RM17: Harmony RM17 series three-phase monitoring relay
TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)
00: 1 переключающий контакт (1C/O) версия; RM17TG20 in the same series is the 2C/O dual-contact model
✅ Основные функции
Monitors three phases L1/L2/L3:
- Phase sequence error (reverse phase, защита от обратного вращения двигателя)
- Phase loss fault (loss of two or more phases; single-phase weak voltage drop will NOT trigger)
Автономный, energized directly from L1/L2/L3, no additional auxiliary источник питания необходимый
📋 Основные технические характеристики
| Элемент | Параметр |
| Monitoring Voltage Range | 208~480 VAC (operating limit 183~528VAC) |
| Частота | 50/60Hz ±10% |
| Выходные контакты | 1C/O (1 Нормально открытый + 1 Нормально закрытый) |
| Rated Contact Current | 5A @250VAC, max.1250VA |
| Power-up Start Delay | ≤650ms |
| Fault Response Time | ≤130ms |
| Потребляемая мощность | ≤22VA @400VAC 50Hz |
| Монтаж | 35мм DIN-рейка, width 17.5mm (1 модуль) |
| Индикатор | Желтый светодиод: ON under normal condition, OFF in fault state |
| Сертификаты | CE, Категория перенапряжения III, IEC60255 |
🔌 Terminal Wiring Definition
Верхние клеммы: Л1, Л2, L3 → Connect to three-phase power supply
Lower contact terminals:
11: Общий
14: Нормально открытый (НЕТ) (closed in normal state, открыт по вине)
12: Нормально закрытый (Северная Каролина) (открыт в нормальном состоянии, closed under fault)
With correct three-phase supply and proper phase sequence: реле подает питание, LED ON; Потеря фазы / reversed phase → relay de-energizes, Светодиод ВЫКЛ.
🛠️ Типичные сценарии применения
Hoisting equipment, лифты, конвейерные линии, water pump sets, preventing motor reverse rotation
Воздушные компрессоры, chiller unit three-phase power protection
Portable equipment power access detection, emergency power switching judgment
⚠️ Troubleshooting Points
- Светодиод выключен: No power on three-phase incoming lines or loose wiring;
- LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
- Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & защита от пониженного напряжения, select RM17TE series.
🧩 Same-series Comparison & Справочник по замене
RM17TG00: 1C/O, последовательность фаз + потеря фазы
RM17TG20: 2C/O dual changeover contacts, последовательность фаз + потеря фазы
17TE00 ринггитов: With voltage unbalance, перенапряжение, пониженное напряжение, phase loss and phase sequence (full-featured model)
📌 Notes
No potentiometer for threshold adjustment, fixed logic without adjustment knobs;
For three-phase 3-wire system only;
Dry contact output for PLC DI or contactor coil interlock circuit.
Шнайдер RM17TG20 Troubleshooting Document
Применимый: RM17TG00 / RM17TG20 three-phase phase sequence & реле потери фазы
Safety Precaution: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.
Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. Нормальное состояние: желтый светодиод горит, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized
- Pre-check Preparation
- Инструменты: Цифровой мультиметр, cross screwdriver, изоляционные перчатки
- Подтверждение модели: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
- System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
- Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
- Troubleshooting by Fault Symptom
Симптом 1: Yellow LED completely off after power-up, relay contacts no action
Описание: No indicator light after energizing, контакты 11/14 и 21/24 fail to close
- Выключить питание, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
- Включение питания, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter
Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage
No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit
- LED still OFF with all three-phase voltages normal:
Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals
Inspect module appearance: Треснувший корпус, burn marks or carbonized terminals → internal damage, replace relay directly
Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective
Симптом 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)
Most frequent on-site fault: Обратная последовательность фаз
- Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
- Выключить питание, swap any two incoming L phases (например. L1 and L3)
- Re-energize and observe LED:
LED ON and contacts close: Fault resolved, root cause reversed phase sequence
LED still OFF after twice phase swap: proceed to next step
- Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
- Still invalid: Relay internal failure, replace for test
Симптом 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)
Power monitoring circuit healthy, fault lies in secondary dry contact circuit
RM17TG20 has two independent changeover contact sets: 11/12/14 и 21/22/24, both act synchronously
- Power off and verify contact wiring:
11, 21: Общие терминалы
14, 24: Нормально открытый (НЕТ) (закрыт при подаче питания; открыт по вине)
12, 22: Нормально закрытый (Северная Каролина) (open when energized; closed under fault)
- Включение питания (relay normal state, LED ON), measure continuity with multimeter:
11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open
- Manually create fault (обратная последовательность фаз), Светодиод ВЫКЛ.:
11 & 14, 21 & 24: открыть; 11 & 12, 21 & 22: руководить
- Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
- Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse
Симптом 4: Random false tripping during motor operation (Светодиод ВЫКЛ., protection trip)
- Monitor three-phase voltage, focus on voltage dip during motor starting:
⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection
- Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
- Check power cables: Повреждение кабеля, earth fault or risk of phase-to-phase short circuit
- EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
- Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
- Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged
Симптом 5: Relay does not alarm with single-phase cut-off (protection no action)
This is NOT a fault, it is inherent design limitation!
RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection
If single-phase loss, voltage unbalance, перенапряжение & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay
III. Quick Self-check Procedure (On-site Maintenance Checklist)
✅ Step1: Выключить питание, inspect appearance and wiring (терминалы, следы ожогов, рыхлость)
✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages
✅ Step3: Observe LED status to locate fault domain (источник питания / последовательность фаз / relay itself)
✅ Step4: Power off and swap two L phases to verify reversed phase sequence
✅ Step5: Power off and test continuity of two contact sets to confirm switching logic
✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring
- Распространенные заблуждения
- ❌ Заблуждение: Relay should protect on single-phase loss
✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.
