Это 8-channel analog output module of the S800 I/O series for ABB Advant 800xA system. Он преобразует цифровые сигналы управления в стандартные промышленные аналоговые сигналы. (0/4-20мА или 0–10 В) для привода оборудования на объекте, такого как приводы и клапаны.
- Model Segment Definition (ABB S800 I/O Naming Rule)
| Модельный сегмент | Значение | Подробное описание |
| 3BSE | Product series prefix | General prefix for ABB industrial automation products, representing control system I/O modules |
| 38415 | Product part number | Numeric code for unique module identification |
| R1 | Revision number | Revision 1, standing for the first official version of the module |
| АО810В2 | Commercial model | AO = Analog Output, 8 = 8 каналы, 10 = Standard type, V2 = 2nd generation upgraded version |
- Основные технические характеристики (Official Data)
| Категория параметра | Technical Index | Примечания |
| Basic Characteristics | ||
| Number of Channels | 8 каналы (galvanically isolated) | Each channel can be individually configured for output type |
| Тип выхода | Текущий / Voltage selectable | 0-20мА, 4-20мА, 0-5В, 1-5В, 0-10В |
| Разрешение | 14-bit (including sign bit) | Accuracy ±0.1% Full Scale |
| Conversion Rate | 25ms per channel | Full channel update cycle: 200РС |
| Электрические параметры | ||
| Current Output Range | 0-25мА (Maximum drive capability) | Standard load 500Ω (4-20мА), High load 850Ω (0-20мА) |
| Voltage Output Range | 0-10В | Minimum load 1kΩ |
| Isolation Level | 250V AC between channels, 500V AC between channel and backplane | Соответствует МЭК 61010-1 safety standard |
| Источник питания | 24В Вашингтоне (±10%) | Power consumption <2W |
| Параметры окружающей среды | ||
| Рабочая температура | 0°С до +55°С | Температура хранения: -20°С до +70°С |
| Влажность | 5% к 95% (Non-condensing) | IP20 protection level |
| Vibration / Shock | 5г / 11РС (Half-sine wave) | Meet anti-interference requirements for industrial environments |
| Сертификаты & Согласие | CE, UL, CSA | Compliant with EN 61131-2, МЭК 61010-1 |
- Accessory List & Требования к установке
3.1 Mandatory Accessories (Must Be Used Together)
| Part Number | Имя | Функция |
| TU810/TU812/ TU814/TU830/ TU833 | Terminal Unit | Provide field wiring terminals for signal connection and isolation |
| TB810 | Terminal Board | Необязательный, for high-density wiring scenarios |
| SD811 | Shield Connector | For analog signal shield grounding and interference reduction |
3.2 Характеристики установки
Монтаж на DIN-рейку: 35mm standard rail complying with DIN EN 50022
Backplane Communication: Communicate with controller via S800 I/O bus backplane
Installation Clearance: Keep at least 10mm gap between modules for heat dissipation
Wiring Requirement: Use shielded twisted pair for analog signals, routed separately from power cables (spacing ≥15cm)
- Same Series Models & Cross-Brand Replacement List
4.1 ABB S800 I/O Analog Output Module Series
| Модель | Channels | Разрешение | Специальные возможности | Сценарии применения |
| АО810В2 (3BSE038415R1) | 8 | 14-bit | Стандартный тип, general output | Общий производственный контроль, экономически эффективный |
| AO815V2 | 8 | 16-bit | High precision with diagnostic function | Process control requiring high measurement accuracy |
| AO820 | 4 | 14-bit | Redundant output, fail-safe | Critical equipment control with redundant backup required |
| AO890 | 8 | 14-bit | HART protocol support | Smart instrument communication and remote diagnosis |
4.2 Cross-Brand Replacement Solution (Parameter Matching)
| Бренд | Модель | Channels | Разрешение | Тип выхода | Примечание о совместимости |
| Шнайдер | BMXDAI1605 | 8 | 14-bit | 0/4-20мА, 0-10В | Adaptable to Modicon M340/M580 system |
| Сименс | 6ES7 332-5HF00-0AB0 | 8 | 14-bit | 0/4-20мА, 0-10В | Compatible with S7-300 system, backplane replacement required |
| Роквелл | 1756-OF8 | 8 | 16-bit | 0/4-20мА, 0-10В | For ControlLogix system, different communication protocol |
| Одомашненный | HollySys FM148A | 8 | 14-bit | 0/4-20мА, 0-10В | Compatible with LK series DCS, высокая стоимость исполнения |
- Рекомендации по выбору & Replacement Tips
5.1 Дерево решений выбора (Quick Demand Matching)
- Channel Quantity: 8 channels satisfy most small and medium control loops; expand by parallel installation or select 16-channel models for more points.
