Schneider VPL12N Power Factor Correction Controller - คอนแทคเตอร์,เบรกเกอร์,เซ็นเซอร์,ตัวเข้ารหัส,บมจ,ตัวแปลง

วีแชท: +86-13184948252 วอทส์แอพพ์: 0086-13811255435 อีเมล: kent@bestcontactor.com

เกี่ยวกับ ติดต่อ |

 Schneider VPL12N Power Factor Correction Controller - คอนแทคเตอร์,เบรกเกอร์,เซ็นเซอร์,ตัวเข้ารหัส,บมจ,ตัวแปลง

บมจ/

Schneider VPL12N Power Factor Correction Controller

PowerLogic series 12-step power factor correction controller (PFC), used in low-voltage reactive power compensation cabinets to switch capacitor banks. It is the upgraded replacement for the obsolete VarLogic NR12. ✅ Model Code Explanation VPL = VarPlus Logic series reactive power compensation controller 12 = Maximum 12 switching outputs (three-phase common compensation, contactor solution) N = ...

  • รายละเอียดสินค้า

PowerLogic series 12-step power factor correction controller (PFC), used in low-voltage reactive power compensation cabinets to switch capacitor banks. It is the upgraded replacement for the obsolete VarLogic NR12.

✅ คำอธิบายรหัสรุ่น

VPL = VarPlus Logic series reactive power compensation controller

12 = Maximum 12 switching outputs (three-phase common compensation, contactor solution)

N = Basic version with RS485 Modbus, no split-phase compensation function

Peer models for reference:

VPL06N: 6-step common compensation

VPL18T / VPL24T: Versions supporting split-phase compensation and mixed compensation

📌 ข้อมูลจำเพาะทางไฟฟ้าหลัก

จัดหา & measurement voltage: 90~550V AC, 50/60เฮิรตซ์ (ช่วงแรงดันไฟฟ้ากว้าง, compatible with 380/400V systems)

การวัดกระแส: 0~5A (CT secondary side)

เอาท์พุต: 12 relay contact outputs for capacitor contactor control

การสื่อสาร: RS485 Modbus RTU, connectable to central monitoring system

แสดง: จอแอลซีดีที่มีแสงพื้นหลัง, shows cosφ, แรงดันไฟฟ้า, ปัจจุบัน, ทีเอชดี, switching cycles, สัญญาณเตือน

โหมดการทำงาน: อัตโนมัติ / คู่มือ; configurable target power factor, switching delay, automatic step capacity recognition

ความแม่นยำ: Current ±1%; cosφ ±2%; voltage THD ±2%

📐 Mechanical & Installation Data

Cutout size: 138×138 mm

มิติโดยรวม: 144×144×58 mm

น้ำหนัก: 0.6 กก

ระดับการป้องกัน: Front panel IP41, ด้านหลัง IP20

การติดตั้ง: Panel flush mount, cabinet plate thickness 1~3mm

🧾 Function List

  1. Automatically switch capacitor banks to maintain set target power factor (ค่าเริ่มต้น 0.95 อุปนัย)
  2. Automatic single-step capacity recognition, switching cycle counter, service life logging
  3. การตรวจสอบฮาร์มอนิก (voltage THD, individual harmonics), แรงดันไฟฟ้าเกิน/แรงดันตก, กระแสเกิน, detuning alarms
  4. 1 passive digital input (external status signal)
  5. Generator mode support (four-quadrant measurement)
  6. Modbus upload: ตัวประกอบกำลัง, พลังงานปฏิกิริยา, แรงดันไฟฟ้า, ปัจจุบัน, สัญญาณเตือน, step status
  7. Switching delay adjustable from 1~6500s, multiple control algorithms available

🔁 Replacement Reference

Obsolete model VarLogic NR12 → Direct replacement VPL12N (compatible cutout, similar control logic)

เทียบเท่าในประเทศ: ABB RVC-12, Acrel ARC-12 and other 12-step compensation controllers

⚠️ Selection Notes

VPL12N for three-phase common compensation only; select VPLxxT models if split-phase / mixed compensation is required

Incorrect CT polarity or phase sequence will cause abnormal control; perform automatic step recognition after power-on

No built-in thyristor drive output; only for contactor-based capacitor switching

  1. Terminal Wiring Description for VPL12N (text wiring diagram, standard 380V three-phase common compensation)

หลักฐานสำคัญ: VPL12N common compensation only, no split-phase function. CT shall be installed on main incoming feeder, not capacitor branches. CT secondary must never be open-circuited.

