Supapă de modulare electromagnetică Siemens MXG461.20-5.0 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

Supapă de modulare electromagnetică Siemens MXG461.20-5.0 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

electric/

Supapă de modulare electromagnetică Siemens MXG461.20-5.0

This is a 3-way/2-way solenoid proportional modulating valve with DN20 (3/4″) racord filetat si o valoare Kvs de 5.0 m³/h. Funcționează la o sursă de alimentare de 24 V AC/DC, cu semnale de control selectabile: 0-10V / 2-10V / 4-20mA. It features a positioning time of less than 2 secunde, a resolution of 1:1000 and an IP54 protection rating. ...

  • Detalii despre produs

This is a 3-way/2-way solenoid proportional modulating valve with DN20 (3/4″) racord filetat si o valoare Kvs de 5.0 m³/h. Funcționează la o sursă de alimentare de 24 V AC/DC, cu semnale de control selectabile: 0-10V / 2-10V / 4-20mA. It features a positioning time of less than 2 secunde, a resolution of 1:1000 and an IP54 protection rating. It is designed for mixing and straight flow control of cold and hot water in closed HVAC systems.

  1. Codul modelului Explicația
Segment de codDescriere
MXGCod seria produsului: MX stands for solenoid actuator; G stands for external thread connection, suitable for cold and hot water systems
461Model type code: ACVATIX™ series solenoid control valve, PN16 pressure rating
0.2Nominal diameter DN: 20mm (3/4 inch)
-5Kvs flow coefficient: 5.0 m³/h (flow rate of cold water at 1 bar pressure differential)
(Suffix P)Optional version: For media containing mineral oil (SAE05SAE50)
(Suffix U)Optional version: Equipped with NPT thread fitting set
  1. Specificatii tehnice principale
CategorieSpecificațiiObservații
Parametrii de bază
Valve TypeSwitchable 3-way mixing valve / 2-way straight valveNot applicable for diverting service
Tip conexiuneExternal thread G1¼B (ISO 228-1)DN20 corresponds to 3/4 inch
Nominal PressurePN16 (1.6MPa)Max. working pressure: 1000kPa
Flow CoefficientKvs=5.0 m³/h, Cv=5.9Cold water at 5-30℃, 1 bar pressure differential
Actuator Parameters
Alimentare electricăAC/DC 24V ±20% (SELV/PELV)Frecvenţă: 45-65Hz
Control SignalDC 0/2-10V or DC 4-20mA (DIP switch selectable)Input impedance: ≥100kΩ (voltage signal), 100Oh (current signal)
Position FeedbackDC 0-10V (Load resistance >500Oh)Non-wear inductive measurement
Positioning Time< 2 secundeRăspuns rapid
Stroke Resolution0.736111111High regulating accuracy
Clasa de protectieIP54Dustproof and splash-proof
Valve Body Parameters
Valve Body MaterialCast iron EN-GJL-250 (GG25)Plug: CrNi steel; Seat: Brass
Seal MaterialEPDM (Standard) / FPM (Tip P)For different media
Medium Temperature1-130℃For cold and hot water systems
Leakage RateA→AB: ≤0.02% Kvs; B→AB: ≤0.2% KvsAt Δp=0.1MPa
Poziția de montareVertical to horizontal installation availableNo special angle restrictions
Fail-Safe FunctionPort A→AB closes automatically upon power loss (întoarcere de primăvară)Safety protection feature
Physical Parameters
Dimensiuni (L1×L2×L3×H2)95×47.5×52.5×260mmUnder straight flow status
Greutate4.2kg
  1. Lista completă a modelelor din seria
ModelDNKvs (m³/h)Tip conexiuneApplicable MediumObservații
MXG461.15-0.6150.6External threadRece & apă fierbinteModel standard
MXG461.15-1.5151.5External threadRece & apă fierbinteModel standard
MXG461.15-3.0153External threadRece & apă fierbinteModel standard
MXG461.20-5.0205External threadRece & apă fierbinteModelul actual
MXG461.25-8.0258External threadRece & apă fierbinteModel standard
MXG461.32-123212External threadRece & apă fierbinteModel standard
MXG461.40-204020External threadRece & apă fierbinteModel standard
MXG461.50-305030External threadRece & apă fierbinteModel standard
MXG461.XX-XXP15-500.6-30External threadMineral oilVersion for oil media
MXG461.XX-XXU15-500.6-30External threadRece & apă fierbinteVersion with NPT fittings
MXF461.XX-XX15-650.6-50FlangeRece & apă fierbinteFlanged version
  1. Cross-Brand & Replacement Model Reference
CategorieModelMatching RateDiferențele
Modele echivalente SiemensMXG461.20-5.0P100%Only seal material changed to FPM, suitable for mineral oil
MXG461.20-5.0U100%Supplied with NPT thread fittings for easier installation
MXF461.20-5.095%Flanged connection type, different mounting method
Alternative interneMuyi MVC20-5.090%Identical functions, aproximativ. 60% of Siemens price, response time 2-3s
Chuanyi ZDLP-20K85%Electric actuator, slightly lower accuracy, IP65 rating
Imported CompetitorsHoneywell V5011P201090%Similar structure and price, positioning time around 2s
Danfoss AVTA20-5085%Slightly different flow characteristics, operating temperature 2-120℃
  1. Mediul de aplicare & Cazuri industriale