- Accuracy Requirement:
General control: АО810В2 (0.1% accuracy) is sufficient
Precision control: Upgrade to AO815V2 (16-bit, 0.05% accuracy)
- Load Capacity:
Standard load (≤500Ω): Directly use AO810V2
High load (500-850Ой): Adopt 0-20mA mode instead of 4-20mA
- Специальные функции:
HART communication: Choose AO890
Redundant output: Choose AO820
Fail-safe: Choose AO825 (SIL certified)
5.2 Replacement Mnemonic Rule (3 Key Matching Elements)
Same channel quantity, no accuracy downgrade, meet load requirement, equivalent isolation performance
5.3 Replacement Precautions
- Protocol Compatibility: ABB S800 I/O adopts Profibus DP or ABB dedicated bus; cross-brand replacement requires system compatibility evaluation.
- Terminal Compatibility: Terminal units of different brands are not interchangeable and shall be replaced together.
- Software Configuration: Reconfigure module parameters after replacement to ensure consistent output range and fail-safe logic.
- Redundant System: Conduct compatibility testing first for critical applications to avoid system failure.
- Main Application Scenarios & Typical Cases
- Process Industry: Valve positioner control in chemical, petrochemical and natural gas processes
- Энергетика: Generator excitation control and transformer tap changer regulation
- Manufacturing: Production line speed control, давление / flow regulation
- Очистка воды: Pump inverter control and chemical dosing flow regulation
Typical configuration: AO810V2 module + TU812 terminal unit + SD811 shield connector, used to control 4-20mA pneumatic regulating valves for precise flow control.
Full List of ABB Analog Output Modules (Structured Quick Reference)
- S800 I/O Series (800xA/DCS System, Industrial Standard Application)
| Module Model | Full Part Number | Channels | Основные функции | Тип выхода | Разрешение | Типичное применение |
| AO801 | 3BSE020514R1 | 8 | Базовый тип, channel isolation | 0/4-20мА, 0-10В | 12-bit | General control, low-cost scenarios |
| AO810 | 3BSE008522R1 | 8 | Standard configurable type | 0/4-20мА, 0-5В, 1-5В, 0-10В | 14-bit | Общий производственный контроль, medium precision |
| АО810В2 | 3BSE038415R1/R2 | 8 | V2 upgraded version, higher stability | 0/4-20мА, 0-5В, 1-5В, 0-10В | 14-bit | Replacement for AO810, mainstream application |
| AO810V2-eA | 3BSE038415R2 | 8 | Optimized for Freelance system | 0/4-20мА, 0-10В | 14-bit | Freelance DCS system |
| AO815 | 3BSE008523R1 | 8 | High precision with diagnosis | 0/4-20мА, 0-10В | 16-bit | Process control & precision regulation |
| AO820 | 3BSE008546R1 | 4 | Redundant output, fail-safe | 0/4-20мА | 14-bit | Critical equipment control with redundancy |
| AO845 | 3BSE008547R1 | 8 | Redundant output with OSP preset value | 0/4-20мА | 14-bit | Safety-related systems, communication fault protection |
| AO845A | 3BSE018107R1 | 8 | AO845 upgrade, HART pass-through | 0/4-20мА | 14-bit | Smart instrument communication & remote diagnosis |
| AO890 | 3BSE008548R1 | 8 | Intrinsically safe, HART | 0/4-20мА (Ex ia) | 14-bit | Hazardous Area Zone 1/2, explosion-proof required |
| AO895 | 3BSE018108R1 | 8 | High precision intrinsically safe | 0/4-20мА (Ex ia) | 16-bit | Precision control in hazardous areas |
- S900 I/O Series (ATEX Explosion-Proof for Hazardous Areas)
| Module Model | Full Part Number | Channels | Explosion-Proof Grade | Основные функции | Тип выхода | Применимая область |
| AO920S | 3KDE175531L9200 | 4 | Ex ia IIC T4 | Isolated, intrinsically safe | 0/4-20мА | Zone 1/2, no HART required |
