The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. С термомагнитным отключением, регулируемый диапазон тока 37–50 А, отключающая способность 100 кА и степень защиты IP20., it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.
| Сегмент кода | Определение | Подробное описание |
| GV3 | Серия продуктов | TeSys GV3 range motor circuit breakers for three-phase motor protection |
| П | Тип продукта | Standard thermal-magnetic trip unit with rotary knob operation |
| 50 | Номинальный ток | Max adjustable trip current 50A; thermal trip setting range: 37–50A |
| Полная модель | GV3P50 | 3-pole thermal-magnetic motor breaker, 37–50A, EverLink BTR screw terminals, IP20 |
| Код заказа | FD6887 | Schneider official standard part number |
- Core Technical Specification Table
| Категория параметра | Технические данные | Примечания |
| Основные параметры | ||
| Конфигурация полюсов | 3П (3-столб) | For three-phase AC circuits |
| Тип поездки | Thermal-Magnetic | Combines thermal overload protection & magnetic short-circuit protection |
| Режим работы | Rotary Knob Control | Manual switching with ON/OFF marking |
| Termination | EverLink BTR screw-clamp terminals | Fast wiring to reduce loose connection risks |
| Электрические параметры | ||
| Thermal Trip Adjustment | 37–50A | Compatible with motors of different rated powers |
| Номинальное рабочее напряжение (Уи) | 690В и | 50/60Гц |
| Номинальное напряжение изоляции (Уэ) | 690В и | Соответствует МЭК 60947-2 |
| Номинальный рабочий ток (Т.е.) | 50А | Maximum continuous operating current |
| Магнитный ток отключения | 700А | Short-circuit instantaneous tripping value |
| Максимальная отключающая способность (Ику) | 100тот | At 400V |
| Matched Motor Rating | 22kW @ 400V | For three-phase asynchronous motors |
| Механический & Ambient Parameters | ||
| Защита от проникновения | IP20 | Finger-touch safe against live components |
| Монтаж | Монтаж на DIN-рейку | Standard 35mm top-hat rail |
| Масса | Приблизительно. 0.45кг | Простая установка & transportation |
| Рабочая температура | -25°С ~ +60°С | Suitable for most industrial environments |
| Температура хранения | -40°С ~ +85°С | Wide storage temperature range |
| Сертификаты | ||
| Main Approvals | CE, UL, CSA, CCC, ЕАС | Globally certified per international standards |
| Eco Certifications | РоХС, REACH | EU-compliant environmentally friendly design |
III. Full GV3P Series Model List
| Модель | Thermal Trip Range | Matched Motor Power @400V | Магнитный ток отключения | Код заказа |
| GV3P40 | 25–40A | 18.5кВт | 600А | FD6886 |
| GV3P50 | 37–50A | 22кВт | 700А | FD6887 |
| GV3P65 | 48–65A | 30кВт | 800А | FD6888 |
| GV3ME50 | 37–50A | 22кВт | 700А | FD6890 |
| GV3ME65 | 48–65A | 30кВт | 800А | FD6891 |
| GV3ME80 | 56–80A | 37кВт | 1000А | FD6892 |
| GV3ME100 | 70–100A | 45кВт | 1200А | FD6893 |
- Alternative Cross Reference (Сменные модели)
- In-house Schneider Replacement
| Оригинальная модель | Замена | Описание |
| GV3P50 | GV3ME50 | Identical performance; ME is enhanced version with better accessory compatibility |
| GV3P50 | New production GV3P50 | No functional change, only production batch update |
- Cross-Brand Equivalents
| Бренд | Эквивалентная модель | Matching Grade | Преимущества |
| АББ | MS132-50 | ★★★★★ | Тот же текущий рейтинг, interchangeable mounting dimension |
| Сименс | 3RV2031-4KA10 | ★★★★☆ | Термомагнитный трип, fits 22kW motors |
| Итон | PKZM0-50 | ★★★★☆ | 3-конструкция столба, 100кА отключающая способность |
| Чинт | NDM2-63M/3300 | ★★★☆☆ | Cost-effective for bulk replacement |
| Вкусный | CDM1-63M/3300 | ★★★☆☆ | Well-known domestic brand with high cost-performance |
- Среды приложений & Field Cases
- Recommended Applications
Промышленная автоматизация: Перегрузка & short-circuit protection for 3-phase asynchronous pumps, fans and compressors
Manufacturing: Production line motor control & machine tool protection
Building Electrical: Central air-conditioning & fire-fighting pump control
Energy Sector: Front-end protection for small generator sets and inverters
Инфраструктура: Wastewater treatment equipment & bulk material conveying systems
- Non-Recommended Applications
DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply
Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)
High Altitude: Derating mandatory above 2000m elevation
Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings
- Типичные случаи применения
Случай 1: Fan System Protection for Food Processing Plant
Equipment: 3×22kW centrifugal fans, 380В/50 Гц
