(Standard part number: FWP-25A22F. The suffix FA is a trade designation; AMP25 means 25A and is not part of the original Итон model number.)
Тип продукта: aR IEC cylindrical high-speed semiconductor предохранитель (ceramic tube, ferrule terminals), 22×58mm size
Пояснение кода модели
ФВП: Bussmann IEC high-speed semiconductor fuse series
25: Номинальный ток 25А
А: аР (semiconductor protection, только защита от короткого замыкания; not suitable for sustained overload)
22: Size code for 22×58mm
Ф: No striker / no fuse indication (FI = with striker, can actuate microswitch)
ФА: Рынок / customs alias; official part number is FWP-25A22F
AMP25: Simple current marking of 25A, not part of original model
Основные электрические характеристики
Номинальное напряжение: 700В и / 700В Вашингтоне (МЭК/УЛ)
Номинальный ток: 25А
Разрывная способность: AC 200kA (symmetrical rms); DC 50kA @700Vdc
Fuse Class: аР (semiconductor short-circuit protection)
Предварительная дуга I²t: 37; Total clearing I²t @700VAC: 530
Номинальная рассеиваемая мощность: 6Вт
Форм-фактор: 22×58mm, ceramic tube, copper ferrules at both ends
Вес нетто: Приблизительно. 62.6г
Сертификаты & Согласие
UL Recognized JFHR2, CSA, CE, РоХС
Compatible Fuse Holder: ДЖМ70100 (matching safety fuse base)
Типичные применения
Short-circuit protection for DC busbars, DC drives, преобразователи частоты, выпрямители / преобразователи мощности, SCR and IGBT semiconductor devices. Widely used in PV energy storage, servo power supplies and UPS DC sides.
Примечание: aR provides short-circuit protection only and cannot replace gR overload protection.
Сравнение с аналогичными моделями
FWP-25A22F: No striker (эта модель)
FWP-25A22FI: With striker, triggers microswitch for alarm upon melting
FWP-25G22F: gR class (перегрузка + защита от короткого замыкания), 600Версия V
FWP-25A22F / FWP-25A22FI (22×58mm FWP aR Cylindrical High-Speed Fuse)
Applicable models: FWP-25A22F (нет нападающего) / FWP-25A22FI (с нападающим)
Basic Electrical Table
| Параметр | FWP-25A22F | FWP-25A22FI |
| Определение суффикса | F = No striker | FI = F + я, fitted with striker |
| Класс защиты | аР (semiconductor short-circuit protection, no overload protection) | аР |
| Номинальное напряжение переменного тока | 700V IEC | 700V IEC |
| Номинальное напряжение постоянного тока | 700В Вашингтоне | 500В Вашингтоне (critical difference!) |
| Номинальный ток | 25А | 25А |
| Отключающая способность переменного тока | 200кА, среднеквадратичное значение, симметричное | 200кА, среднеквадратичное значение, симметричное |
| Отключающая способность постоянного тока | 50kA @700Vdc | 50кА при 500 В постоянного тока |
| Предварительная дуга I²t | 37 А²·с | 37 А²·с |
| Total clearing I²t (700В и, pf=0.15) | 530 А²·с | 530 А²·с |
| Power Dissipation @In | 6Вт | 6Вт |
| Размеры | 22×58mm ceramic ferrule fuse | 22×58mm ceramic ferrule fuse |
| Масса | 62.6г | 61.6г |
| Fuse Holder | ДЖМ70100 (compatible with microswitch version) | ДЖМ70100 (microswitch version required) |
| Сертификаты | UL признан, CSA, CE, РоХС | UL признан, CE, РоХС |
| Striker Function | No fuse alarm output | Striker pops on melting, actuates microswitch for dry contact alarm |
Важное напоминание: The FI model is derated to 500V DC. Do not use FI for DC bus >500В; use F version only. For AC operation, both versions have identical characteristics, I²t and time-current curves.
Time-Current (T-C) Characteristic Notes (Техническая спецификация 720026)
Curves shown are nominal melt curves for aR fuses:
- Almost no operation under low-magnitude overload: aR is designed exclusively for semiconductor short-circuit protection, not conventional overload protection. Melting time is extremely long at 1.6×In (40А), so it cannot be relied on for overload protection.
- Short-circuit region (приблизительно. 10×В): Fast current-limiting melting with low I²t to protect IGBT/SCR. This is its intended operating range.