| AO920N | 3KDE175533L9200 | 4 | Ex ia IIC T4 | Non-isolated, intrinsically safe | 0/4-20мА | Zone 1/2, cost priority |
| AO920B | 3KDE175532L9200 | 4 | Ex ia IIC T4 | Enhanced isolated, intrinsically safe | 0/4-20мА | Zone 1/2, high anti-interference |
| AO930S | 3KDE175531L9300 | 4 | Ex ia IIC T4 | Isolated with HART | 0/4-20мА | Zone 1/2, smart instrument connection |
| AO930N | 3KDE175533L9300 | 4 | Ex ia IIC T4 | Non-isolated with HART | 0/4-20мА | Zone 1/2, HART + cost priority |
| AO930B | 3KDE175532L9300 | 4 | Ex ia IIC T4 | Enhanced isolated with HART | 0/4-20мА | Zone 1/2, HART + high anti-interference |
| DSAX452 | 3KDE175534L9452 | 8 | Ex ia IIC T4 | High-density, intrinsically safe | 0/4-20мА | Zone 1/2, multi-channel demand |
- AC500 PLC S500 Series (Modular PLC Application)
| Module Model | Full Part Number | Channels | Основные функции | Тип выхода | Разрешение | Compatible CPU |
| AO523 | 1SAP250200R0001 | 16 | High density, software configurable | 0/4-20мА, 0-10В, ±10 В | 12-bit | PM5xx series, AC500-eCo |
| AO562 | 1SAP250201R0001 | 4 | High precision, быстрый ответ | 0/4-20мА, 0-10В, ±10 В | 16-bit | PM5xx series, high-performance application |
| AX521 | 1SAP250100R0001 | 4AI/4AO | Mixed I/O, компактный | 0/4-20мА, 0-10В | 12-bit | Compact system with limited I/O points |
| AX522 | 1SAP250101R0001 | 8AI/8AO | High-density mixed I/O | 0/4-20мА, 0-10В, Pt100 | 12-bit | Medium system with multi-function demand |
| 500MBA02 | 1MRB150003R0001 | 8 | Базовый тип, экономически эффективный | 0/4-20мА, 0-10В | 12-bit | AC500 basic series |
- Other Series (Специальные сценарии применения)
4.1 Advant Master Series
| Module Model | Part Number | Channels | Функции | Приложение |
| AO800 | 3BSE008521R1 | 8 | Basic analog output | Advant Master DCS system |
4.2 Safety-Related Modules (SIL Certified)
| Module Model | Part Number | Channels | SIL Level | Функции | Приложение |
| AO825 | 3BSE018109R1 | 4 | СИЛ 2 | Fail-safe, redundant output | Safety Instrumented System (SIS) |
- Selection Mnemonic & Сравнение ключевых параметров
5.1 Selection Rule
System Matching → Channel Quantity → Accuracy → Explosion-Proof → Special Functions
System Matching: S800 for 800xA, S900 for explosion-proof, AC500 for PLC
Channel Quantity: 4/8/16 channels selected by control loop quantity
Точность: 12-bit (Базовый), 14-bit (Стандартный), 16-bit (Precision)
Explosion-Proof: Non-explosion-proof (S800), Intrinsically safe (S900)
Специальные функции: HART (AO845A/AO890/AO930), Redundant output (AO820/AO845), Fail-safe (AO825)
5.2 Key Parameter Comparison Table
| Ряд | Typical Accuracy | Max Load (4-20мА) | Isolation Level | Рабочая температура | Redundancy Support |
| S800 | ±0.1% | 500Ой (Стандартный) / 850Ой (Высокий) | 250V AC between channels | 0-55℃ | Partial models (AO820/AO845) |
| S900 | ±0.1% | 750Ой | Ex ia IIC | -20-60℃ | Необязательный |
| AC500 | ±0.2% | 600Ой | 500V AC between channels | 0-60℃ | Нет |
- Instructions & Примечания
- Правило именования модели:
AO = Analog Output
Digit = Channel quantity (например. 8 = 8 каналы)
Suffix V2 = 2nd generation upgraded version
Suffix S/B/N (S900) = Isolated / Enhanced Isolated / Non-isolated
Suffix -eA = Optimized for Freelance system
- Соответствие аксессуаров:
S800 series: Match with TU810/TU812/TU814/TU830/TU833 terminal units
S900 series: Match with SA910S/SA920S terminal units
AC500 series: Direct DIN rail mounting with integrated terminals