Решение: GV3P50 + LC1D65 contactor combination
Outcome: Triple protection against overload, короткое замыкание & потеря фазы; equipment failure rate reduced by 40%
Случай 2: Submersible Sewage Pump Control at Wastewater Plant
Equipment: 4×22kW submersible sewage pumps, 380В/50 Гц
Решение: GV3P50 + вспомогательные контакты + PLC interlock control
Outcome: Full motor protection plus remote monitoring, lower maintenance expense
- Air Shipment Compliance & Сертификация CE
- Соблюдение требований в области авиаперевозок
UN38.3: Not required; no built-in lithium battery or supercapacitor inside
Shipping Class: General commodity without special transport restriction
Упаковка: Standard industrial carton to avoid transit damage
Shipping Document: Copy of CE certificate + RoHS compliance declaration available
- CE Certification Details
Applicable Standards: МЭК 60947-2 (LV switchgear) & МЭК 60947-4-1 (motor control equipment)
Valid Region: European Economic Area (EEA) & global territories accepting CE marking
Validity: Permanently valid complying with current normative requirements
Расследование: Check Schneider official website product page or certification database
VII. Устранение распространенных неисправностей
| Симптом неисправности | Probable Causes | Remedial Actions |
| Frequent thermal tripping | 1. Перегрузка двигателя | 1. Inspect motor load |
| 2. Underset trip current | 2. Adjust rotary knob to correct setting | |
| 3. Excess ambient temperature | 3. Improve ventilation or derate operating current | |
| Невозможно закрыть | 1. Tripping latch not reset | 1. Toggle knob OFF then ON to reset |
| 2. Short circuit in wiring | 2. Troubleshoot short-circuit faults | |
| 3. Механические помехи | 3. Clean or replace breaker | |
| No protection upon phase loss | 1. Неправильная проводка | 1. Recheck three-phase cabling |
| 2. Damaged trip unit | 2. Replace trip component | |
| 3. Severe 3-phase unbalance | 3. Balance connected loads | |
| Overheated terminals | 1. Loose terminals | 1. Retighten terminal screws |
| 2. Undersized cable | 2. Upgrade to proper wire gauge | |
| 3. Terminal oxidation | 3. Clean terminals or replace unit |
VIII. Sizing Guidelines & Правила быстрого выбора
Quick Selection Formula Summary
> GV3P series 3-pole thermal-magnetic breakers;
> Suffix number denotes upper current limit;
> 40 = 25–40A, 50 =37–50A, 65 max at 65A;
> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.
Quick Rules
- Текущее соответствие: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Power Reference: At 400V, GV3P50 matches 22kW motor (~44A nominal)
- Accessory Option: Вспомогательный контакт: GV3AE11 (1НО+1НЗ) / GV3AE20 (2НЕТ)
- Mounting Spacing: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
- Установка & Инструкция по подключению
- Этапы установки
Confirm standard 35mm DIN rail
Snap breaker firmly onto rail
Incoming power: top-feed or bottom-feed acceptable
Motor cable connection: terminal tightening torque 2.5Nm recommended
- Спецификация проводки
Wire cross-section range: 1.5mm² min ~35mm² max
Терминал: EverLink BTR screw terminal compatible with copper/aluminum conductors
Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)
- EMC Protection
Maintain ≥50mm clearance between breaker and contactors
Separate control wiring from power cables to avoid cross-interference
Install EMC filter if needed for EMI suppression
Full Application Overview for Schneider GV3P50 Motor Circuit Breaker
- Core Application Summary
Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: motor overload, короткое замыкание & phase-loss protection plus manual switching, widely used in below industries:
- Detailed Application Classification
- Промышленная автоматизация & Manufacturing
| Приложение | Equipment | Protection Requirement | Application Benefit |
| Production Line Control | Конвейеры, sorters, упаковочные машины | Continuous running protection against overload shutdown | Improve line stability & reduce breakdown loss |
| Станки | Фрезерование, lathe & grinder spindle motors | Protection for frequent start-stop & instant short-circuit breaking | Protect costly equipment and extend service life |
| Bulk Handling | Bucket elevators, винтовые конвейеры | Stall & phase-loss protection | Prevent burnout & cut maintenance cost |
| General Machinery | Печать, текстиль & plastic processing machines | Защита от перегрузки + emergency manual cut-off | Simplify control circuit & enhance operational safety |
- Fluid Conveyance Systems
| Приложение | Equipment | Protection Feature | Typical Parameter |
