Modul de alimentare Siemens 6SL3224-0BE13-7UA0

6SL3224: G120 PM240 power-module series 0BE13: 400 V class, 0.37 kW heavy-duty rating 7UA0: No integrated Class-A EMC filter, built-in braking chopper Status: Întrerupt. Available only as spare-part; not for new-project selection. ⚠️ This is power-module only, CU control unit and BOP panel not included. Mandatorily used with CU240B-2 / CU240E-2 or equivalent control units for operation. ...

  • Detalii despre produs

6SL3224: G120 PM240 power-module serie

0BE13: 400 V class, 0.37 kW heavy-duty rating

7UA0: No integrated Class-A EMC filter, built-in braking chopper

Stare: Întrerupt. Available only as spare-part; not for new-project selection.

⚠️ This is power-module only, CU control unit and BOP panel not included. Mandatorily used with CU240B-2 / CU240E-2 or equivalent control units for operation.

Specificații tehnice de bază

ArticolCaietul de sarcini
Power Supply Input3‑phase AC 380‑480 V, 47-63Hz
Heavy‑Duty HO (0~+50 °C)0.37 kW, output current 1.3 A
Light‑Duty LO (0~+40 °C)0.55 kW, output current 1.7 A
HO Overload Capacity200 % for 3 s; 150 % for 57 s, cycle 300 s
Dimensiunea cadruluiFSA
Clasa de protectieIP20
Dimensiuni (H×L×D)173 × 73 × 145 mm
Greutate1.1 kg
Hardware FeaturesIntegrated braking chopper, este necesară rezistența de frânare externă; no built‑in line filter
Frecvența de ieșire0‑550 Hz

Aplicație

Modular general-purpose SINAMICS G120 inverter for fans, pompe, belt conveyors and general variable-speed applications.

Built-in braking chopper suitable for fast-stop and potential-energy loads (small lifting mechanisms) with external braking resistor.

Without integrated EMC filter. For industrial environments, external line filter is recommended: 6SE6400-2FA00-6AD0.

Înlocuire directă (New-Generation PM240-2)

PM240 legacy series discontinued. Frame-size-compatible replacement:

6SL3210-1PE11-8UL0 (PM240-2, 0.37 kW, fara filtru incorporat, integrated braking chopper, cadru FSA)

Nota: Existing CU control units are fully compatible; parameters can be migrated directly. Mounting dimensions are identical.

Second-hand / Spare-part Inspection Checklist

  1. Verificare vizuală: Burn marks on DC-bus and power terminals; abnormal fan noise.
  2. Test de izolare: Input-to-output, input-to-earth insulation resistance.
  3. Inverter stage: Measure forward/reverse diode drop of IGBTs to verify power semiconductors.
  4. Braking-chopper test: Check for short-circuit failure of braking power device.
  5. Commission with control-unit under load; verify 3-phase output current balance.

Hardware Manual Information for 6SL3224-0BE13-7UA0 (SINAMICS G120 PM240 FSA 0.37 kW)

Legacy discontinued PM240 power-module. Corresponding official hardware manual:

Document-ID: A5E36985441 SINAMICS G120 Power Module PM240 Hardware Manual, eliberare 07-2016, Siemens CSID: 109738501.

This manual covers FSA-FSF frame PM240 units, including full mechanical mounting, wiring and maintenance for 6SL3224-0BE13-7UA0. Original is English; no standalone full-Chinese edition. Use the Chinese G120 system manual as complementary reference.

📥 Official Download Access

  1. Siemens Industry Support Portal, search by document-ID: 109738501 for original PDF.
  2. Siemens Download Center, search part-number: `6SL3224-0BE13-7UA0`, filter hardware-installation manual.

⚠️ Do NOT confuse with PM240-2 manual (ID:109812684). Hardware structures differ; manuals are not interchangeable.

📋 Key Manual Excerpts for FSA-Frame 6SL3224-0BE13-7UA0

  1. Safety Preconditions

Protecție ESD: Wear anti-static wrist-strap during disassembly/assembly. După oprire, wait 5 minutes for DC-bus capacitor full discharge before opening housing.

Clasament IP20: Cabinet-mount only, outdoor installation forbidden.

  1. Instalare mecanică (FSA Frame)
  2. Orientarea montajului: Vertical upright installation. Horizontal or inverted mounting prohibited.
  3. Cabinet clearances:

Top ≥100 mm; Bottom ≥100 mm; 0 mm side clearance; rear surface flush with mounting back-plate.

Operating ambient: 0~+50 °C for heavy-duty; derating required above 40 °C.

  1. Cut-out dimension: FSA mounting cut-out W62 mm × H162 mm; overall unit size:173 × 73 × 145 mm.
  2. Assembly sequence: Fix power-module first, then snap-fit CU control-unit (CU240B-2 / CU240E-2). Ensure full latch engagement and secure communication connector contact.
  3. Definiția terminalului

L1/L2/L3: 3-phase 380-480 V AC mains input

U/V/W: Motor output

DC- / R2: Braking-resistor terminals. Braking chopper integrated; external resistor mandatory. Do NOT short-circuit. Recommended resistor order-code: 6SE6400-4BD11-0AA0 (0.37-1.5 kW PM240 compatible).

PE: Pământ protector. Reliable connection to cabinet protective-earth bar, cable cross-section ≥4 mm².

No built-in Class-A EMC filter. For high-EMI industrial sites, fit external line filter 6SE6400-2FA00-6AD0.

  1. Specificații cablu (FSA-0.37 kW)

Mains input cable: minimum 1.5 mm²; motor cable: 1.5 mm²; protective earth ≥4 mm².