- Replacement Principle:
Higher version can replace lower version within the same series (AO810V2 replaces AO810)
Cross-series replacement requires system and protocol compatibility check
Accuracy and channel quantity shall not be lower than original module
Selected Application Cases of ABB Analog Output Modules (Full Industry Coverage + Конфигурация & Измерение значения)
- Власть & Energy Industry (Mainly S800 I/O, Высокая надежность & Redundancy Demand)
1.1 Thermal Power Plant Boiler Combustion Control System (AO810V2+AO845A)
End User: Large state-owned power plant (600MW unit)
Core Configuration:
Main Controller: AC800M redundant controller (PM865)
Analog Output: 8 pcs AO810V2 (feed water regulating valve, forced/draught fan inverter control) + 2 pcs AO845A (fuel valve redundant output)
Terminal Unit: 10 pcs TU812 + SD811 shield connector
Realized Functions:
Precisely control boiler feed water flow, air flow and fuel supply via 4-20mA signals to optimize combustion efficiency (excess air factor controlled at 1.15-1.2)
AO845A redundant output keeps fuel valve at safe opening during communication failure, соответствует МЭК 61850
Real-time regulation of turbine inlet valve to match grid load demand
Customer Benefits:
Boiler efficiency increased by 2.3%, saving about 12,000 tons of standard coal annually
NOₓ emission reduced by 18%, meeting ultra-low emission standard
System availability up to 99.99%, reducing unplanned shutdowns
1.2 Wind Farm Pitch Control System (AO815+AO820)
End User: Multinational wind power operator (100MW wind farm)
Core Configuration:
Pitch Controller: AC800M + 3 pcs AO815 (high-precision pitch angle control) + 3 pcs AO820 (redundant safety chain output)
Signal Type: 0-10В (pitch motor servo control) + 4-20мА (safety brake control)
Realized Functions:
Dynamically adjust blade angle (0-90°) according to wind speed and grid frequency to maximize wind energy capture
16-bit high precision of AO815 ensures pitch angle control error <0.1% and improves power generation efficiency
AO820 redundant output triggers safety brake rapidly in emergency to guarantee equipment safety
Customer Benefits:
Annual power generation increased by 3.2%, revenue increased by about 2.1 million CNY
Blade fatigue damage reduced by 25%, service life extended
Compliant with GL 2010 wind power safety standard and TÜV certified
- Нефтехимическая промышленность (S800/S900, Explosion-Proof & High Precision Demand)
2.1 Refinery Distillation Column Control System (AO810V2+AO890)
End User: Integrated refining & chemical enterprise (10 million tons/year refining capacity)
Core Configuration:
Distillation Unit: 800xA system + 6 pcs AO810V2 (reflux pump inverter, reboiler steam valve control) + 2 pcs AO890 (tower bottom temperature control for hazardous area)
Explosion-Proof Level: AO890 meets Ex ia IIC T4 for Zone 1 hazardous area
Realized Functions:
Precisely control reflux ratio (0.5-3.0) and tower bottom temperature ( ±0.2°C ) to maintain mass and energy balance
HART function of AO890 realizes remote diagnosis of smart valve positioner and early warning of sticking fault
MPC algorithm optimizes product purity through analog output modules
Customer Benefits:
Gasoline product purity increased by 0.5 percentage points, annual premium income about 8 million CNY
Steam consumption reduced by 12%, annual energy cost saving about 3.5 million CNY
Unplanned shutdown reduced by 4 times per year, avoiding loss of about 20 million CNY