เทอร์มินัลสัญญาณคำอธิบายการเดินสายไฟ
ยู1, ยู2Voltage measurement & แหล่งจ่ายไฟConnect to two phases of incoming feeder (เช่น. L1, L2), 90~550V AC; fuse recommended; voltage taken from the same primary side as CT
S1, เอส2CT current inputCT secondary S1 → S1, S2 → S2; remove CT secondary shorting link before energization; คู่บิด, 2.5มม.²; CT ratio set in menu 100; CT polarity & phase sequence are insensitive
1~12, คอม12 relay switching outputs (ผู้ติดต่อแบบพาสซีฟ)1~12: NO contacts for each step; คอม: เทอร์มินัลทั่วไป. Each circuit drives capacitor contactor coil. การจัดอันดับการติดต่อ: AC250V / 5ก; drive contactor only, not capacitors directly
AL1, AL2Common alarm passive contactClosed on any alarm, for external sound-light alarm
F1, F2Fan temperature control contactClosed when cabinet temperature exceeds threshold set in menu 511, controls cooling fan
D0, D1RS485 Modbus RTUD0=B, D1=A; fit 120Ω terminator at bus end; shield single-ended grounding; ที่อยู่ & baud rate set in communication menu
DI+, จาก-External passive digital inputสัมผัสแห้ง, commonly used for generator mode switching or interlock (block compensation on undervoltage trip)

✅ Standard topology summary:

Main incoming L1/L2 → U1/U2 (แหล่งจ่ายไฟ & voltage measurement); main feeder CT secondary → S1/S2; outputs 1~12 to coils of 12 capacitor contactors; AL1/AL2 for alarm; D0/D1 for Modbus communication to SCADA.

⚠️ Wiring Critical Rules:

  1. CT secondary circuit must not be open-circuited; short CT secondary before maintenance
  2. Outputs are passive relay contacts. Coil power supply comes separately from cabinet, not supplied by controller
  3. Fuse must be fitted on voltage loop to prevent phase-to-phase short circuit and controller damage
  4. Voltage sampling must be on upstream incoming side, not downstream of capacitors
  5. Standard Commissioning Procedure after Wiring
  6. Double-check wiring, disconnect all capacitor circuits and release contactors
  7. เปิดเครื่อง, verify voltage and current readings on display; I Lo = current <15มิลลิแอมป์, all steps locked off
  8. เข้าเมนู 100: set CT ratio, แรงดันไฟฟ้าของระบบ, target cosφ (ค่าเริ่มต้น 0.95 อุปนัย)
  9. เมนู 200: switching delay, overvoltage/undervoltage threshold, harmonic protection threshold
  10. เมนู 308: enable automatic step recognition (Auto detect step), manually trigger each step sequentially; controller records kVAr per step automatically
  11. After recognition finished, switch to Auto mode and monitor switching logic

III. Alarm Codes & Troubleshooting List (ชไนเดอร์ official alarms)

  1. I Lo (Low Current Alarm, frequent fault)

อาการ: ปัจจุบัน <15มิลลิแอมป์, all steps forced open, no switching

การแก้ไขปัญหา:

CT secondary shorting link not removed

Loose or broken wiring on S1/S2

No load on CT primary or very light load

Excessive CT ratio, insufficient secondary current under light load

Poor connection or accidental short at terminal block

  1. StEP FLtY + step number flashing (Step Fault)

อาการ: Controller retries switching 3 ครั้ง, marks step faulty and locks it for 24h; lock can be cleared early by power cycle

การแก้ไขปัญหา:

Fuse or MCB tripped for corresponding branch

Burnt contactor coil, stuck auxiliary contact or mechanical jam

Damaged, ปูด, open-phase or degraded capacitor

Step capacity too large, recognition failure under light load

Check menu 403 whether the step is manually set to OFF

  1. PFC (Compensation Failure, target power factor unreachable)

อาการ: Continuous under-compensation or over-compensation, cosφ cannot reach set value

การแก้ไขปัญหา:

Total installed capacitor capacity insufficient or capacitors heavily degraded

Multiple faulty locked steps reduce available capacity

Wrong CT phase or wrong voltage sampling point

Heavy fluctuating load or frequent impulse load

Target power factor set too high

  1. พัดลม (Fan Alarm)

อาการ: Cabinet temperature exceeds threshold in menu 511, F1/F2 contact closes

การแก้ไขปัญหา:

