SIEMENS 3RT1056-6AP36 Power Contactor - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

SIEMENS 3RT1056-6AP36 Power Contactor - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

contactor/

SIEMENS 3RT1056-6AP36 Power Contactor

SIRIUS 3RT series 3-pole AC power contactor, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts Model Decoding 3RT1056-6AP36 3RT: SIRIUS power contactor series 10: Contactor standard (non-safety, non-reversing type) 56: Frame size S6, AC-3 400V 185A 6: Coil voltage 220…240V AC/DC A: Main circuit busbar connection P: Screw terminals for ...

  • Detalii despre produs

SIRIUS 3RT series 3-pole AC power contactor, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts

  1. Decodarea modelului

3RT1056-6AP36

3RT: SIRIUS power contactor series

10: Contactor standard (non-safety, non-reversing type)

56: Frame size S6, AC-3 400V 185A

6: Coil voltage 220…240V AC/DC

O: Main circuit busbar connection

P: Screw terminals for auxiliary contacts

36: Contacte auxiliare 2 Deschis normal + 2 În mod normal închis (2NU+2NC)

  1. Specificații electrice de bază
ArticolParametru
Numărul de poli principali3 stâlpi (3NU)
AC-3 (Motor load @400V)185O, 90kW
AC-1 (Resistive load @40℃)215O
Rated operating voltage UeMax. 1000V și
Coil control voltage Uc220~240V AC/DC (Wide-range AC/DC coil)
Contacte auxiliare2NU + 2NC, terminale cu șuruburi
Conexiunea circuitului principalBara de distribuție
Dimensiunea cadruluiS6
Grad de protectieFront IP00; IP20 with cover installed
Impulse withstand voltage8kV main circuit / 6kV auxiliary circuit
Temperatura mediului ambiant-25℃ ~ +60℃ (Degradarea este necesară peste 40℃)
  1. Domeniul de aplicare

On/off control of 3-phase motors such as fans, pompe de apa si compresoare

Control cabinets, central air conditioning, industrial production lines and power cabinets

Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression

  1. Modele alternative
  2. Intern SIEMENS înlocuire: 3RT5056-6AP36

Funcție identică, current rating and coil specification. Fabricate în China, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model

  1. Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
  2. Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)

Nota: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.

  1. Instalare & Ghid de întreținere
  2. Instalare: Montare verticală, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
  3. Circuitul principal: Busbar connection, tighten to specified torque per datasheet to prevent overheating and contact burning.
  4. Bobina: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
  5. Contact life: Under AC-3 motor duty, mechanical life approx. 10 milioane de operațiuni; electrical life depends on breaking current.
  6. Depanare

Coil energized but no pull-in: Măsurați tensiunea bobinei, check coil open circuit or mechanical jamming

Pull-in but no continuity on main circuit: Loose busbar or burned main contacts

Pălăvrăgeală / abnormal noise: Tensiune scăzută a bobinei, accumulated dust on iron core, oboseala de primăvară

  1. Codul HS vamal

85364900 (Electromagnetic contactor)

  1. Optional Spare Parts & Accesorii

Releu termic de suprasarcina: 3RU2156 series (for 90kW motor)

Surge suppressor: 3RT1955-1CD00 (Circuit RC), 3RT1955-1DG00 (Varistor)

Auxiliary contact block: 3RH1951 (for extra auxiliary contacts)

Arc shield & main contact repair kit: 3RT1956 contact assembly

Tabel de comparație: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36

Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.

