Numele complet: LOGO! DM8 230R Digital I/O Modul de extindere (LOGO! 8 Serie)
- Interpretarea Codului Modelului
6ED1055-1FB00-0BA2
6ED1055: Prefix for LOGO! 8 module de extindere în serie
1FB: DM8 230R, 115/230 Alimentare V AC/DC, 4DI/4DO relay output
00: Versiune hardware
0BA2: Versiune de firmware (LOGO!8 platform, incompatible with LOGO!6/7 (0BA6/0BA7) main units)
- Specificații electrice de bază
| Articol | Caietul de sarcini |
| Alimentare electrică | 115~230 V AC/DC (85~265 V AC; 100~253 V DC) |
| Intrare digitală DI | 4 canale, universal AC/DC signal |
| Logică 0: <40 V AC /<30 V DC | |
| Logică 1: >79 V AC />79 V DC | |
| Input delay: 0→1=40 ms; 1→0=75 ms | |
| Digital Output DO | 4 channels relay normally-open isolated contacts |
| Sarcină rezistivă: 5 O / 250 V și | |
| Sarcina inductivă: 3 O / 250 V și | |
| Minimum load current: 100 mA | |
| Max switching frequency: 2 Hz (resistive); 0.5 Hz (inductive) | |
| Montare | 35 mm șină DIN, lăţime 2 THE (35.5 mm) |
| Dimensiuni generale | W35.5 × H90 × D58 mm |
| Clasa de protectie | IP20 (for cabinet installation only) |
| Temperatura ambiantă de funcționare | -20 ℃ ~ +55 ℃, fara condens |
| Greutate | Aproximativ. 0.17 kg |
- Instrucțiuni de compatibilitate
✅ Supported Main Units: LOGO! 8 / 8.2 / 8.3 (0BA8 and later firmware)
Typical main unit models: 6ED1052-1FB08-0BA0, 6ED1052-1FB08-0BA1 and other 230 V main units
❌ Not Supported: LOGO! 6, LOGO!7 (0BA6/0BA7) main units. Backplane bus protocol differs, communication not available
- Definiția terminalului (Top: Putere & Intrare; Fund: Ieșire)
Upper Terminals (Alimentare electrică + Intrare)
L1, N: Module operating power supply
I1, I2, I3, I4: 4 intrări digitale
Lower Terminals (Ieșire releu)
Î1, Q2, Q3, Î4: 4 independent relay normally-open contact groups (2 terminals per channel, no common terminal)
⚠️ Important: Four relays are electrically isolated; different voltage circuits can be connected to each channel independently
- Scenarii tipice de aplicare
Small HVAC control, pompa de apa & fan control, circuite de iluminat, door interlock, simple conveyor lines. Ideal for sites equipped with existing 220 V AC sensors and contactor circuits without additional DC power supply.
- Ghid de selecție & Common Pitfalls
- Input signal must exceed 79 V to be reliably recognized as logic 1; low voltage signals cannot be used.
- Relay mechanical contacts not suitable for high-frequency switching. Select transistor output modules for frequent operation.
- Maximum expansion limit: A single LOGO! main unit can connect up to 4 module de expansiune.
- All input channels are recommended to use the same phase power. Do not connect I1~I4 across different phases to avoid false triggering caused by induced voltage.
- Install RC snubbers or freewheeling diodes in parallel with inductive loads (contactoare, electrovalve) to extend relay service life.
- Comparație cu modele de serie similare
6ED1055-1FB10-0BA2 (DM16 230R): 8DI+8DO relay version with doubled I/O capacity
6ED1055-1HB00-0BA2 (DM8 24R): 24 V DC powered version
Complete Technical Documentation for Siemens 6ED1055-1FB00-0BA2 (LOGO! DM8 230R)
- Informații de bază despre produs
Comanda nr.: 6ED1055-1FB00-0BA2
Numele produsului: LOGO! DM8 230R Digital Expansion Module (LOGO!8 Serie)
Funcţie: 4DIN / 4DO relay output expansion module
Poziționare: Extend I/O capacity for LOGO!8/8.2/8.3 main units, cannot run standalone
- Full Model Code Interpretation
6ED1055 1FB00 0BA2
- 6ED1055: LOGO! 8 series expansion module category
- 1FB: DM8 230R, 115~230 V AC/DC power supply, 4-channel AC input, 4 independent normally-open relay outputs
- 00: Revizuire hardware
- 0BA2: Versiune de firmware (LOGO!8 platform, incompatible with LOGO!6/7 (0BA6/0BA7) controlorii)
- Detailed Electrical Specifications
3.1 Alimentare electrică
| Parametru | Caietul de sarcini |
| Tensiune nominală | 115…230 V AC/DC |
| Operating Range | AC: 85~265 V; DC: 100~253 V |
| Gama de frecvente | 47~63 Hz |
| Module Power Consumption | Max. 2.2 VA |
3.2 Intrare digitală DI (I1, I2, I3, I4)
Cantitate: 4-channel universal AC/DC input
Logică 0: <40 V AC / <30 V DC
Logică 1: >79 V AC / >79 V DC
Input response delay: 0→1: 40 Domnișoară; 1→0: 75 Domnișoară
Tip de intrare: Passive AC voltage input, 24 V DC signals are not allowed
Maximum cable length: 100 m (unshielded cable)
