Разбивка кода модели
MY2N-GS DC24V
- MY: Miniature General-Purpose Силовое реле Ряд
- 2: 2 столбы (DPDT, 2НЕТ + 2Северная Каролина, 2 Form C contacts)
- Н: Equipped with built-in LED operation indicator and mechanical status window (green LED for DC coils)
- GS: Upgraded new generation; direct drop-in replacement for discontinued MY2N-J
- 24 В постоянного тока: Rated coil voltage DC 24 В
Extended variants:
MY2N-D2-GS DC24V: Built-in freewheeling diode (suppresses coil back EMF, ideal for direct PLC driving)
MY2IN-GS: Equipped with locking test lever for circuit inspection; Suffix -R denotes export version with fully compatible pin layout
- Основные электрические характеристики
2.1 Параметры катушки (24 В постоянного тока)
Номинальное напряжение: округ Колумбия 24 В
Потребляемая мощность катушки: 0.7 Вт
Coil resistance (@23℃): ≈662 Ω
Operate voltage: ≤80% of rated voltage (≤19.2 VDC)
Release voltage: ≥10% of rated voltage (≥2.4 VDC)
Allowable voltage fluctuation range: 21.6~26.4 VDC
2.2 Contact Ratings (резистивная нагрузка, Nominal 5A)
Конфигурация контактов: 2 sets of Form C changeover contacts (DPDT)
Contact material: Silver (Ag)
Rated switching capacity:
✅ 5A / 250В и
✅ 5A / 30В Вашингтоне
Maximum continuous carry current: 10А (static steady-state conduction; frequent switching not recommended)
Minimum applicable load: 1мА / 5В постоянного тока (suitable for low-level signal circuits)
Maximum switching capacity: 1100Вирджиния (переменного тока); 120Вт (округ Колумбия)
2.3 Срок службы
Механическая жизнь: 50 миллион операций (18,000 циклов/час)
Электрическая жизнь (@5A resistive load): ≥500,000 operations (2,400 циклов/час)
Operate time ≤15ms; Release time ≤5ms
2.4 Диэлектрическая прочность & Изоляция
Coil ↔ Contacts: 2000В и / 1 мин
Contacts of different poles: 2000В и /1 мин
NO and NC contacts within the same pole: 1000В и /1 мин
Insulation resistance ≥1000 MΩ (measured at 500VDC)
- Определение контакта (Standard 8-pin plug-in layout)
Compatible sockets: PYF08A-E / PYFZ-08-Э
Приколоть 13, 14: Coil terminals (non-polarized for standard MY2N-GS; Polarity required for D2 version: Pin14=Positive, Pin13=Negative)
1st contact set: 9 (COM common), 1 (NC Normally Closed), 5 (NO Normally Open)
2nd contact set: 12 (COM common), 4 (NC Normally Closed), 8 (NO Normally Open)
Wiring principle: Energize coil pins 13-14 → 9-5 & 12-8 закрывать; Power off → restore NC path 1-9 & 4-12
- Compatible Socket List
| Socket Model | Тип терминала | Способ монтажа | Примечания |
| PYF08A-E | M3 screw terminals | DIN-рейка / винтовое крепление | Most widely used standard domestic socket |
| PYFZ-08-Э | Finger-safe screw terminals | DIN-рейка | Preferred for control cabinet safety design |
| PYF-08-Пута | Spring push-in terminals (tool-free) | DIN-рейка | Improves wiring efficiency |
Optional accessory: PYC-A1 locking clip (prevents relay loosening under vibration)
- Ambient Operating Limits
Рабочая температура: -40℃ ~ +70 ℃ (Нет конденсата, no icing)
Температура хранения: -55℃~+70℃
Humidity range: 5%~95%RH; condensation and long-term moisture ingress prohibited
Unsuitable environments: Тяжелая пыль, агрессивный газ, sustained severe vibration
- Рекомендации по выбору & Critical Restrictions
- Индуктивные нагрузки (электромагнитные клапаны, contactor coils)
Standard MY2N-GS has no built-in surge suppression. For DC inductive loads, select MY2N-D2-GS with integrated diode. Fit external RC snubber circuits for AC inductive loads, otherwise rapid contact erosion will occur.
