- Разбивка кода модели
| Сегмент | Код | Определение |
| А9 | А9 | Product family code for Acti9, Шнайдер’s standard low-voltage distribution series |
| Ф | Ф | Type code for iC65N миниатюрный автоматический выключатель (МКБ); F=iC65, K=iC65N-K, V=Vigi iC65 |
| 18 | 18 | Internal item code for standard iC65N version |
| 2 | 2 | Pole quantity: 2П (2-столб); 1=1P, 2=2P, 3=3P, 4=4P |
| 10 | 10 | Rated current code for 10A; 01=1A, 02=2A, 04=4A, 06=6A, 10=10A, и т. д.. |
Full Model Definition: Schneider Acti9 iC65N standard miniature circuit breaker, 2-столб, C-кривая, 10А
- Основные технические характеристики
| Категория | Detailed Parameters | Стандарты & Сертификаты |
| Basic Ratings | • Family: Акти9 iC65N | МЭК 60898-1 |
| • Type: Thermal-magnetic MCB | ГБ 10963.1 | |
| • Poles: 2П | CCC, CE, CCS Approval | |
| • Rated current (В): 10A @30°C | ||
| • Tripping curve: C-кривая (5~10×In) | ||
| • Breaking capacity: 6kA@400V AC, 10kA@380~415V AC, 20kA@220~240V AC, 36kA@12~133V AC | ||
| • Rated operational voltage (Уэ): 400В переменного тока 50/60 Гц | ||
| • Rated insulation voltage (Уи): 500В и | ||
| • Rated impulse withstand voltage (Умп): 6кВ | ||
| Механический & Электрические характеристики | • Mechanical endurance: 20,000 операции | МЭК 60947-2 |
| • Electrical endurance: 10,000 операции | ||
| • Current limiting class: Сорт 3 | ||
| • Disconnector function: Available | ||
| • Operation: Toggle handle | ||
| • Status indication: ON/OFF contact position marker | ||
| • Cable capacity: Solid wire 1~25mm², flexible wire 1~16mm² | ||
| • Strip length: 14мм | ||
| • Tightening torque: 2.5Н·м | ||
| Physical Dimensions | • Mounting: DIN rail mount | МЭК 60529 |
| • Width: 36мм (4×9mm modular pitch) | ||
| • Height: 94мм | ||
| • Depth: 78.5мм | ||
| • Weight: 206г | ||
| • Ingress protection: IP20 | ||
| Условия окружающей среды | • Operating temperature: -35°С ~ +70°С | МЭК 60068-1 |
| • Storage temperature: -40°С ~ +85°С | ||
| • Relative humidity: 95% @55°C | ||
| • Pollution degree: Сорт 3 | ||
| • Damp heat resistance: Grade 2 | ||
| Sustainability Features | • Green Premium certified product | China Green Design Product Certification |
| • Compliant with EU RoHS Directive | ||
| • SVHC-free per REACH regulation | ||
| • Mercury-free construction | ||
| • Product lifecycle carbon footprint: 4kg CO₂ equivalent |
- Full Part Number List (iC65N 2P C Curve Range)
| Part No. | Описание | Номинальный ток |
| A9F18201 | iC65N 2P C1A | 1А |
| A9F18202 | iC65N 2P C2A | 2А |
| A9F18203 | iC65N 2P C3A | 3А |
| A9F18204 | iC65N 2P C4A | 4А |
| A9F18206 | iC65N 2P C6A | 6А |
| A9F18210 | iC65N 2P C10A | 10А |
| A9F18213 | iC65N 2P C13A | 13А |
| A9F18216 | iC65N 2P C16A | 16А |
| A9F18220 | iC65N 2P C20A | 20А |
| A9F18225 | iC65N 2P C25A | 25А |
| A9F18232 | iC65N 2P C32A | 32А |
| A9F18240 | iC65N 2P C40A | 40А |
| A9F18250 | iC65N 2P C50A | 50А |
| A9F18263 | iC65N 2P C63A | 63А |
Full series coverage: 1П/2П/3П/4П, B/C/D tripping curves, rated current from 1A to 63A
- Межбрендовая ссылка & Варианты замены
4.1 In-brand Schneider Replacements
| Original PN | Replacement PN | Specification Difference |
| A9F18210 (iC65N 2P C10A) | A9F19210 (iC65H 2P C10A) | Более высокая отключающая способность: up to 15kA@400V vs original 10kA |
| A9F18210 | A9F20210 (iC65L 2P C10A) | Промышленный класс, enhanced current-limiting performance |
| A9F18210 | A9F75210 (iDPNa 2P C10A) | Compact 1P+N design with only 18mm width |
4.2 Cross-Brand Equivalent List
| Шнайдер | АББ | Сименс | Вкусный |
| A9F18210 (iC65N 2P C10A) | S201-C10 (2П) | 5SY6210-7CC | HDBE-63 C10 2P |
| Отключающая способность:6кА при 400 В | Отключающая способность:6кА при 400 В | Отключающая способность:6кА при 400 В | Отключающая способность:6кА при 400 В |
| C-кривая (5~10×In) | C-кривая (5~10×In) | C-кривая (5~10×In) | C-кривая (5~10×In) |
- Область применения & Отраслевые случаи
5.1 Recommended Applications
| Область применения | Типичное использование | Преимущества выбора |
| Civil Buildings | Overcurrent protection for lighting & socket circuits in residential and commercial buildings | C-curve matches general loads; защита IP20, quick DIN installation |