Element de comparație3RT1056-6AP36 (Imported Version)3RT5056-6AP36 (Versiunea domestică)
Linie de produseSIRIUS 3RT1, global standard imported versionSIRIUS 3RT5, local domestic version
OrigineAmberg Factory, GermaniaSIEMENS low voltage plant in China (SEAL)
AC-3 @400V185O / 90kW185O / 90kW
AC-1 Resistive Load215O215O
Coil Specification220~240V AC/DC220~240V AC/DC
Contacte auxiliare2NU+2NC, terminale cu șuruburi2NU+2NC, terminale cu șuruburi
Conexiune la circuitul principalBara de distribuțieBara de distribuție
Dimensiunea cadruluiS6S6
Dimensiunea de ansamblu / Orificii de montareIdentic, direct interschimbabilIdentic, direct interschimbabil
Viața mecanică10 milioane de operațiuni10 milioane de operațiuni
Durata de viață electrică AC-3Aceleaşi (depends on breaking current)Aceleaşi (depends on breaking current)
Ambient Temperature Range-25℃ ~ +60℃-25℃ ~ +60℃
Accesorii compatibileCompatibilitate deplină: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, bloc de contacte auxiliare100% compatible with accessories of 3RT1056
CertificariCCC, CE, UL, CSA, suitable for overseas projectsCCC, CE; UL optional for certain batches, standard for domestic projects
NameplateGerman + English marking, Fabricat in Germaniachinez + English marking, made in China
Delivery Lead TimeLong, mostly forward order with unstable lead timeScurt, domestic stock available with fast delivery
PreţSuperiorLower with cost advantage
Scenarii de aplicareExport equipment, overseas projects, high-end foreign-invested projects, cases requiring imported componentsDomestic control cabinets, pompe de apa & fani, HVAC, general industrial automation
Performanță electricăIdentic, no derating differenceIdentic, no derating difference
Cod HS8536490085364900
Model Naming Definition3RT10: Global original series3RT50: Domestic localized series

Note cheie

  1. Interschimbabilitatea: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, bara colectoare, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
  2. Ghid de selecție

✅ Choose 3RT5056: Proiecte interne, budget control, livrare rapida; preferred for most domestic panel building projects.

✅ Choose 3RT1056: Mașini de export, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.

  1. Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.

Suplimentar: Shared Spare Parts List

Releu termic de suprasarcina: 3RU2156 series

Surge suppressor: 3RT1955-1CD00 / 3RT1955-1DG00

Main contact repair kit: 3RT1956

Additional auxiliary contact block: 3RH1951

Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36

Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185O). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.

  1. Common Applications (Both Models Applicable)

(1) Direct-on-line Motor Starting (Main AC-3 Duty)

Pompe de apă, pompe de canalizare, circulating pumps (tratarea apei, HVAC, clădire, industria chimică)

Compresoare de aer, ventilatoare mari, ventilatoare de evacuare a fumului

Transportoare, mixere, extrudere, concasoare (alimente, building material, minerit)

Chillers and large refrigeration compressors for central air conditioning

MCC motor control centre drawer units for 90kW motor circuits

(2) AC-1 Resistive Load

High-power heating elements, cuptoare cu rezistență

Main circuit switching of high-power circuits inside distribution cabinets

(3) AC-6B Capacitor Switching

Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)

Potrivire: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.

  1. Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
  2. Domestic panel projects, domestic factories, HVAC, aprovizionare cu apă & drenaj, general factory automation

Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.

  1. Domestic municipal projects: Stații de tratare a apelor uzate, municipal pump stations, building HVAC cabinets
  2. Domestic machinery OEM: Fani, compresoare de aer, chiller units sold in domestic market
  3. Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
  4. Retrofit replacement for old contactors, tight budget and fast delivery required

✅ Suitable for: Domestic projects without mandatory UL/CSA certification or German origin requirement

  1. Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
  2. Mașini de export & echipamente (export to Southeast Asia, Middle East, Europe and other overseas sites)

Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.

  1. New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
  2. Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
  3. High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
  4. Spare part replacement for legacy equipment: Original unit fitted with 3RT1056 and client requires identical OEM spare parts

✅ Suitable for: Mașini de export, overseas projects, client specified imported components, mandatory UL/CSA certification

  1. Evitarea capcanelor de selecție
  2. Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
  3. For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
  4. For export to Europe / America de Nord, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
  5. Heavy vibration & dusty heavy industry environments (minerit, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
  6. Scenarii neaplicabile

Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.

Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)

Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)

Prev:

Lasă un răspuns

Lăsaţi un mesaj