Separate power cables and control wiring; maintain minimum 20 cm spacing. Shielded motor cable is recommended with 360-degree shield termination to cabinet earth bar.

  1. Pre-power-on Check-List
  2. Confirm CU control-unit is fully latched without loose fit.
  3. Verify braking-resistor wiring; no short-circuit between DC-and R2.
  4. No phase-to-phase or phase-to-earth short-circuit on input and output terminals.
  5. Confirm supply voltage AC380-480 V; 220 V single-phase supply must not be applied.
  6. Check insulation of motor cable and motor winding.
  7. Note de întreținere

FSA-frame PM240 has no field-replaceable fan unit. Periodically blow dust from cooling air-passages.

Retorque power terminals every 6 months; cuplul de strângere: 1.2 N·m.

⚠️ Critical Difference: Legacy PM240 vs PM240-2 replacement 6SL3210-1PE11-8UL0

Although FSA mounting holes are compatible, terminal layout and braking-circuit assignments differ. Do not apply PM240-2 installation manual to legacy 6SL3224-0BE13-7UA0.

Replacement Options for 6SL3224-0BE13-7UA0 (PM240 0.37 kW FSA)

Legacy PM240 officially discontinued. Hardware specification: 3-phase 380-480 V, no integrated EMC filter, built-in braking chopper, cadru FSA, HO 0.37 kW(1.3 O), LO 0.55 kW(1.7 O).

Categories: Official upgrade, OEM spare-part, higher-rating same-series spare, compact all-in-one drive, domestic functional equivalent.

  1. Siemens Official Upgrade (PM240-2, Preferred for New Retrofits)

✅ Order-Code: 6SL3210-1PE11-8UL0

Serie: SINAMICS G120 PM240-2; cadru FSA; 3-phase 380-480 V; fara filtru incorporat, integrated braking chopper.

HO rating:0.37 kW /1.3 A; LO rating:0.55 kW /1.7 A, power/current fully matched to original.

FSA mounting footprint compatible for drop-in installation in existing cabinet. Existing CU240B-2 / CU240E-2 control-units can be reused, parameters downloadable directly.

⚠️ Terminal layout and braking-resistor marking changed. Follow PM240-2 manual; do not copy legacy PM240 wiring. Minor depth difference; verify cabinet clearance.

Suffix explanation: -UL0 = without Class-A EMC filter; -AL0 = with integrated Class-A EMC filter (avoid mis-selection)

Common Wrong Selection to Avoid

❌6SL3210-1PE11-8AL0: Equipped with built-in EMC filter. Hardware condition mismatches original 7UA0; not recommended for direct swap.

  1. Spare-part Repair Solutions (No modification to program / cablare)
  2. Original part 6SL3224-0BE13-7UA0: Întrerupt. Only used stock / second-hand units available. High cost, limited supply. For emergency repair with zero wiring/parameter change and CU reuse.

Second-hand focus points: DC-bus capacitors, IGBT modules, integrity of built-in braking chopper.

  1. Up-rated same-PM240 spare: 6SL3224-0BE15-5UA0 (0.55 kW FSA)

Same FSA frame, nici un filtru, built-in braking chopper. Higher power rating supports derated operation for 0.37 kW motor. Mechanical installation identical with minimal parameter adjustment. Dezavantaj: cost mai mare.

III. Compact All-in-one Drive Replacement (Abolish split-type CU+PM architecture)

Original G120 is split power-module plus control-unit. Switch to monoblock G120C inverter, no separate CU required. Complete rewiring and PLC communication re-configuration needed.

6SL3210-1KE11-8UB2 (G120C, 0.37 kW, no integrated filter, 3-phase 380 V, built-in braking chopper)

Nota: Form-factor different, cabinet cut-out modification needed. Terminal assignment fully revised; legacy CU cannot be reused.

  1. Domestic Functional Equivalent (Optimizat din punct de vedere al costurilor, full re-commissioning required)

Suitable for new projects or full retrofit; existing CU discarded, control logic & communication re-engineered.

  1. Inovance MD290-0.37-T4: 3-phase 380 V, 0.37 kW, external braking-resistor support; V/F & control vectorial; Modbus capability, general-purpose for fans & transportoare.
  2. Inovance MD520-0.37-T4: High-performance vector drive.

Tabel de comparație a selecției de înlocuire

SoluţieNumărul pieseiCabinet Cut‑outWiring ModificationAplicație tipică
Upgrade oficial6SL3210‑1PE11‑8UL0FSA footprint compatibleMinor braking‑circuit re‑wiringProiect nou & machine retrofit (first choice)
Original Spare Stock6SL3224‑0BE13‑7UA0IdenticZero modificationEmergency breakdown repair
Up‑rated Same‑series Spare6SL3224‑0BE15‑5UA0IdenticZero modificationTemporary backup when original spare unavailable
All‑in‑one G120C6SL3210‑1KE11‑8UB2Cut‑out modification requiredComplete re‑wiringEliminate split‑module hardware
Alternativă internăInovance MD290‑0.37‑T4New cut‑outComplete re‑wiringCost‑reduced new‑build / full retrofit

⚠️ Critical Replacement Notes

  1. PM240-2 (6SL3210-1PE11-8UL0): Braking-resistor terminal labels changed. Legacy PM240 uses DC-/ R2; PM240-2 uses R1/R2. Strictly follow manual; mis-wiring destroys braking power device.
  2. Original unit without built-in EMC filter. Select -UL0 for replacement. -AL0 (cu filtru) may trigger interference faults under poor earthing conditions.
  3. CU parameters can be uploaded/downloaded to PM240-2, but verify motor maximum current and braking parameters after replacement.