 Siemens 6EP1437-2BA10 Industrial Power Supply

Siemens 6EP1437-2BA10 SITOP POWER 40 Three-Phase Industrial Power Supply

  1. Model Code Breakdown

6EP1437-2BA10

6EP: Standard industrial power supply series of SITOP

1437: High-power three-phase AC model, 40A output platform

2: Basic standard version (without redundant diagnostic interface)

BA: DIN rail mounting, 24VDC output

10: 3-phase 400–500V input, 40A / 960W output specification

  1. Core Electrical Parameters

Input Side (3-Phase Industrial Grid)

Input format: 3×400~500V AC, 3-phase 5-wire L1/L2/L3/PE

Frequency: 50/60Hz

Voltage dip tolerance: Minimum 340V for 2 seconds without output collapse

Wire gauge for input terminals: 0.5~4mm² solid/stranded copper wire

Output Side (Standard Industrial 24VDC)

Rated output: 24VDC / 40A, total power 960W

Adjustable output voltage range: 22.8~26.4V (tweaked via potentiometer at bottom)

Ripple & noise: Ripple <150mVpp, peak noise <240mVpp

Output terminals: Dual groups of +/terminals for parallel connection; wire gauge 0.5~10mm²

Parallel expansion: Two identical units can be directly paralleled for max. 80A output

Protection Functions (Full-condition Protection)

  1. Short-circuit protection: Automatic hiccup current limiting, auto-recovery after fault clearance
  2. Overvoltage Protection (OVP): Output cut-off when voltage >27V
  3. Overload Protection (OLP): Current limiting at 120% rated current
  4. Over-temperature Protection (OTP): Shutdown on overheat, auto-restart after cooling down
  5. Protection against input phase loss, surge and industrial EMC interference

III. Mechanical & Environmental Specifications

Mounting: Vertical installation on standard 35mm DIN rail

Overall dimensions (W × H × D): 160 × 125 × 121 mm

Net weight: Approx. 2.0 kg

Protection class: IP20 (for cabinet installation only)

Operating temperature: 0~+55°C (full power derating required above 55°C)

Storage / transport temperature: -25℃~+85℃

Humidity: 5%~95%RH, no condensation

Certifications: CE, UL, GL marine certification; compliant with EN61010, EN61000 industrial EMC standards

  1. Comparison Table of Same-Series 3-Phase Power Supplies
Order No.Input24V OutputPowerPositioning
6EP1436-2BA103AC 400–500V20A480WMedium-capacity 3-phase power supply
6EP1437-2BA103AC 400–500V40A960WHigh-power standard 3-phase power supply
6EP1437-3BA003AC 400–500V40A960WEquipped with relay signal output (fault contacts 13/14)
  1. Terminal Definition
  2. Input terminals: L1, L2, L3, PE (3 phases + protective earth)
  3. Output terminals: Dual sets of +24V, 0V (parallel for current sharing)
  4. Voltage trimming potentiometer: Located at bottom; adjust with flat screwdriver
  5. Indicator light: Solid green = normal output; off / flashing = fault (phase loss, short circuit, overheating)
  6. Typical Application Scenarios
  7. Large PLC control cabinets (S7-1500/400, full-station power supply for ET200SP distributed I/O)
  8. Multi-axis servo systems, inverter control stations, robot workstations
  9. Packaging, logistics sorting, automotive welding & assembly production lines
  10. Water treatment, wind power, metallurgy, cement and other high-power industrial control equipment
  11. Centralized 24V power supply scenarios requiring 3-phase industrial incoming power and high current loads

VII. Replacement & Capacity Expansion Solutions

  1. Upgraded same-spec model: 6EP1437-3BA00 (with fault relay contacts for PLC diagnostic connection)
  2. Capacity expansion: Parallel two 6EP1437-2BA10 units for max. 80A / 1920W output
  3. Downsized alternative: 6EP1436-2BA10 (20A / 480W) for half-load applications

VIII. Installation Prohibitions & Troubleshooting Guide

Forbidden Operations (Critical Restrictions)

  1. Horizontal or upside-down mounting is strictly prohibited; blocked cooling air duct triggers rapid over-temperature protection
  2. Long-term power-on with direct output short circuit will cause continuous hiccup power derating
  3. Long-term operation with missing input phase accelerates aging of internal power components
  4. Do not install alongside high-power inverters without partition plates to avoid EMC interference

Common Fault Matrix

PhenomenonRoot CauseCountermeasures
Green light off, no 24V output3-phase power loss, circuit breaker tripped, internal overheatingCheck 3-phase incoming voltage; power off and cool down then restart; clean dust in air duct
Green light flashing, output voltage dropOutput overload / short circuitDisconnect loads and locate short circuit by segmentation; limit total load within 40A
Output voltage below 23V under loadUndersized cables causing excessive voltage dropThicken 24V main cables; add auxiliary power supplies nearby
Frequent over-temperature shutdownAmbient temp >55℃, clogged air duct, fully enclosed cabinetInstall cabinet cooling fan, lower ambient temperature, reserve ≥50mm top & bottom ventilation clearance

Official Overall Dimensions of Siemens 6EP1437-2BA10 (SITOP POWER 40 3-Phase 40A Power Supply)

  1. Overall Unit Dimensions (W × H × D, unit: mm)

160 × 125 × 121 mm

Width (horizontal along DIN rail): 160 mm

Height (vertical cooling air flow direction): 125 mm

Depth (cabinet depth direction): 121 mm

Net weight: Approx. 2.0 kg

  1. Dimension Differentiation of Confusable Same-Series Models (Avoid Errors in Procurement & Cabinet Layout)
Order No.SpecificationW × H × D (mm)Weight
6EP1436-2BA103-phase 20A90 × 125 × 1201.6 kg
6EP1437-2BA103-phase 40A (without fault contacts)160 × 125 × 1212.0 kg
6EP1437-3BA003-phase 40A (with fault relay)160 × 125 × 1212.0 kg
6EP1437-2BA20 (New PSU300S Series)New generation 40A145 × 145 × 1503.1 kg
  1. Cabinet Installation Clearance Requirements
  2. Mounting rail: Standard 35mm TH35 DIN rail, vertical installation (terminals downward)
  3. Top & bottom ventilation clearance: Reserve at least 40mm for heat dissipation; derating mandatory if ambient temp exceeds 55℃
  4. Side-by-side mounting: Units of same model can be tightly arranged without extra spacing

Supplementary Note

Dimensions such as 250×180×92 and 145×145×150 shown on some foreign websites belong to the new PSU300S model 6EP1437-2BA20, which is incompatible with the legacy 6EP1437-2BA10. Cabinet cutout and DIN rail layout cannot be shared between them.