Основная информация о продукте
Бренд: SAMWHA EOCR (Шнайдер Корея)
Тип продукта: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)
- Model Code Breakdown of EOCRSS-60NW7PQ
| Сегмент | Код | Определение |
| EOCRSS | Ряд | SS Economy Integrated Through-Core Motor Protector |
| 60 | Текущий рейтинг | Built-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors |
| Н | Режим защиты | Type N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails |
| W7 | Источник питания | W7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids) |
| П | Конфигурация контактов | P = Standard changeover contacts: 95(Северная Каролина)/97(НЕТ) (1 Нормально открытый + 1 Нормально закрытый) |
| вопрос | Дополнительная функция | Q = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval |
Основные технические характеристики
3.1 Текущий & Time Adjustment
Текущий диапазон: 5~60A (10:1 wide adjustment ratio)
D-Time (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current
O-Time (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves
3.2 Функции защиты
- Перегрузка & Защита от перегрузки по току (O-Time delayed trip)
- Three-Phase Phase Loss Protection (Instant trip)
- Stall Protection (D-Time + O-Time dual delay)
- Three-Phase Current Unbalance Protection
3.3 Электрические характеристики
Operating Power Supply: AC 180~480V (W7 wide voltage)
Выходные контакты: 5A/250VAC changeover contacts (95Северная Каролина, 96КОМ, 97НЕТ)
Коммуникация: RS485 Modbus RTU (Exclusive to Q suffix models)
Dielectric Withstand Voltage: 2kV for 1 минута
Потребляемая мощность: ≤250mA
3.4 Среда & Установка
Рабочая температура: -20℃~+60℃; Температура хранения: -30℃~+80℃
Влажность: 30%~85%RH, неконденсирующийся
Монтаж: Standard 35mm DIN rail or screw fixing
Основная схема: Two through-core CTs (Pass L1 and L2 through protector windows)
- Front Panel Knobs & Indicators
- LOAD(А): Motor rated current adjustment knob (5~60A)
- D-TIME: Start delay (Prevent false tripping during startup)
- O-TIME: Overload trip delay
- Green PWR LED: Питание нормальное
- Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
- RESET: Manual reset button; ТЕСТ: Unit self-test button
- Key Differences of PQ Suffix (vs Standard 60NW7)
- Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
- PCB of Q model integrates communication terminals, supporting multi-protector bus networking
- Ideal for automated production lines, pump stations, central air conditioning and centralized monitoring control rooms
- Типичные сценарии применения
380V three-phase fans, водяные насосы, воздушные компрессоры, belt conveyors and mixing motors
Motors with rated current 5~60A, no external current transformer required
Control cabinets requiring PLC remote motor data collection and remote fault reset
- Wiring Guidelines
- Основная схема: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
- Power Terminals A1/A2: Connect to AC380V control power supply
- Схема управления: 96COM as common terminal; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
- RS485 Communication: A/B differential bus, daisy-chain wiring for multiple devices
- Troubleshooting Matrix
| Явление неисправности | Root Cause | Решения |
| TRIP LED stays lit and cannot be reset | Continuous overload / motor stall | Уменьшите нагрузку, increase set current, check mechanical jamming |
| TRIP LED flashes twice | Phase loss | Inspect main circuit fuses, contactor contacts and motor wiring |
| No response after power-on, PWR LED off | Abnormal power supply to A1/A2 | Measure 380V power supply, replace the protector |
| No Modbus communication data | A/B wires reversed / duplicate device addresses | Swap RS485 A/B polarity, set unique address for each device |
- Alternative Models in the Same Series
- Non-communication version: EOCRSS-60NW7P (No RS485, более низкая стоимость)
- 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
- Higher current rating: For motors over 60A, select EOCRSS-100 series with external CT