- Overload forbidden
5A is the rated switching current. Avoid switching loads exceeding 6A continuously. Derate for motors and lighting loads with high inrush current.
- Do not drive coil via high-frequency PWM
Continuous PWM switching causes contact chatter and burnout. Select SSR solid-state relays for high-frequency control scenarios.
- Never mix AC & DC coil models
Powering DC coil relays with AC voltage leads to overheating and permanent damage; AC coil relays fail to pull in under DC supply.
- Not applicable for safety circuits
No forced guided contacts. Use dedicated safety relays such as G9SX for emergency stop and safety interlock loops.
- Типичные сценарии применения
PLC signal expansion, pneumatic solenoid valve control, small contactor driving, control cabinet logic interlock, lighting circuit switching, signal transfer on automated production lines.
- Drop-In & Upgrade Alternatives
- Direct replacement for legacy model: MY2N-J DC24V (identical pin layout and compatible sockets)
- Built-in freewheeling diode upgrade: MY2N-D2-GS DC24V
- 4-contact variant within the same series: MY4N-GS DC24V (14-pin socket PYF14A-E required)
Application Industry & Scenario Overview: OMRON MY2N-GS DC24V 5A
Core positioning: DC24V controlled intermediate relay with 2 переключающие контакты (DPDT). Mainly used for signal transfer after PLC outputs and low-power load switching; rated 5A/250VAC contacts, suitable for low-voltage control of high-voltage circuits.
Limitation reminder: Cannot be used as safety relay; not fit for high-frequency switching, high-inrush loads, explosive or heavily corrosive environments.
- Промышленная автоматизация (Largest Application Field)
- Custom automation equipment
Conveyor systems, transfer modules, stop cylinder control, directional switching for small pneumatic solenoids; signal interlock for photoelectric and proximity sensors, indicator light control.
- Станки
CNC auxiliary indicator lamps, lubrication pump on/off, door limit signal transfer, cooling fan control, auxiliary loops for tool changers.
⚠ Machine tools contain many inductive loads (электромагнитные клапаны). MY2N-D2-GS (built-in diode) is recommended to protect contacts and PLC modules.
- Упаковка & Печатное оборудование
Case sealers, этикетировщики, film winding mechanisms, small actuator switching, alarm buzzers and signal light circuits.
- Резина & Plastic Injection Auxiliary Equipment
Hopper heating fans, material level alarm, signal transfer for conveyor start/stop control.
- ОВК & Автоматизация зданий
Central air-conditioning control cabinets: Air damper actuators, differential pressure alarms, auxiliary fan control, anti-freeze protection signal interlock
Fresh air systems, вытяжные вентиляторы, cooling tower auxiliary circuits
Zone lighting control; fire alarm signal transfer (only signal relay, NOT main fire protection circuit)
- Логистика & Складское оборудование
Automated warehouses, sorting conveyor lines, peripheral control cabinets for AGVs
Конвейеры, sorting baffle cylinder control, logic expansion for photoelectric sensors
Indicator lights and alarm driver for warehouse access control
- Очистка воды & Environmental Equipment
Dosing systems, auxiliary control of small water pumps, high/low level signal transfer, aeration fan auxiliary circuits, signal switching for online water quality monitoring cabinets.
Environmental note: Anti-condensation treatment is mandatory inside humid cabinets to prevent contact oxidation and poor connectivity.
- Энергия, EV Charging & PV Auxiliary Cabinets
- Auxiliary fault alarm and cooling fan control for small PV combiner boxes
- Signal transfer inside AC charging station control boards, fault indicator lights and auxiliary contactor coil driving
Forbidden: Do NOT switch high-voltage DC main circuits; only permitted for low-voltage control loops.