- Reference melt points (shared by FWP-25A22F / FI):
100А: Melting time ~10ms
250А: Melting time ~1ms
>500А: Sub-millisecond current-limiting operation
Curve feature: The T-C curve of aR fuse is very steep. It operates extremely fast under large short-circuit current while tolerating low multiple overloads for a long time.
The original T-C diagram is log-log plotted. F and FI of the same current rating share identical melt curves; differences are limited to DC voltage rating and striker construction.
I²t Correction Rule (Mandatory for Semiconductor I²t Coordination Check)
А 530 A²·s value above is total clearing I²t under 700V AC, коэффициент мощности 0.15.
When operating voltage is lower than 700V AC, actual total clearing I²t reduces, multiplied by correction factor K:
Eg=700Vac → K=1.0
Eg=600Vac → K≈0.82
Eg=480Vac → K≈0.64
DC I²t verification cannot directly reuse AC I²t values. Separate DC curve check is required, especially for FI limited to 500Vdc.
Striker FI Wiring & Fuse Holder Description
JM70100 has two configurations:
- Standard JM70100: For F version only, no microswitch
- ДЖМ70100 + microswitch module: For FI version. Striker triggers microswitch, typically 1NO+1NC for PLC alarm or trip interlock.
⚠️ The striker provides only a mechanical alarm signal. It does not change fuse protection characteristics or increase breaking capacity.
FWP-25A22F vs FWP-25A22FI Application Selection Table
| Сценарий применения | Рекомендуемая модель | Причина |
| DC bus 550~700V (накопитель энергии, PV DC side) | FWP-25A22F | FI limited to 500V DC, not permitted above |
| AC 690V frequency converter / выпрямитель, alarm required | FWP-25A22FI | Same AC parameters + функция будильника |
| AC application, no fault signal required, чувствительный к затратам | FWP-25A22F | Более низкая стоимость, simpler construction |
| DC ≤500V with fuse trip reporting | FWP-25A22FI | Meets DC voltage and alarm requirement |
Координация & Рекомендации по замене (Engineering Reference)
- Semiconductor protection check sequence: Device withstand I²t ≥ fuse corrected total clearing I²t
- Do not replace with gG general-purpose fuses; gG has much higher I²t and may destroy IGBTs.
- Domestic replacement must satisfy three criteria: 22×58mm size, aR class, 700Vdc rating (if DC circuit), and I²t close to 530. Many domestic aR fuses are only rated 500Vdc and cannot directly substitute F version.
- Temperature derating: 25A rating is based on 25℃ ambient temperature. Derate to 0.85In typically for 40℃ cabinet ambient.
FWP-25A22FA (FWP-25A22F, aR 700VAC/700VDC, 25А) Область применения
Основное позиционирование: aR high-speed semiconductor short-circuit fuse, low I²t current-limiting protection for IGBT, СКР, diode power devices, no overload protection.
- Original Datasheet Listed Applications
- DC Common Bus
Shared DC bus for multi-drive systems, busbar short-circuit protection. Widely used in energy storage, multi-servo and multi-inverter common-bus schemes. 700Vdc rating supports high-voltage DC bus.
- DC Drives
DC motor drives, high-power DC speed controllers, short-circuit protection for rectifier bridges and SCR thyristors.
- Power Converters / Rectifiers
AC-DC rectifier modules, SCR rectifier cabinets, active / passive rectifier units.
- Reduced Voltage Solid-State Starters
Thyristor circuit short-circuit protection inside solid-state soft starters.
- Extended Industry Applications
PV & Хранение энергии
PV inverter DC side, string inverter power loops
PCS DC bus, post battery cluster power circuit protection (≤700Vdc)
Преимущество: 700Vdc rating, strong DC breaking capacity, low I²t, ideal for DC side.
Variable Frequency & Сервоприводы
690V class three-phase inverter rectifier and IGBT module protection
High-power servo drives, multi-axis servo DC bus
Кран, металлургия, conveyor multi-drive common DC bus systems
UPS & Промышленные источники питания
Industrial online UPS, bidirectional DC/DC converters
High-frequency switching power supplies, гальваника & electrolysis power supplies
High-power SSR solid-state relay circuit protection
Сварка & Special Power Supplies
Inverter welding machines, plasma power supplies, high-frequency heat treatment power supplies, IGBT power board protection
Other Power Electronic Equipment
Active Power Filter APF, Static Var Generator SVG power modules
Energy feedback units, тормозные блоки (braking IGBT protection)
- Selection Differentiation (F vs FI)
FWP-25A22F (эта модель, нет нападающего): Preferred for DC bus >500В, no alarm demand, ценовое преимущество.