5.1 Scenarii aplicabile

Sisteme HVAC: Cold/hot water mixing control and fan coil unit temperature regulation for commercial buildings, hotels and hospitals

District Heating: Secondary hot water temperature control for residential communities and office parks

Industrial Temperature Control: Water flow regulation for chillers and heat pumps, cooling systems for data centers

Răcirea procesului: Temperature control loops for plastic molding machines and printing equipment

5.2 Scenarii nerecomandate

Media with solid particles (A pre-filter with filtration accuracy ≥100μm is required)

Vacuum systems or working conditions with high pressure differential (>300kPa)

Diverting flow applications (For mixing and straight flow only)

Corrosive media (Select MXG461S stainless steel version)

5.3 Cazuri tipice de aplicare

Caz 1: HVAC System of Commercial Complex

Project: HVAC water system renovation for a 30-floor shopping mall

Aplicație: Cold and hot water mixing control for air handling units on each floor, total 80 sets of MXG461.20-5.0

Outcome: Temperature control accuracy improved to ±0.5℃, energy consumption reduced by 18%, response speed tripled

Caz 2: Industrial Water Chiller

Equipment: 500RT screw chiller

Aplicație: Chilled water outlet temperature control (7℃), 4 units operated in parallel

Caracteristici: Matched with Siemens PLC for 0-10V proportional control, water temperature fluctuation stabilized below 0.3℃

  1. Depanare & Ghid de întreținere
Fenomen de eroareCauze posibilePași de depanareSoluții
Valve fails to operate1. No power supply1. Measure terminal voltage (24V±20%)1. Repair power circuit
2. Missing control signal2. Check 0-10V/4-20mA control signal2. Inspect controller output
3. Actuator failure3. Manual operation test (Turn handwheel clockwise)3. Replace ASE1 electronic module
Poor regulating accuracy1. Position offset1. Perform auto-calibration (Long press calibration button)1. Recalibrate the valve
2. Incorrect valve characteristic setting2. Check DIP switch (Linear / Equal percentage)2. Reset DIP switch
3. Impurities in medium3. Inspect filter cleanliness3. Clean the filter
Excessive leakage1. Aged seals1. Check seal condition1. Replace EPDM seals
2. Worn valve seat2. Measure leakage under closed status2. Replace valve seat assembly
3. Excessive pressure differential3. Confirm system pressure differential ≤300kPa3. Install bypass valve to reduce pressure difference
Abnormal feedback signal1. Faulty feedback wiring1. Measure feedback terminal voltage (0-10V)1. Repair feedback wiring
2. Damaged electronic module2. Check module indicator lights2. Replace electronic module
3. Defective inductive sensor3. Inspect sensor connection3. Replace inductive sensor