- Пищевое оборудование & Central Kitchen Equipment (Key Target Segment)
Vegetable washing equipment, конвейеры, small exhaust fans, warning lights
Smart Canteen & Central Kitchen Electrical Cabinets: Alarm signal for transparent kitchen monitoring, automatic door control, auxiliary ventilation control, solenoid valve drive for cleaning machines
✅ Advantage: DC24V is standard industrial voltage, unified with HMI, PLC and sensor power supply, supporting standardized cabinet wiring.
- Rail Support & Off-Highway Mobile Equipment
Onboard control cabinets for construction machinery, small tunnel ventilation control boxes, barrier and gate control cabinets; access control lock and traffic light drivers.
Vibration warning: Fit PYC-A1 locking clip to avoid relay disconnection.
- Лаборатория & Testing Instruments
Aging test equipment, thermostats, small test fixtures; электромагнитные клапаны, low-power heating loads and alarm signal switching.
Compatible Load Classification
✅ Recommended Loads
- DC24V miniature solenoid valves, indicator lamps, buzzers
- 220VAC small fans, lighting loads, AC contactor coils
- Passive dry contact signal transmission
❌ Not Recommended / Strictly Forbidden Loads
- High-power motors and heating elements (inrush current far exceeds 5A rating)
- Loads with switching frequency >10 cycles/minute (accelerates contact wear)
- Hazardous explosive zones (нет сертификата взрывозащиты)
- Safety interlock and emergency stop circuits (use dedicated safety relays e.g. G9SX)
Selection Matching Advice
- Driven by PLC transistor outputs → Priority: MY2N-D2-GS (built-in diode, prevents back EMF damage to PLC)
- Driven by relay-output PLC → Standard MY2N-GS directly applicable
- If driving inductive loads such as contactors and solenoids without diode version, fit external surge absorption components.
Монтажные размеры: OMRON MY2N-GS DC24V (5А) Official Standard Values
- Relay Body (without socket, 8-pin plug-in)
Maximum overall dimension (L × W × H): 28.0 × 21.5 × 36.0 мм
Глубина (front-back): ≤28 mm
Ширина (left-right): ≤21.5 mm
Высота (excluding pins): ≤36 mm
Булавки: 8 cylindrical plug pins, standard 8-pin layout for MY2 series.
- Dimensions of Common DIN-mount Sockets
1) PYF08A-E (Standard widely used socket)
Overall dimension: 72 (Д) ×22 (Вт) ×30 (ЧАС) мм
Монтаж: 35mm standard DIN rail or screw fixing
Screw mounting holes: 2 шт., Φ4.2×5 slotted hole, center distance 44 мм
Terminal screw specification: М3
2) PYFZ-08-Э (Finger-safe safety socket)
Overall dimension: 72 (Д) ×23 (Вт) ×31 (ЧАС) мм
3) PYF-08-Пута (Push-in spring terminal socket)
Overall dimension: 72 ×23 ×31 mm
Reference total height: Relay fully inserted into socket ≈64 mm (for cabinet layout reservation)
- PCB Mount Alternative (Optional PY08-02 soldering socket)
For PCB soldering installation: PY08-02 PCB socket, fully pin-compatible with MY2N-GS.
- Practical Layout Parameters for Control Cabinet Design
- Minimum side-by-side mounting clearance: Can be installed adjacently; single unit occupied width 22 мм. Total width for N units ≈ 22 × N mm
- Vertical cooling clearance recommendation: ≥8mm top & bottom; ≥10mm for densely packed arrangements
- Cabinet depth reservation: ≥75mm for socket + relay assembly (avoid interference with cabinet door)
- Vibration-prone applications: Install PYC-A1 locking clip to prevent dislodging.
- Important Remarks
- MY2N-GS shares identical outline dimensions and fully compatible sockets with legacy MY2N-J; direct field replacement supported.
- Narrow width of only 21.5mm, ideal for space-restricted control cabinets.
- Avoid mounting adjacent to contactors and high-power power supplies; elevated ambient temperature shortens contact service life.