min/Max/C terminals
- Sensitivity set too low (resistance threshold too small for sewage to conduct)
- Medium conductivity too low (apă ultrapură, insulating liquid, not suitable for this model)
Soluții
- Remove electrodes, curat / polish scale and sludge; regular electrode maintenance
- Priority check C electrode: ensure C is immersed in liquid and wiring secure
- Opriți, test cable continuity, tighten Min/Max/C terminals
- Increase sensitivity appropriately (raise resistance threshold, adjustable from 5kΩ~100kΩ)
- For low-conductivity water / ulei, use float level switch instead
Vina 3: Relay false action when liquid level below electrode (detects liquid with no actual liquid), pump starts unexpectedly
Simptom: Liquid level below electrodes, relay reports liquid present, pump starts mistakenly
Cauze
- Conductive foam / scum on liquid surface closes electrode circuit (common in sewage tank)
- Long electrode cable, stray capacitance causes false trigger (>300m is high risk)
- Sensitivity set too high, minor leakage triggers detection
- Electrode cable routed in parallel with power cable, interferențe electromagnetice
- Terminal condensation / scurgeri între electrozi
Soluții
- Ridicați poziția de montare a electrodului pentru a evita spuma; instalați deflector de spumă
- Reduce sensibilitatea; utilizați cablu ecranat pentru firul de semnal lung, scut cu un singur capăt împământat; separat de cablurile de alimentare
- Curățați condensul terminalului, îmbunătățește rezistența la umiditate a dulapului
Vina 4: Pornire-oprire frecventă a pompei, ştafetă de ştafetă / oscilaţie
Simptom: Nivelul lichidului stabil în interval, releul se activează și se dezactivează în mod repetat, pompa circulă rapid
Cauze
- Turbulență severă a lichidului, suprafața lichidă mătură electrozii în mod repetat; conducere intermitentă prin spumă
- Electrozi murdari, rezistență instabilă a electrodului
- Mod de funcționare greșit, logica histerezis dezactivată (doar un singur electrod cablat)
Soluții
- Extindeți electrozii, instalați manșon anti-supratensiuni; montați electrozii în zona liniştită a rezervorului
- Curățați electrozii, reglați fin sensibilitatea și evitați setarea critică
- Cablaj standard cu 3 electrozi (C+Min+Max), activați logica memoriei de histerezis încorporată, evitați controlul într-un singur punct
Vina 5: LED-ul releului normal, dar contactul de ieșire nu acționează, pompa nu pornește
Simptom: LED indicator de nivel corect, ci contactor din aval / pompa nu functioneaza
Cauze
- Cablare greșită a contactelor de ieșire (11/12/14 bornele conectate greșit)
- Sarcina de contact depășește valoarea nominală de 8A, eroziunea de contact / sudare / circuit deschis
- Fără alimentare pe circuitul de control din aval
Soluții
- Opriți și verificați cablarea contactelor: 11 comun, 12 NC,14 NU
- Apăsați butonul de testare T și măsurați continuitatea între 11-14; circuit deschis = contact deteriorat, înlocuiți releul
- Verificați alimentarea de comandă a pompei / contactor
Vina 6: Sudarea la contact, pompa funcționează continuu și nu se poate opri
Simptom: Nivelul lichidului ajunge în poziția de oprire, ieșirea rămâne închisă, pompa nu se poate opri
Cauze
- Supraîncărcare pe termen lung, arcul electric determină sudarea prin contact
- Fără absorbție de supratensiune pentru bobina contactorului, spate EMF deteriorează contactele
Soluții
- Înlocuiți imediat RM22LG11MR dacă contactele sunt sudate
- Adăugați un amortizor RC sau o diodă de roată liberă pentru sarcina inductivă (bobina contactorului) pentru a proteja contactele interne de 8A
Recommended On-site Troubleshooting Sequence
- Porniți, check power LED; LED off → inspect A1/A2 power supply
- Press T test button and observe output toggle
Output toggles by T: Unitatea sănătoasă, fault in electrode, cable or liquid medium
No response by T: Relay unit damaged, înlocuiți direct
- Verify C common electrode fully immersed and wiring tightened
- Clean electrodes and adjust sensitivity knob
- Check if signal cable runs together with power cable; use shielded cable for long distance