FWP-25A22FI (с нападающим): For AC or DC ≤500V, when fuse alarm, PLC interlock and fault reporting are required.
- Prohibited Applications
- General distribution circuits, освещение, отопительные нагрузки (aR does not protect overload; low overload will not melt and may damage downstream equipment)
- напряжение постоянного тока >700В
- Circuits requiring overload protection without separate thermal / electronic overload protection
- Direct replacement of gG distribution fuses (gG high I²t risks IGBT destruction)
Eaton Bussmann FWP Cylindrical High-Speed Fuse List (22×58mm series, matching FWP-25A22FA)
Примечание: A = aR (semiconductor short-circuit, 700VAC/700VDC); G = gR (full range, перегрузка + короткое замыкание, 690ВАК); suffix F = no striker, FI = with striker. FA in trade name refers to original F; AMPxx is only current marking.
- FWP-xxA22F / FWP-xxA22FI (аР, 700VAC/700VDC, 22×58mm)
| Номинальный ток | No Striker Model | With Striker Model | Предварительная дуга I²t | Total I²t @700VAC | Power Dissipation W |
| 20А | FWP-20A22F | FWP-20A22FI | 22 | 310 | 5.2 |
| 25А | FWP-25A22F | ФВП-25A22FI | 37 | 530 | 6 |
| 32А | FWP-32A22F | FWP-32A22FI | 55 | 780 | 8 |
| 40А | FWP-40A22F | FWP-40A22FI | 68 | 960 | 12 |
| 50А | FWP-50A22F | FWP-50A22FI | 155 | 2200 | 12.5 |
| 63А | FWP-63A22F | FWP-63A22FI | 280 | 4000 | 15 |
| 80А | FWP-80A22F | FWP-80A22FI | 550 | 7800 | 15 |
| 100А | FWP-100A22F | FWP-100A22FI | 1100 | 15600 | 16.5 |
⚠️ FI version DC rating derated to 500V. Do not use FI for DC >500В; use F version.
- FWP-xxG22F / FWP-xxG22FI (gR, 690ВАК, 22×58mm, перегрузка + короткое замыкание)
| Номинальный ток | No Striker Model | With Striker Model | Предварительная дуга I²t | Total I²t @690VAC | Power Dissipation W |
| 20А | FWP-20G22F | FWP-20G22FI | 26 | 165 | 4 |
| 25А | FWP-25G22F | FWP-25G22FI | 43 | 274 | 3.7 |
| 32А | FWP-32G22F | FWP-32G22FI | 97 | 616 | 4.9 |
| 40А | FWP-40G22F | FWP-40G22FI | 180 | 899 | 4.5 |
| 50А | FWP-50G22F | FWP-50G22FI | 283 | 1362 | 6.3 |
| 63А | FWP-63G22F | FWP-63G22FI | 516 | 2575 | 7.4 |
| 80А | FWP-80G22F | FWP-80G22FI | 1092 | 5448 | 8.4 |
| 100А | FWP-100G22F | FWP-100G22FI | 2065 | 10300 | 9.4 |
- Other FWP Cylindrical Ferrule Sizes
- 10×38mm: FWP-xxA10F / FWP-xxG10F, current range 4~32A
- 14×51mm: FWP-xxA14F / FWP-xxG14F, current range 4~50A
Protection class aR / gR same as above; Напряжение: 700В(аР) / 690В(gR)
- Other Eaton Bussmann High-Speed Semiconductor Fuse Series (Bolt / Blade Style, Высокий ток)
ФВП (bolt-on): 700В, 35~600А, аР, busbar and high-power converter
FWJ: 1000В, high-voltage DC, PV & energy storage high-power
ФВХ: 1000Vdc high-voltage DC fuse
FWA: 500В, small cylindrical high-speed
FWX: 250В, North American blade high-current
DFJ: Drive dedicated high-speed fuse
- Matching Fuse Holders (22×58)
ДЖМ70100: Standard holder (for F version)
ДЖМ70100 + microswitch module: For FI striker version, dry contact alarm output
- Model Code Summary
FWP Current + A/G + Size Code + F/FI
ФВП: Bussmann IEC high-speed semiconductor fuse
А: аР (short-circuit only, IGBT/SCR protection)
Г: gR (full range, перегрузка + короткое замыкание)
22 = 22×58mm; 14 = 14×51mm; 10 = 10×38mm
Ф: No striker; FI: With striker