| Промышленный контроль | Power protection for small motor control loops and PLC power supply | Class3 current limiting, fast reliable short-circuit protection |
| Public Infrastructure | Security alarm, fire alarm and low-voltage auxiliary systems | Wide operating temperature range (-35°С~70°С), stable in harsh environments |
| Data Center | Branch circuit protection for server cabinets & network equipment | Long mechanical/electrical service life for frequent switching |
| Новая Энергия | Output-side protection for PV inverters and energy storage branch circuits | High breaking capacity plus certified disconnector safety function |
5.2 Non-Recommended Application Scenarios
Direct-on-line large motors: select D-curve or motor-specific MCB instead
Frequently switched heavy inductive loads: configure contactor + тепловое реле перегрузки
Цепи постоянного тока: adopt iC65-DC series with part numbers starting with A9F8
High altitude (>2000м): derate rated current or specify altitude-adapted dedicated models
5.3 Типичные случаи применения
Случай 1: Lighting System of Commercial Complex
Приложение: Branch protection for public area lighting circuits in shopping mall
Конфигурация: A9F18210 (2P C10A) for each 10A lighting feeder
Outcome: Перегрузка & защита от короткого замыкания; paired with Vigi residual current accessory A9V52210 for earth leakage protection, complying with GB 50054 electrical code for buildings
Случай 2: Control Circuit for Automated Production Line
Приложение: Power protection for PLC input modules & secondary control loops
Конфигурация: A9F18210 as backup protection of control transformer secondary side
Преимущество: Excellent current limiting cuts off short-circuit instantly to safeguard PLC modules against damage
- Устранение распространенных неисправностей
| Симптом неисправности | Root Cause | Remedial Action |
| Frequent unwanted tripping | 1. Circuit overload | 1. Reduce connected load or upgrade higher rated breaker |
| 2. Wiring short-circuit | 2. Inspect cable insulation and eliminate short fault | |
| 3. Mismatched tripping curve | 3. Replace with matched curve (например. D-кривая) | |
| 4. Excessive ambient temperature | 4. Improve cabinet ventilation to lower surrounding temp | |
| Unable to close ON | 1. Not reset after fault trip | 1. Toggle handle fully OFF then reclose ON |
| 2. Internal mechanism jamming | 2. Inspect mechanical parts or replace breaker if damaged | |
| 3. Loose terminal wiring | 3. Retighten terminals to 2.5N路m torque | |
| 4. Persistent downstream short-circuit | 4. Clear short-circuit fault before re-energizing | |
| Incorrect handle position indication | 1. Damaged position indicator component | 1. Inspect indicator window and replace unit as needed |
| 2. Failed internal linkage mechanism | 2. Contact Schneider after-sales service |
- Air Shipment Compliance & Сертификаты
7.1 Air Transport Compliance
Product construction: Нет встроенной литиевой батареи / supercapacitor, classified as general electrical equipment
Shipping classification: Неопасные грузы, compliant with IATA DGR Clause 9
Packaging requirement: Standard industrial carton to avoid transit mechanical damage
7.2 Main Certification Summary
| Certificate Type | Certificate No. | Valid Application Region |
| CCC Approval | 2.02001E+15 | Domestic sales & installation in China |
| CE Certificate | 0081/CE | Евросоюз & European Economic Area |
| CCS Marine Approval | CCS-ZY-2021-001 | Onboard marine electrical systems |
| RoHS Compliance | Compliant with Directive 2011/65/EU | Restricted hazardous substances per EU environmental regulation |
- Правила быстрого выбора & Mnemonic
Mnemonic (Engineering Summary)
Remember PN A9F18210: 2P C10 rating confirmed
Six kiloamp breaking, safe for lamp and socket conformation
Standard Acti9 range, easy DIN rail fixation
C-curve trips at five-to-ten In, dual protection from overload & short condition
Quick Look-up Rules
- Pole identification: 4th digit of PN = pole count (1=1P,2=2P,3=3P,4=4P)
- Current reading: Last two digits denote rated amp (01=1A,06=6A,10=10A,63=63A)
- Curve selection: C=general-purpose standard; B=precision electronics; D=heavy-duty motor loads
- Breaking capacity code: N=6kA, H=10kA, L=15kA @400V AC