- ❌ Заблуждение: Front panel adjustment knobs are available for threshold setting
✅ Note: RM17TG has no potentiometer, threshold fixed.
- ❌ Заблуждение: Two contact sets can act independently
✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.
- ❌ Заблуждение: Can be used in 3P4W system (с нейтральным проводом)
✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.
- Replacement Criteria (Replace relay if any condition met)
- L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
- Two contact sets act asynchronously, contacts burnt or fail to switch
- Housing or terminals show black burn marks, bulging or carbonization
- Fault eliminated after installing new relay under same power condition
- Рекомендации по техническому обслуживанию
- Периодическая проверка: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
- Условия окружающей среды: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
- Очистка: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
- Срок службы: Mechanical life of contacts >10 миллион циклов; electrical life approx.100,000 cycles at 5A@250VAC
Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35мм DIN-рейка, 17.5mm 1-module width)
All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system
- RM17TG (Базовая модель: последовательность фаз + phase loss only, no adjustment knobs, fixed threshold)
| Модель | Контакты | Диапазон напряжения | Основные функции | Типичное применение |
| RM17TG00 | 1C/O (1 переключение) | 208~480VAC | Phase sequence error, ≥2 phases loss protection; No unbalance / над&пониженное напряжение | Single interlock, water pump and general motor protection |
| RM17TG20 | 2C/O (2 independent changeover) | 208~440VAC | Phase sequence error, ≥2 phases loss protection; No unbalance / над&пониженное напряжение | Hardware interlock + Сигнализация ПЛК, подъем, лифт |
TG Series Features: Нет потенциометра, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm
- RM17TT / ОБЛИЦОВКА / TU / ТО (Multi-function adjustable type, transparent cover with adjustment knobs)
| Модель | Контакты | Диапазон напряжения | Функции мониторинга | |
| RM17TT00 | 1C/O | 208~480VAC | Потеря фазы + последовательность фаз; rated voltage selectable, delay adjustable; No voltage unbalance, повышенное/пониженное напряжение | Basic adjustable phase sequence & потеря фазы, suitable for multi-voltage site |
| RM17TA00 | 1C/O | 208~480VAC | Потеря фазы + последовательность фаз + three-phase voltage unbalance; unbalance threshold & delay adjustable; No over/undervoltage | Motor winding protection, detect three-phase asymmetry |
| 17TU00 ринггитов | 1C/O | 208~480VAC | Потеря фазы + последовательность фаз + контроль пониженного напряжения; undervoltage threshold & delay adjustable; No overvoltage, нет дисбаланса | Power supply drop monitoring, generator set, incoming power supervision |
| 17TE00 ринггитов | 1C/O | 208~480VAC | Полные функции: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurement | Чиллер, air compressor, UPS switching, full protection requirement |
III. RM17 Series Single-phase / DC Voltage Monitoring (Та же серия, non three-phase)
| Модель | Тип | Monitoring Range | Контакты |
| RM17UAS14 | Постоянное напряжение | 9~15VDC | 1C/O |
| RM17UAS16 | AC/DC универсальный | 20~80V AC/DC | 1C/O |
| RM17UAS15 | AC/DC универсальный | 65~260V AC/DC | 1C/O |
| RM17UBE Series | Single-phase AC Over & Пониженное напряжение | 24~240 В переменного тока | 1C/O |
| RM17UB310 | Single-phase Voltage Monitoring | 200~240 В переменного тока | 1C/O |
- Model Suffix Coding Definition (RM17Txx00)
TG: Базовый тип, fixed threshold, no adjustment knob, последовательность фаз + потеря фазы
ТТ: Adjustable basic model, последовательность фаз + потеря фазы, voltage range selectable
ОБЛИЦОВКА: Т + Asymmetry voltage unbalance detection
TU: Т + Undervoltage monitoring
ТО: Total full functions (последовательность фаз, потеря фазы, разбалансировать, перенапряжение, пониженное напряжение)
00: 1C/O output
20: 2C/O dual independent changeover contacts (only available for TG series)
- Таблица быстрого выбора (Three-phase models)
| Требование | Рекомендуемая модель |
| Only phase sequence+phase loss, single contact output, 480V application | RM17TG00 |
| Phase sequence+phase loss, dual independent dry contacts for interlock + тревога | RM17TG20 |
| Phase loss+phase sequence, multi-voltage option, delay required | RM17TT00 |
| Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection) | RM17TA00 |
| Phase loss+phase sequence+undervoltage monitoring | 17TU00 ринггитов |
| Полная защита: phase loss+phase sequence+unbalance+overvoltage+undervoltage | 17TE00 ринггитов |
- Common General Specifications
- Монтаж: 35мм DIN-рейка, 1 модуль (17.5мм);
- Output Logic: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
- Источник питания: Self-powered directly from L1/L2/L3, нет нейтрального провода, three-phase 3-wire system only;
- Время ответа: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
- Рейтинг контактов: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads
VII. Замена & Upgrade Reference
RM17TG00 ↔ RM17TG20: identical function, only contact quantity differs
RM17TT00 → RM17TA00: add voltage unbalance detection
RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring
Legacy RM22TG series is substitute series (та же функция, different form factor)