Maintenance Schedule

Articol de întreținereCicluOperation Content
Inspecție vizualăLunarCheck valve body and actuator for damage and loose connections
Filter CleaningTrimestrialClean inlet filter to prevent impurity ingress
Auto-CalibrationSemianualExecute auto-calibration to ensure positioning accuracy
Seal InspectionAnualCheck seal aging and replace if necessary
OverhaulFiecare 3 aniDismantle for internal inspection and replace wearing parts
  1. Ghid de selecție
  2. Three Key Selection Factors: DN size (match pipeline) → Kvs flow rate (meet system demand) → Medium type (Standard type for cold/hot water, Type P for mineral oil)
  3. Signal Selection: DC 0-10V for general control; DC 4-20mA for long-distance transmission (puternic anti-interferență)
  4. Sfaturi de instalare: Follow the flow direction marked on the valve body; do not use as diverting valve; 4-wire connection for power and signal ensures higher stability
  5. Fault Judgment: Automatic shutdown after power loss (întoarcere de primăvară) is a standard safety function; manual operation can quickly verify mechanical performance
  6. Informații de comandă

Model standard: MXG461.20-5.0 (BPZ:MXG461.20-5.0)

Accesorii recomandate: ALG203 thread fitting set (3 union nuts + 3 garnituri + 3 plain washers), Z155/20 blind flange set

Replacement Module: ASE1 electronic module (Applicable for DN15-32)

Supplementary Application Description

MXG461.20-5.0 is a DN20 solenoid proportional modulating valve with Kvs=5.0. It is mainly used for continuous and precise temperature control in closed cold and hot water systems. Featuring fast positioning (<2s) and high resolution (1:1000), it is only applicable for mixing and straight flow, not for diverting service.

  1. HVAC & Refrigeration (Primary Application)

Air Handling Units / Fresh Air Units: Proportional regulation of cold/hot water coils to stabilize supply air temperature (±0.5℃)

Fan Coil Units (FCU): Terminal temperature control for high-rise and commercial buildings, available for 2-way on/off or 3-way mixing flow

Chilled Water Systems: Water temperature regulation and bypass mixing control for chillers

Cooling Tower Control: Stabilize cooling water temperature and save energy

Computer Room Precision Air Conditioning: High-precision water temperature control for data center and equipment room cooling

  1. District Heating & Boiler Systems

Heat Exchanger Stations: Secondary hot water temperature regulation and mixing loop control

Radiant Floor Heating: Limit supply water temperature (35–45℃) and prevent overheating via 3-way mixing

Boiler Load Control: Stabilize hot water outlet temperature and follow system load changes

Domestic Hot Water (DHW): Mix cold and hot water to provide constant-temperature water (de ex. 45–55℃)

  1. Industrial Process & Special Media

Răcirea procesului: Precise cooling water temperature control for injection molding machines, printing machines and lasers

Mold Temperature Controllers: Proportional regulation for thermal oil and hot water circuits (Type P for mineral oil)

Mâncare & Industria farmaceutică (Sanitary Application): Closed-loop temperature control for pure water and hot water

Solar Water Heating Systems: Mix water from solar collectors and return water for constant water supply

  1. Typical Circuit Applications

3-way Mixing (Combining Flow): Mix high-temperature primary water and low-temperature secondary water to stabilize supply water temperature (most common application)

2-way Straight Flow: On/off or proportional regulation for coil/equipment inlet, automatic shutdown upon power loss for safety

Bypass / Differential Pressure Control: Stabilize system pressure difference and balance flow under partial load

  1. Disqualified Application Scenarios

❌ Media with solid particles (Pre-filter ≥100μm required)

❌ Diverting flow service (Mixing and straight flow only)

❌ Vacuum conditions, high pressure differential (>300kPa) or highly corrosive media

❌ Steam systems (Operating medium: cold/hot water and thermal oil, 1–130℃)

  1. Application Matching Based on Core Advantages

Răspuns rapid (<2s): Ideal for systems with fluctuating load requiring rapid temperature stabilization, such as HVAC terminals and process cooling

Rezoluție înaltă (1:1000): Suitable for high-precision temperature control scenarios including precision air conditioning, pharmaceutical and electronic manufacturing

Power-off Safety (Port A→AB Closed): Safety loop for heating and hot water systems to avoid overheating and scalding risks

Prev:

Lasă un răspuns

Lăsaţi un mesaj