- Confirm mode selection: Fill (aprovizionare cu apă) / Scurgere (drenaj)
Întreținere preventivă
- Sewage application: Clean electrodes every 3~6 months to prevent scaling
- Keep electrode cable length within 500m where possible; reduce sensitivity and adopt shielded cable if longer
- Ensure cabinet moisture-proof to avoid terminal condensation leakage
- Install surge absorption device for inductive load (contactor) to protect 8A contacts
Schneider RM22 Harmony Modular Monitoring Relay Full Series List
Series common features: Montare pe șină DIN, width 22.5mm (RM22TG20:17.5mm); equipped with T test button, status LED, sealable transparent cover; evaluarea contactului: 8A@250VAC; suffix MR=24~240V AC/DC universal supply; MT=380~415V AC supply
- RM22L Conductivity Level Monitoring Relay (series of your model)
Conductive electrode liquid level detection for high/low level control of water tank and sewage sump
|RM22LG11MR|1C/O (1 schimbarea)|24~240V AC/DC|Model standard, your reference unit, sensitivity 5k~100kΩ|
|RM22LG11MT|1C/O|380~415V AC|High voltage supply level relay|
|RM22LA32MR|2C/O (2 schimbarea)|24~240V AC/DC|Dual-channel output, 3 sensitivity levels: LS/St/HS|
|RM22LA32MT|2C/O|380~415V AC|Dual-contact high voltage supply level relay|
- RM22T 3-phase Power Monitoring Relay (Secvența fazelor / pierdere de fază / 3-dezechilibru de fază / supratensiune & subtensiune)
Monitor 3-phase power supply for motor, pompa de apa, air compressor protection
|RM22TA31|2C/O|Secvența fazelor, pierdere de fază, 3-dezechilibru de fază|200~240VAC|
|RM22TA33|2C/O|Secvența fazelor, pierdere de fază, 3-dezechilibru de fază|380~480VAC|
|RM22TU21|2C/O|Secvența fazelor, pierdere de fază, subtensiune|200~240VAC|
|RM22TU23|2C/O|Secvența fazelor, pierdere de fază, subtensiune|380~480VAC|
|RM22TR31|2C/O|Secvența fazelor, pierdere de fază, dezechilibra, overvoltage/undervoltage with delay|200~240VAC|
|RM22TR33|2C/O|Secvența fazelor, pierdere de fază, dezechilibra, overvoltage/undervoltage with delay|380~480VAC|
|RM22TG20|2C/O|Secvența fazelor, pierdere de fază (compact version,17.5mm)|183~528VAC|
- RM22U Single-phase / DC Voltage Monitoring Relay (Supratensiune & Undervoltage monitoring)
AC/DC single-phase voltage monitoring for DC panel and single-phase power protection
|RM22UA32MR|2C/O|1~100V AC/DC|24~240V AC/DC|
|RM22UA33MR|2C/O|15~500V AC/DC|24~240V AC/DC|
|RM22UA33MT|2C/O|15~500V AC/DC|380~415V AC|
|RM22UB34MR|2C/O|Wide range single phase voltage|24~240V AC/DC|
- RM22J Current Monitoring Relay (AC current monitoring, suprasarcina / undercurrent)
Work with current transformer CT for motor load current monitoring
|RM22JA21MR|1C/O|0.1~5A AC|24~240V AC/DC|
|RM22JA32MR|2C/O|0.1~5A AC|24~240V AC/DC|
- Regula de codificare a modelului (RM22XXYYZZ)
- RM22: Series code Harmony modular monitoring relay
- XX: Function group
LG: Nivelul lichidului, single sensitivity
THE: Nivelul lichidului, multi-range sensitivity
TA/TU/TR/TG: 3-phase power monitoring
UA/UB: Single-phase voltage monitoring
JA: Current monitoring
- YY: Cantitatea de contact
11: 1 contact de schimbare (1C/O)
32: 2 contacte de schimbare (2C/O)
- ZZ: Power supply code
DL: 24~240V AC/DC universal (most widely used in engineering)
MT: 380~415V AC 3-phase high voltage supply
- Legacy Model Replacement (RM35 → RM22)
RM35LM old level relay → RM22LG / RM22LA
RM35TA/TU old 3-phase protection relay → RM22TA/TR/TU
RM35 series discontinued, select RM22 for new projects
- Tabel de selecție rapidă
| Aplicație | Model recomandat |
| Rezervor / nivelul de conductivitate al rezervorului, pornire-oprire o singură pompă | RM22LG11MR (modelul dvs. de referință) |
| Controlul nivelului lichidului care necesită două canale independente de alarmă/ieșire | RM22LA32MR |
| 3-motor de fază: pierdere de fază + secvența fazelor + protecție împotriva dezechilibrului | RM22TA33 |
| 3-putere de fază: pierdere de fază + secvența fazelor + peste & protecție completă la subtensiune | RM22TR33 |
| Monitorizarea curentului de sarcină a motorului (detecție CT) | RM22JA21MR |
| panou DC, o singură fază depășită & alarma de subtensiune | RM22UA33MR |