2.2 Chemical Reactor Temperature & Pressure Control (AO815+AO845A)
End User: Fine chemical enterprise (pesticide intermediate production)
Core Configuration:
Reactor Control: AC800M + 4 pcs AO815 (heating/cooling system control) + 2 pcs AO845A (pressure regulating valve redundant output)
Тип выхода: 4-20мА (proportional valve control) + 0-10В (heating power control)
Realized Functions:
Temperature control accuracy up to ±0.1°C, pressure control accuracy ±0.02MPa, meeting fine chemical synthesis requirements
AO815 diagnostic function monitors valve status in real time and early warns leakage risk
Precisely control feeding rate and reaction time in batch production to improve product consistency
Customer Benefits:
Product yield increased from 92% к 99.5%, reducing waste disposal cost
Reaction cycle shortened by 15%, annual production capacity increased by 20%
Safety risk reduced and passed HAZOP analysis certification
- Manufacturing Industry (S800/AC500, Flexible Configuration & Быстрый ответ)
3.1 Automotive Painting Workshop Precision Control (AO815)
End User: Joint venture automobile manufacturer (300,000 vehicles annual output)
Core Configuration:
Painting Line: 800xA system + 12 pcs AO815 (12 sets of painting valves and coating transfer pump control)
Signal Type: 4-20мА (coating flow control, accuracy 0.01L/min)
Realized Functions:
Dynamically adjust nozzle flow based on vehicle 3D model data to achieve uniform coating thickness (±5μm)
HART communication monitors valve status in real time and early warns blockage or wear
Synchronize with robot trajectory to ensure painting quality on complex curved surfaces
Customer Benefits:
Coating rework rate reduced by 8%, annual coating cost saving about 4.5 million CNY
Production tact improved by 10%, annual capacity increased by 30,000 vehicles
VOCs emission reduced by 12%, meeting environmental standards
3.2 PV Module Laminator Temperature Control (АО810В2)
End User: Leading PV enterprise (5GW module annual output)
Core Configuration:
Laminator: AC500 PLC + 4 pcs AO810V2 (8 heating zones, 2 channels per module in parallel)
Тип выхода: 0-10В (heating power control, 14-bit resolution)
Realized Functions:
PID algorithm precisely controls heating plate temperature with uniformity ±0.5°C to ensure full cross-linking of EVA film
Automatically compensate heat loss by monitoring temperature difference of each heating zone
Link with vacuum system to realize precise control of pressure-temperature-time
Customer Benefits:
Module yield increased from 92% к 98%, annual loss reduction about 60 million CNY
Energy consumption reduced by 18%, annual electricity saving about 2.8 million CNY
Equipment maintenance cycle extended by 50%, reducing downtime
- Очистка воды & Environmental Protection Industry (AC500/S800, Energy Saving & Stable Operation)
4.1 Municipal Wastewater Treatment Plant Aeration System (AO810V2+AC500)
End User: Municipal wastewater treatment plant (500,000 tons daily treatment capacity)
Core Configuration:
Aeration Tank Control: AC500 PM573 + 6 pcs AO810V2 (12 Roots blower inverter control)
Control Logic: PID regulation based on dissolved oxygen (ДЕЛАТЬ) concentration (2-4mg/L)
Realized Functions:
Dynamically adjust blower speed according to inlet water quality and flow to precisely control aeration volume
Alternate operation of multiple blowers to balance equipment wear and extend service life
Link with online water quality analyzer to realize precise aeration and avoid over-oxygenation