3.3 Relay Output DO (Q1~Q4, isolated normally-open contacts)
⚠️ Four relays are mutually isolated; different voltage circuits can be wired to each channel
|Tip de încărcare|Evaluarea contactului|
| —| —|
|Sarcină rezistivă (Resistors, Iluminat)|5 O / 250 V și|
|Sarcina inductivă (Contactoare, Electrovalve)|3 O / 250 V și|
|Minimum Carry Current|100 mA (Poor contact performance may occur below this value)|
|Frecvența maximă de comutare|Sarcină rezistivă: 2 Hz; Sarcina inductivă: 0.5 Hz; Mechanical no-load limit:10 Hz|
|Prohibited Operation|Parallel connection of multiple output contacts for current boosting is forbidden|
- Mecanic & Parametrii de mediu
Montare: 35 mm șină DIN standard
Lăţime: 2 THE (35.5 mm)
Dimensiuni generale: W35.5 × H90 × D58 mm
Greutate: Aproximativ. 170 g
Clasa de protectie: IP20 (indoor cabinet use only)
Temperatura de operare: -20 ℃ ~ +55 ℃ (condensation prohibited)
Depozitare & Temperatura de transport: -40 ℃ ~ +70 ℃
Umiditatea relativă: 5% ~ 95%, fara condens
Rezistenta la vibratii: Conform IEC 60068-2-6
- Definiția terminalului
Upper Terminals (Alimentare electrică + Intrare)
L1, N: Module operating power supply 115~230 V AC/DC
I1, I2, I3, I4: 4 intrări digitale
Lower Terminals (Ieșire releu)
Q1 two terminals: 1st relay normally-open contact
Q2 two terminals: 2nd relay normally-open contact
Q3 two terminals: 3rd relay normally-open contact
Q4 two terminals: 4th relay normally-open contact
- System Compatibility Rules
✅ Supported Main Units (LOGO!8 Platform)
6ED1052-1FB08-0BA0, 6ED1052-1FB08-0BA1, all LOGO!8.2 / 8.3 230 V controllers
Maximum expansion quantity: Până la 4 expansion modules per LOGO! unitate principală
❌ Incompatible Equipment
LOGO!6 (0BA6), LOGO!7 (0BA7) legacy controllers. Backplane communication protocol mismatch, cannot be recognized.
- Software Configuration Requirements
Software de programare: LOGO! Soft Comfort V8.0 or higher
- Select corresponding expansion module model in project hardware catalog;
- I/O addresses of expansion modules automatically follow main unit addresses, no manual assignment required;
- Verify hardware list before program download to avoid errors caused by version mismatch.
- Certificari
CE, UL, CSA, CQC; Conform EN 61010-1, ÎN 55011 (EMC Class B, applicable for commercial building environments)
- Ghid de implementare a ingineriei (Official Specifications)
- RC snubbers must be connected in parallel with inductive loads (electrovalve, bobine de contactor) for AC circuits to extend relay lifespan.
- All input channels are recommended to adopt power supply from the same phase. Do not connect input terminals across different phases to prevent false triggering induced by stray voltage.
- Mechanical relay contacts have limited service life. Select transistor output modules (DM8 24T) for high-frequency start-stop applications.
- The module must be installed horizontally; vertical inverted installation is prohibited.
- Maintain heat dissipation clearance in control cabinets to avoid heat accumulation when multiple modules are mounted side by side.
- Comparison Table of Similar Models
| Comanda nr. | Model | Alimentare electrică | Configurare I/O | Tip ieșire |
| 6ED1055-1FB00-0BA2 | DM8 230R | 115~230 V AC/DC | 4D/4C | Releu |
| 6ED1055-1FB10-0BA2 | DM16 230R | 115~230 V AC/DC | 8D/8C | Releu |
| 6ED1055-1HB00-0BA2 | DM8 24R | 24 În DC | 4D/4C | Releu |
Engineering Application Cases for Siemens 6ED1055-1FB00-0BA2 (LOGO! DM8 230R)
Avantajele de bază: Direct acquisition of 115~230 V AC/DC signals; isolated relay contacts directly drive 220 V loads without additional DC power supply. Matched with LOGO! 230RCE main unit (6ED1052-1FB08-0BAx). Suitable for new construction and retrofit projects with fully AC control circuits on site.
I/O Allocation: 4DIN (220 V AC input) + 4 independent normally-open relay outputs
Caz 1: Dual Sewage Pump Automatic Alternation Control for Basement Sump (Building Water Supply & Drenaj)
- Project Requirements
Two 220 V sewage pumps for underground parking sump; high/low level float switches with 220 V contact signals.
High water level: Start pumps; ultra-high level: Dual pumps run simultaneously + audible & visual alarm;
Low water level: All pumps stop;
Automatic timing alternation between main/standby pumps for uniform wear; Manual/Auto switching and fault feedback function.
