SIRIUS 3RT series 3-pole AC power contactor, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts
- Decodarea modelului
3RT1056-6AP36
3RT: SIRIUS power contactor series
10: Contactor standard (non-safety, non-reversing type)
56: Frame size S6, AC-3 400V 185A
6: Coil voltage 220…240V AC/DC
O: Main circuit busbar connection
P: Screw terminals for auxiliary contacts
36: Contacte auxiliare 2 Deschis normal + 2 În mod normal închis (2NU+2NC)
- Specificații electrice de bază
| Articol | Parametru |
| Numărul de poli principali | 3 stâlpi (3NU) |
| AC-3 (Motor load @400V) | 185O, 90kW |
| AC-1 (Resistive load @40℃) | 215O |
| Rated operating voltage Ue | Max. 1000V și |
| Coil control voltage Uc | 220~240V AC/DC (Wide-range AC/DC coil) |
| Contacte auxiliare | 2NU + 2NC, terminale cu șuruburi |
| Conexiunea circuitului principal | Bara de distribuție |
| Dimensiunea cadrului | S6 |
| Grad de protectie | Front IP00; IP20 with cover installed |
| Impulse withstand voltage | 8kV main circuit / 6kV auxiliary circuit |
| Temperatura mediului ambiant | -25℃ ~ +60℃ (Degradarea este necesară peste 40℃) |
- Domeniul de aplicare
On/off control of 3-phase motors such as fans, pompe de apa si compresoare
Control cabinets, central air conditioning, industrial production lines and power cabinets
Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression
- Modele alternative
- Intern SIEMENS înlocuire: 3RT5056-6AP36
Funcție identică, current rating and coil specification. Fabricate în China, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model
- Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
- Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)
Nota: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.
- Instalare & Ghid de întreținere
- Instalare: Montare verticală, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
- Circuitul principal: Busbar connection, tighten to specified torque per datasheet to prevent overheating and contact burning.
- Bobina: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
- Contact life: Under AC-3 motor duty, mechanical life approx. 10 milioane de operațiuni; electrical life depends on breaking current.
- Depanare
Coil energized but no pull-in: Măsurați tensiunea bobinei, check coil open circuit or mechanical jamming
Pull-in but no continuity on main circuit: Loose busbar or burned main contacts
Pălăvrăgeală / abnormal noise: Tensiune scăzută a bobinei, accumulated dust on iron core, oboseala de primăvară
- Codul HS vamal
85364900 (Electromagnetic contactor)
- Optional Spare Parts & Accesorii
Releu termic de suprasarcina: 3RU2156 series (for 90kW motor)
Surge suppressor: 3RT1955-1CD00 (Circuit RC), 3RT1955-1DG00 (Varistor)
Auxiliary contact block: 3RH1951 (for extra auxiliary contacts)
Arc shield & main contact repair kit: 3RT1956 contact assembly
Tabel de comparație: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36
Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.
| Element de comparație | 3RT1056-6AP36 (Imported Version) | 3RT5056-6AP36 (Versiunea domestică) |
| Linie de produse | SIRIUS 3RT1, global standard imported version | SIRIUS 3RT5, local domestic version |
| Origine | Amberg Factory, Germania | SIEMENS low voltage plant in China (SEAL) |
| AC-3 @400V | 185O / 90kW | 185O / 90kW |
| AC-1 Resistive Load | 215O | 215O |
| Coil Specification | 220~240V AC/DC | 220~240V AC/DC |
| Contacte auxiliare | 2NU+2NC, terminale cu șuruburi | 2NU+2NC, terminale cu șuruburi |
| Conexiune la circuitul principal | Bara de distribuție | Bara de distribuție |
| Dimensiunea cadrului | S6 | S6 |
| Dimensiunea de ansamblu / Orificii de montare | Identic, direct interschimbabil | Identic, direct interschimbabil |
| Viața mecanică | 10 milioane de operațiuni | 10 milioane de operațiuni |
| Durata de viață electrică AC-3 | Aceleaşi (depends on breaking current) | Aceleaşi (depends on breaking current) |
| Ambient Temperature Range | -25℃ ~ +60℃ | -25℃ ~ +60℃ |
| Accesorii compatibile | Compatibilitate deplină: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, bloc de contacte auxiliare | 100% compatible with accessories of 3RT1056 |
| Certificari | CCC, CE, UL, CSA, suitable for overseas projects | CCC, CE; UL optional for certain batches, standard for domestic projects |
| Nameplate | German + English marking, Fabricat in Germania | chinez + English marking, made in China |
| Delivery Lead Time | Long, mostly forward order with unstable lead time | Scurt, domestic stock available with fast delivery |
| Preţ | Superior | Lower with cost advantage |
| Scenarii de aplicare | Export equipment, overseas projects, high-end foreign-invested projects, cases requiring imported components | Domestic control cabinets, pompe de apa & fani, HVAC, general industrial automation |
| Performanță electrică | Identic, no derating difference | Identic, no derating difference |
| Cod HS | 85364900 | 85364900 |
| Model Naming Definition | 3RT10: Global original series | 3RT50: Domestic localized series |
Note cheie
- Interschimbabilitatea: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, bara colectoare, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
- Ghid de selecție
✅ Choose 3RT5056: Proiecte interne, budget control, livrare rapida; preferred for most domestic panel building projects.
✅ Choose 3RT1056: Mașini de export, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.
- Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.
Suplimentar: Shared Spare Parts List
Releu termic de suprasarcina: 3RU2156 series
Surge suppressor: 3RT1955-1CD00 / 3RT1955-1DG00
Main contact repair kit: 3RT1956
Additional auxiliary contact block: 3RH1951
Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36
Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185O). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.
- Common Applications (Both Models Applicable)
(1) Direct-on-line Motor Starting (Main AC-3 Duty)
Pompe de apă, pompe de canalizare, circulating pumps (tratarea apei, HVAC, clădire, industria chimică)
Compresoare de aer, ventilatoare mari, ventilatoare de evacuare a fumului
Transportoare, mixere, extrudere, concasoare (alimente, building material, minerit)
Chillers and large refrigeration compressors for central air conditioning
MCC motor control centre drawer units for 90kW motor circuits
(2) AC-1 Resistive Load
High-power heating elements, cuptoare cu rezistență
Main circuit switching of high-power circuits inside distribution cabinets
(3) AC-6B Capacitor Switching
Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)
Potrivire: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.
- Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
- Domestic panel projects, domestic factories, HVAC, aprovizionare cu apă & drenaj, general factory automation
Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.
- Domestic municipal projects: Stații de tratare a apelor uzate, municipal pump stations, building HVAC cabinets
- Domestic machinery OEM: Fani, compresoare de aer, chiller units sold in domestic market
- Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
- Retrofit replacement for old contactors, tight budget and fast delivery required
✅ Suitable for: Domestic projects without mandatory UL/CSA certification or German origin requirement
- Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
- Mașini de export & echipamente (export to Southeast Asia, Middle East, Europe and other overseas sites)
Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.
- New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
- Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
- High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
- Spare part replacement for legacy equipment: Original unit fitted with 3RT1056 and client requires identical OEM spare parts
✅ Suitable for: Mașini de export, overseas projects, client specified imported components, mandatory UL/CSA certification
- Evitarea capcanelor de selecție
- Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
- For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
- For export to Europe / America de Nord, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
- Heavy vibration & dusty heavy industry environments (minerit, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
- Scenarii neaplicabile
Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.
Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)
Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor


















NH42-63-318x560.png)