Customer Benefits:
Blower energy consumption reduced by 25%, annual electricity saving about 1.8 million CNY
Sludge production reduced by 15%, lowering treatment cost
Effluent quality stably meets Class 1-A standard of GB 18918-2002
4.2 Waterworks Chemical Dosing System (AO523+AC500-eCo)
End User: County-level water supply company (100,000 tons daily water supply)
Core Configuration:
Dosing Room: AC500-eCo + 2 pcs AO523 (16 каналы, ПКК & PAM dosing pump control)
Тип выхода: 4-20мА (dosing pump frequency control, 0-50Гц)
Realized Functions:
Automatically calculate dosing amount based on raw water turbidity, pH and flow for precise dosing control
Link with sedimentation tank liquid level and effluent turbidity to realize closed-loop control
Historical data recording and trend analysis to optimize dosing strategy
Customer Benefits:
Chemical consumption reduced by 12%, annual cost saving about 350,000 CNY
Effluent turbidity stably below 0.5NTU, improving water supply quality
Manual operation reduced and labor intensity lowered
- Metallurgical Industry (S800, High Load & Anti-Interference)
5.1 Steel Hot Rolling Reheating Furnace Control (AO810+AI810)
End User: Large iron & steel group (hot rolled coil production line)
Core Configuration:
Reheating Furnace: AC800M redundant controller + 5 pcs AO810 (gas flow valve & air flow valve control) + 5 pcs AI810 (temperature acquisition)
Тип выхода: 4-20мА (proportional regulating valve control, load 800Ω)
Realized Functions:
Zoned furnace temperature control (1200-1250°С) with temperature deviation within ±5°C
Optimize air-fuel ratio (1.05-1.1) to improve combustion efficiency and reduce NOₓ emission
Link with rolling mill speed to realize precise billet temperature control
Customer Benefits:
Furnace thermal efficiency increased by 3%, annual gas cost saving about 5 million CNY
Steel billet oxidation loss reduced by 0.2%, annual output increase about 12,000 tons
Product thickness tolerance improved from ±0.15mm to ±0.08mm, upgrading product quality
- Application Selection Key Points (Выбор & Измерение значения)
6.1 Module Selection Matching Table
| Промышленность | Core Demand | Recommended Module | Ключевые особенности |
| Власть | Redundancy & Высокая надежность | AO845A/AO820 | Redundant output, fail-safe, МЭК 61850 compliant |
| Химическая | Explosion-Proof & Высокая точность | AO890/AO815 | Intrinsically safe, 16-bit precision, HART communication |
| Manufacturing | Быстрый ответ & Uniformity | AO815/AO810V2 | Быстрый ответ, 14/16-bit precision, channel isolation |
| Очистка воды | Energy Saving & Стабильность | AO810V2/AO523 | Multi-channel, низкое энергопотребление, PID optimization |
| Metallurgy | High Load & Anti-Interference | AO810 | 850 high load capacity, 500V isolation |
6.2 Core Value Formula
Application Value = Quality Improvement from Higher Precision + Cost Saving from Energy Reduction + Downtime Loss Reduction from Higher Reliability
6.3 Key Success Factors for Implementation
- System Matching: S800 for 800xA/DCS, AC500 for PLC, S900 for explosion-proof areas
- Complete Accessories: Terminal unit (TU810/812/830) + shield connector (SD811) are essential
- Parameter Optimization: Select current/voltage output according to load type and set proper fail-safe value
- Diagnosis Utilization: Enable HART function for predictive maintenance and lower operation cost
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи