Разбивка кода модели
Официальная модель: PXC16.2-E.A (PXC16.2-E-A is the common industry notation)
PXC: APOGEE Compact Series DDC (Direct Digital Controller) для building automation
16: Общий 16 integrated I/O points onboard
.2: Second-generation hardware revision
Э: BACnet/IP Ethernet Automation Level Network (ALN) (10/100M Ethernet)
А: Standard temperature variant (non-rooftop extended temperature model)
Reference for model differentiation:
PXC16.2-P.A: RS485 BACnet MS/TP version
PXC16.2-EF.A: Ethernet with FLN field bus support (requires license)
PXC16.2-EF32.A: Ethernet with FLN bus, поддержка до 32 FLN devices
- I/O Point Definition (TX-I/O™ Software Configurable)
Общий: 16 integrated I/O points with adaptive signal configuration
| Point Type | Количество | Описание |
| UI Universal Input | 3 | Resistive sensors, 0–10 В, 4–20 мА, pulse digital input |
| U Universal I/O | 5 | Configurable as input / 0–10V analog output / digital input |
| DI Digital Input | 2 | Вход с сухим контактом |
| AOV Analog Output | 3 | 0–10V DC analog output |
| DO Digital Output | 3 | Relay contact output (for AC24V loads) |
✅ Supported sensors: 1k Nickel, 1k Platinum, 10K/100K NTC thermistors, 0–10 В, 4–20mA transmitters
- Core Hardware & Электрические характеристики
- Источник питания: 24 В переменного тока, power consumption ≈18 VA
- Процессор: MPC852T, 100 MHz clock speed
- Память: 16MB for program & data storage; built-in lithium backup RTC clock (typical service life: 10 годы)
- AD/DA Conversion: 16-bit ADC sampling, 10-bit DAC output
- Монтаж: DIN rail mounting or direct screw mounting; pluggable terminal blocks
- Масса: Приблизительно. 0.91 кг
- Условия окружающей среды
Рабочая температура: 0 ℃ ~ +50 ℃ (Standard Type A)
Condensation, heavy dust and strong electromagnetic interference are prohibited
- Сертификация: BTL certified, BACnet B-BC profile compliant
- Коммуникационные интерфейсы
- Ethernet (Primary ALN): БАКнет/IP, 10/100Base-TX
- Local Commissioning Ports
USB-B device port (ввод в эксплуатацию, program download/upload)
RS232 HMI port for direct laptop connection
- FLN Bus: No onboard hardware FLN interface; select EF/EF32 variants if external field sensor modules are required
- Программное обеспечение & Programming Ecosystem (Критическое примечание)
Belongs to APOGEE Insight Building Management System
Programming Language: PPCL (APOGEE Proprietary Control Language)
Commissioning Tools:
Insight (Supervision + programming integrated platform)
Коннектикут (Controller Tool, standalone commissioning software)
⚠️ Important Distinction: Incompatible with new-generation Desigo ABT Site software. ABT Site is designed exclusively for Desigo PXC4/PXC5/PXC7 and cannot be used for legacy APOGEE PXC Compact controllers.
- Типичные сценарии применения
Air Handling Units (AHU), Primary Air Units (PAU), chiller auxiliary control, heat exchanger stations, small plant rooms, packaged air handlers, fan coil group control. Ideal for independent DDC control of medium & small HVAC equipment.
- Product Lifecycle & Варианты замены
- Статус: APOGEE PXC Compact series Obsolete (Снято с производства). Only stock / second-hand units available; no official hardware upgrade variants released by Сименс.
- No direct cross-compatibility between old and new platforms (Incompatible programming software, control logic and program migration)
Recommended New Generation Replacement (Desigo Platform)
Desigo PXC4.E16: 16-point Ethernet BACnet/IP DDC, mainstream modern controller, programmed via ABT Site
Примечание: Similar I/O count, but all control programs must be rewritten; PPCL programs cannot be migrated directly.
- Common Pitfalls & Рекомендации по выбору
- Do not confuse PXC16.2-E.A (Ethernet) vs PXC16.2-P.A (485 MS/TP); hardware communication circuits are incompatible.
- This model has no native FLN bus interface. Select EF32 variant if TX-I/O field expansion modules are required.
- Expired backup battery only causes real-time clock loss; stored control programs remain intact.
- DO relay contacts cannot drive high-power contactors directly; interposing relays are mandatory.
- When wiring 4–20mA transmitters to universal points, verify external power supply configuration to avoid channel burnout.
Supplementary ④: Коды неисправностей, Коренные причины & On-site Troubleshooting for Siemens PXC16.2-E-A
4.1 System Fault Code Table (Common to all PXC16 firmware revisions)
| Код неисправности | Описание неисправности | Первопричина | Standard Remedial Procedures |
| Err01 | Undervoltage Alarm | AC24V supply voltage drop, незакрепленные клеммы, insufficient power capacity | 1. Measure AC24V at controller terminals; 2. Check cable voltage drop; 3. Затяните винты клемм.; 4. Use dedicated transformer; avoid sharing low-capacity power supply among multiple devices |
| Err02 | Memory Checksum Error | Corrupted program, flash memory failure, uncontrolled power cycling | 1. Re-download PXC program; 2. Factory reset and reflash firmware; 3. Replace controller if error recurs persistently (hardware fault) |
| Err03 | Analog Input Out-of-Range | Sensor open circuit, короткое замыкание, mismatched signal type | 1. Inspect sensor wiring; 2. Verify configured signal type (NTC / 4–20 мА); 3. Terminate unused analog channels |
| Err04 | LON Bus Communication Fault | LON short circuit, missing terminating resistors, reversed polarity | 1. Install 105Ω terminating resistors at both bus ends; 2. Check cable insulation damage & короткое замыкание; 3. Isolate faulty bus nodes |
| Err05 | Output Overload Alarm | Shorted DO contacts, чрезмерный ток нагрузки | 1. Disconnect external load and retest; 2. Add interposing relay for relay outputs; 3. Do not directly drive large solenoid valves |
| Err06 | RTC Clock Failure | Depleted internal backup battery | Симптом: Time resets after power loss. The controller can still run, but cannot retain time. Full replacement recommended for long-term operation. |
| Err07 | Watchdog Reset | Program infinite loop, electromagnetic interference, firmware bugs | 1. Optimize PPCL control logic; 2. Separate power cables and signal cables; 3. Upgrade to official stable firmware |
| Err08 | Module Over-Temperature | Плохая вентиляция шкафа, ambient temperature exceeding 55°C | 1. Improve enclosure cooling; 2. Avoid mounting adjacent to VFDs and contactors; 3. Reduce cabinet operating temperature |
4.2 High-Frequency On-site Troubleshooting Procedures
- Controller fails to power up, all indicators off
- Disconnect all external wiring, power the controller standalone to distinguish load short circuit or internal hardware failure
- Confirm supply voltage is AC24V. 24 В постоянного тока / AC220V will cause permanent damage
- No reverse-polarity protection for power terminals L/N. Avoid reversed wiring.
- Program download failure
- Кабель связи: Crossed RS232 commissioning cable required
- CT tool communication parameters: 9600 baud, 8N1, нет паритета
- Close other serial port software occupying COM port; prioritize FTDI USB-to-serial adapters for industrial PCs
- Firmware version must match program; mismatched firmware leads to download interruption
- No actuation from output points
- Distinguish between software interlock / manual-auto mode / hardware circuit fault
- DO channels provide dry contacts only; external power supply is required for load circuit
- AO analog outputs require load impedance above minimum specification to prevent signal collapse
4.3 Strict Installation & Commissioning Prohibitions
- ❌ Never route AC220V cables to controller I/O terminals; immediate channel burnout
- ❌ Run power cables and sensor wiring within the same cable tray; causes interference and signal drift
- ❌ Omit LON bus terminating resistors; leads to intermittent communication loss
- ❌ Missing cabinet protective earthing; static electricity triggers random controller resets
- ❌ Hot-plug I/O wiring frequently; risk of buffer chip breakdown
4.4 Рекомендации по техническому обслуживанию
- Annual inspection: Напряжение питания, terminal tightness, cabinet temperature & влажность, LON wiring
- Back up PXC program files (.pxc) regularly for critical projects; source code cannot be recovered once hardware fails due to product obsolescence
- Данная модель снята с производства; full unit replacement is preferred upon hardware failure. No spare parts available for component-level repair.
Typical Application Cases of Siemens PXC16.2-E-A (APOGEE Insight System, BACnet/IP Ethernet Model)
Основное позиционирование: 16-point compact DDC for independent control of single medium/small HVAC equipment. Built-in Ethernet, suitable for distributed plant room layout and standalone control cabinets. No native FLN bus, not recommended for large numbers of external P1 field devices.
Precondition for selection: Total I/O ≤16 points, standalone equipment control, access to building LAN via BACnet/IP. Upgrade to PXC24.2 / PXC36 for higher point count requirements.
Случай 1: Primary Air Unit (PAU) on Typical Office Floors (Most Common Application)
Обзор проекта
Grade A office building, each floor equipped with one Primary Air Unit (PAU), общий 22 единицы. Building Automation System adopts Siemens APOGEE Insight. PXC16.2-E-A deployed for each air handling unit for independent control.
I/O Allocation (Fully utilizing native 16-point TX-I/O)
DI Digital Inputs
- Supply fan run status feedback
- Supply fan fault alarm
- Filter differential pressure alarm
UI Universal Inputs
- Outdoor air temperature
- Supply air temperature
- Supply air humidity
U Universal Configurable Points
- Return air CO₂ concentration
- Freeze protection switch signal
AOV Analog Outputs
- Chilled water control valve
- Hot water control valve
- Fresh air damper actuator
DO Digital Outputs
- Supply fan start/stop control
- Unit freeze protection alarm output
- Electric preheat contactor control
Функции управления
- PID constant supply air temperature control; fresh air damper modulated in response to CO₂ concentration
- Seasonal mode switching: cooling via chilled water in summer, heating & humidification via hot water in winter
- Freeze protection interlock: close fresh air damper, fully open hot water valve at low temperature
- Scheduled start/stop, fault alarm upload, historical data logging
- Uinterrupted standalone operation after power recovery; independent of upper workstation
Selection Justification
Point count matches compact PAU without additional expansion modules
Native Ethernet for direct connection to building switch, простая проводка
No FLN device required; EF variant unnecessary
Limitation Reminder
Additional humidifier or VFD feedback signals will exceed available points. Upgrade to PXC24.2 for future expansion.
Случай 2: Exhaust Fan / Car Park Induced Ventilation Control for Shopping Mall
Обзор проекта
Underground parking of shopping complex, divided into multiple ventilation zones. Each zone ventilation package controlled by one PXC16.2-E-A.
Логика управления
Fan start/stop & speed modulation linked to car park CO concentration; full exhaust damper opening triggered by fire alarm signal; fan fault monitoring, hand-auto switchover.
Brief I/O List
ОТ: Fan status, вина, fire dry contact signal, CO detector
ДЕЛАТЬ: Fan contactor, audible/visual alarm
К: Fan VFD signal, exhaust air damper
Преимущества
Distributed equipment rooms in parking area simplify Ethernet networking; compact DDC delivers cost-effective solution for low-point-count zone ventilation.
Случай 3: Small Air Handling Unit (AHU) for Outpatient Departments in Hospital
Обзор проекта
Small purification AHU for consultation rooms in Grade 2 больница, requiring precise temperature & humidity control for basic medical ventilation.
Special Control Requirements
- Constant supply air temperature & humidity PID regulation
- Filter differential pressure alarm for maintenance reminder
- Hardwired interlock with fire alarm system; unit shutdown upon fire signal
- Continuous long-term stable operation
Selection Highlights
APOGEE PXC series widely deployed in healthcare projects for proven reliability. PXC16.2-E-A Ethernet interface supports seamless integration into hospital BMS intranet.
⚠️ Operating rooms, ICUs and high-grade purification air handlers require more control points; PXC36 is recommended instead of PXC16.
Случай 4: Secondary Side Plate Heat Exchanger Control for Industrial Park Heat Station
Обзор проекта
Small heat substation in industrial park, monitoring and regulation of single plate heat exchanger.
Конфигурация ввода/вывода
ОТ: Circulation pump run status, pump fault
UI: Primary supply/return water temperature, secondary supply/return water temperature
К: Primary side heating water control valve
ДЕЛАТЬ: Circulation pump start/stop, over-temperature alarm
Control Strategy
PID regulation to maintain constant secondary supply water temperature; low-temperature freeze interlock; time-based heating setpoint adjustment.
Application Boundary
Only applicable to single heat exchanger + single circulation pump small heat station. Select PXC36 for multi-unit large heat stations.
Случай 5: Combined Air Handler + Public Lighting Integrated Control for Hotel Back-of-House
Обзор проекта
Budget hotel service plant room. One PXC16.2-E-A controls small AHU together with corridor public lighting.
Hybrid Control Functions
- Supply air temperature control for air handling unit
- Scheduled automatic switching of public lighting, linkage with motion sensors
- Unified fault alarm upload for all equipment
Примечание
Reserve 2~3 spare I/O points for renovation when mixing HVAC and lighting control.
❌ Unsuitable Scenarios for PXC16.2-E-A (Selection Avoidance Guide)
- Large quantity of external P1 FLN sensors/actuators required → select PXC16.2-EF-A with FLN license
- AHU equipped with VFD, увлажнитель, reheat coil and multiple dampers; total I/O 16 points → PXC24.2 / PXC36
- Outdoor rooftop installation requiring extended temperature range → select dedicated rooftop variant
- Massive remote I/O expansion required; no native TX-I/O expansion bus onboard
✅ General Project Implementation Experience (Applicable to All Cases)
- Сетевая архитектура: PXC16.2-E-A → LAN Switch → Insight Server (БАКнет/IP)
- ввод в эксплуатацию: Program download via RS232 local connection using CT tool
- Spare Parts Note: Данная модель снята с производства. New construction projects prefer Desigo series. Renovation & maintenance projects may source surplus/second-hand stock.
- Program Migration: Legacy PXC PPCL programs cannot be imported directly to new Desigo controllers; full control logic rewriting is mandatory.
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи






















NH42-63-318x560.png)