- Configurare hardware
Unitatea principală: 6ED1052-1FB08-0BA1 (LOGO! 230RCE, onboard 8DI/4DO)
Modul de extindere: 6ED1055-1FB00-0BA2 ×1 (DM8 230R)
- Atribuire I/O
Onboard Channels of Main Unit
I1: Auto/Manual Switch; I2: Manual Start Pump 1; I3: Manual Start Pump 2; I4: Oprire de urgență;
Î1: Contactor of Pump 1; Q2: Contactor of Pump 2;
Expansion Channels of DM8 230R
I5 (Module I1): Low Level Float Switch; I6 (Module I2): High Level Float Switch; i7 (Module I3): Ultra-High Level Float Switch; I8 (Module I4): Spare;
Q5 (Module Q1): Ultra-high level alarm buzzer; Q6 (Module Q2): Fault indicator light; Î7, Q8: Spare
- Solution Highlights
Float switches connect directly to module 220 V inputs without intermediate relays. Four isolated relay contacts can drive alarms and indicator lights separately with independent power circuits. No extra DC24V power supply required inside control cabinet, simplifying wiring.
Caz 2: Fresh Air & Exhaust Fan Interlock Control for Office Building (HVAC)
- Project Requirements
Four 220 V fresh air/exhaust fans with scheduled operation, temperature linkage, fan running feedback and fault alarm. Main unit onboard I/O insufficient, expanded by additional module.
- Hardware List
LOGO! 230RCE Main Unit + 6ED1055-1FB00-0BA2 ×1
- Module Utilization
DI Channels: 4-channel contactor running feedback signals (220 V);
DO Channels: Control contactors for extra two exhaust fans, fault audible & visual alarm, system running indicator light.
- Engineering Features
All control signals are 220 V și; isolated relay contacts allow different phase power feeding. Compact 2TE width saves DIN rail space for wall-mounted small control cabinets.
Caz 3: Timed Group Control of Plant Lighting (Building Lighting System)
- Requirements
Multiple groups of 220 V lighting circuits for plant road and perimeter lighting; Time-based staged switching via internal real-time clock; Local manual pushbutton override; Fault status feedback.
- Configurare hardware
LOGO! 230RCE (Built-in Real-Time Clock) + DM8 230R (6ED1055-1FB00-0BA2)
- Module I/O Assignment
DIN: 4-channel local manual pushbuttons (220 V signal);
DO: Drive AC contactor coils for 4 lighting groups.
- Motivul selecției
Module relay supports maximum 5 A resistive load, capable of directly driving small contactors. Lighting circuits are electrically isolated; single circuit failure will not affect others.
Caz 4: Simple Automatic Transfer Switch for Dual Power Supply of Small Pump Station
- Cerințe de proces
Two 220 V control power sources (principal + așteptare). Automatically switch to standby power upon main power failure; interlock to prevent parallel operation; status indication and fault alarm available.
- Configurare hardware
LOGO! 230RC Main Unit + 6ED1055-1FB00-0BA2
- Atribuire I/O
Expansion DI: Dual power supply voltage detection feedback signals;
Expansion DO: Control closing coils of two circuit breakers and switching completion indicator.
This configuration is widely adopted in power distribution renovation projects and listed as official typical application by Siemens.
Caz 5: Greenhouse Evaporative Cooling Fan & Spray Solenoid Valve Interlock Control (Agricultural Automation)
Requirements
Automatically activate cooling fans and spray solenoid valves when temperature & humidity exceed threshold; delay shutdown; local manual buttons and equipment fault feedback.
Hardware
LOGO! 230RCE + DM8 230R
Expansion DI: Manual pushbuttons, thermal relay fault feedback of fans;
Expansion DO: 220 V spray solenoid valve, standby fan contactor.
Observa
Solenoid valves belong to inductive loads. Install AC RC snubbers in parallel with relay outputs to extend relay operating life.
Caz 6: Poarta de siguranta, Conveyor and Warning Light Interlock for Light-Duty Conveying Equipment (OEM Machinery)
Logica de control
Conveyor allowed to start only when safety guard gate is closed; conveyor stops immediately once gate opens; warning light stays on and buzzer sounds intermittently during operation; emergency stop has highest priority.
Configurare hardware
LOGO! main unit I/O capacity insufficient, expanded via 6ED1055-1FB00-0BA2:
DIN: Safety door limit switch, oprire de urgență, butonul de resetare;
DO: Conveyor contactor, audible & visual alarm.
General Engineering Mandatory Specifications for All Cases
- ✅ Input Wiring Rule: Toate 4 DI channels must be powered by the same phase L + N. Do not wire I1~I4 across different live phases to avoid false triggering caused by induced voltage.
- ✅ Relay outputs are isolated normally-open contacts; different voltage circuits can be wired to each channel.
- ✅ Snubber components are mandatory for inductive loads (contactoare, electrovalve).
- ✅ Maximum 4 expansion modules can be cascaded with one LOGO! unitate principală.
- ✅ Only compatible with LOGO!8 / 8.2 / 8.3 main units (0BA8 firmware). LOGO!7 and earlier versions are not supported.
- ✅ Cannot operate independently; must be stacked on the right side of LOGO! main unit via expansion bus.