| Pump Set | Industrial pump, fire pump, sewage pump | Dual overload + phase-loss protection, влагостойкий | 22кВт/380В,50Гц, setting 37–50A |
| Fan Unit | Centrifugal/axial/induced draft fans | Light-load startup protection against impeller jamming | Adapt to current fluctuation from variable duct resistance |
| Compressor | Воздух & холодильные компрессоры | Heavy-start & overheat protection | Tolerate frequent loading/unloading cycles |
| Vacuum Pump | Промышленный & water-ring vacuum pumps | Low-current idle-running damage prevention | Adjustable setting for light-load operation |
- Building & Municipal Infrastructure
| Sector | System | Key Demand | Способ монтажа |
| ОВК | Central air-con, air handler, cooling tower | Stable continuous-duty protection | DIN rail mounted with contactor interlock |
| Автоматизация зданий | Fire control, безопасность & elevator room equipment | Emergency cut-off safety | Remote monitoring via PLC |
| Wastewater | Aerator & sludge processing units | Dust & moisture resistance | Cabinet installation with IP20 protection |
| Новая Энергия | Small gen-set & PV inverter | Перегрузка по току & grid-fault isolation | Rated up to 690V high-voltage system |
- Other Industrial Sectors
| Промышленность | Equipment | Special Requirement | Matching Advantage |
| Сельское хозяйство | Irrigation pump & feed processor | Outdoor installation against grid voltage swing | Wide operating temp: -25°C~+60°C |
| Горное дело | Small conveyor & mine ventilation fan | Heavy startup + high short-circuit withstand | 100kA high breaking capacity |
| Еда & Beverage | Mixer & оборудование для стерилизации | Sanitary & easy-clean layout | No exposed live parts for hygiene compliance |
| Pharma | Фармацевтический & cleanroom machinery | Precise control & низкий процент отказов | High accuracy thermal-magnetic trip characteristic |
III. Non-Recommended Applications (Avoidance Guide)
| Unsuitable Condition | Причина | Alternative Solution |
| DC Circuit | Abnormal tripping characteristic under DC (rated only AC 50/60Hz) | Dedicated DC-rated Schneider circuit breakers |
| >30 Starts/Hour | Accelerated trip unit ageing & shortened service life | GV3ME enhanced series or match with soft starter |
| Altitude>2000m | Performance derating required | High-altitude specified breaker or add upstream protection |
| Strong Corrosive Atmosphere | Uncoated terminals prone to oxidation | Anti-corrosion coated model or protective enclosure |
| Explosion Hazard Zones | Standard version without ATEX certification | ATEX certified explosion-proof breakers |
| Single-Phase Motors | 3-pole structure cannot provide single-phase protection | GV2 single-phase motor breaker series |
- Detailed Field Application Cases
Case1: 22kW Fan Protection in Food Factory
Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit
Схема: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact
Logic: Manual/Auto switch; auto stop & alarm upon overload
Результат: Triple protection realized; failure rate -40%, maintenance cost -30%
Case2: Submersible Sewage Pump Control at WWTP
Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation
Схема: GV3P50 + PLC interlock + level transducer
Состояние: Humid environment, 10~15 starts/hour frequent cycling
Результат: Anti-stall burnout + remote auto-switching, improved system reliability
Case3: Central Air-conditioning for Shopping Mall
Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz
Схема: GV3P50 + инвертор + temperature sensor
Особенность: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload
Результат: ≥30% energy saving, service life doubled, superior system stability
- Recommended Matching Components & Selection Tips
- Recommended Matching List
| Аксессуар | Part No. | Функция | Ценить |
| Контактор переменного тока | LC1D65 | Remote control for frequent start-stop | Enable automatic control & reduce manual operation |
| Вспомогательный контакт | GV3AE11 | 1NO+1NC signal output | Alarm feedback or PLC interlock |
| Тепловое реле перегрузки | LRD4363 | Optional secondary overload protection | Double motor protection for enhanced safety |
| Control Pushbutton | XB4 Series | Manual start/stop | ЧМИ & emergency shutdown function |
- Sizing Rules
- Power Match: 22кВт (~44A @400V) optimally paired with GV3P50 (37–50A)
- Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
- Wiring Torque: Cable terminal tightening torque fixed at 2.5Nm
- Ambient Derate: Снизить мощность 1% rated current per every 1°C rise above +40°C ambient temperature