การระบายอากาศของตู้ไม่ดี, blocked fan

อุณหภูมิแวดล้อมสูง, excessive capacitor heating

Temperature threshold in menu 511 set too low

  1. THi (การป้องกันอุณหภูมิเกิน)

อาการ: Temperature exceeds secondary limit, controller locks switching for ~30 minutes, resumes automatically after cooling

การแก้ไขปัญหา:

การระบายอากาศของตู้ไม่ดี, controller mounted close to busbars

แสงแดดโดยตรง, controller surrounded by high-heat components

  1. อฟ / UV Overvoltage / แรงดันตก

อาการ: Voltage out of configured range, compensation stops, capacitors blocked (การป้องกันตัวเก็บประจุ)

การแก้ไขปัญหา:

Naturally high system voltage (common during light load at night)

Wrong voltage sampling wiring

Narrow overvoltage/undervoltage window setting

  1. ทีเอชดี (Harmonic Overlimit Alarm)

อาการ: Voltage THD exceeds threshold, switching locked to avoid harmonic amplification and capacitor burnout

การแก้ไขปัญหา:

Large number of variable frequency drives and rectifier loads, high harmonic distortion

No series reactor on capacitor branches

Harmonic threshold set too low

  1. SPLx (Step Power Loss, Step x capacity degradation)

อาการ: Detected reactive output of this step drops by more than 25%, alarm for capacitor degradation

การแก้ไขปัญหา:

Measure capacitor current and compare with rated current to confirm ageing

Poor contactor contact or semi-blown fuse

Step recognition data captured under abnormal operating condition → re-run automatic step recognition

  1. Modbus communication failure (D0/D1)

การแก้ไขปัญหา:

A/B (D1/D0) ย้อนกลับ (ที่พบบ่อยที่สุด)

ที่อยู่, อัตรารับส่งข้อมูล, parity mismatch with host SCADA

Missing terminator or multiple terminators on bus

Multi-point grounding of shield causing interference

  1. General Fault Troubleshooting (no alarm but abnormal behaviour)
  2. Controller does not switch capacitors, ไม่มีการปลุก

Confirm mode in menu 308 is Auto (not manual)

Current cosφ already better than target, no compensation required

Check alarm history for hidden alarms

Too long switching delay configured

  1. Frequent rapid switching (hunting / การสั่น)

Single-step capacity too large, large gap between steps

Switching delay too short

Rapidly fluctuating load

Target power factor set too high

  1. Manual switching works, auto mode does not switch

Locked by I Lo, อฟ, ทีเอชดี, THi or other protection

Wrong CT phase / sampling, reactive power direction detected reversed

  1. Over-compensation (leading PF) once switched on

Wrong CT phase

Incorrect step recognition, step capacity overestimated

Low inherent reactive load

  1. ข้อควรระวังด้านความปลอดภัย

Isolate power and apply lockout-tagout before any voltage / CT circuit work; short CT secondary before maintenance

Capacitors must be fully discharged after power-off to prevent electric shock

VPL12N relay outputs cannot be paralleled for higher capacity; add intermediate relay if larger driving capacity is needed

Schneider VarPlus Logic (VPL) Power Factor Correction Controller | แบบอย่าง & รายการหมายเลขคำสั่งซื้อ

ชุด: PowerLogic VarPlus Logic; N = relay output (contactor switching); T = thyristor drive (solid-state switching, supports split-phase / mixed compensation)

All models equipped with RS485 Modbus RTU, การตรวจสอบฮาร์มอนิก, automatic step recognition, ติดต่อปลุก, fan output

✅ Current Production VPL Series (Model = Order Number)

หมายเลขคำสั่งซื้อ.ขั้นตอนCompensation TypeDrive Typeคำอธิบาย
VPL06N6 ขั้นตอนThree-phase common compensation onlyRelay contact (คอนแทค)Basic 6-loop common compensation, for small cabinets
VPL12N12 ขั้นตอนThree-phase common compensation onlyRelay contact (คอนแทค)ใช้กันอย่างแพร่หลาย, 12-step common compensation
VPL18N18 ทั่วไป / 6 แยก / ผสมทั่วไป / แยก / mixed selectableRelay contact (คอนแทค)18 เอาท์พุทรีเลย์, mixed compensation available
VPL18T18 ทั่วไป / 6 แยก / ผสมทั่วไป / แยก / mixed selectableThyristor driveSolid-state switching for frequent switching duty
VPL24T24 ทั่วไป / 8 แยก / ผสมทั่วไป / แยก / mixed selectableThyristor driveTop model, maximum 24-loop solid-state compensation

Model explanation: VPL=VarPlus Logic; digits = maximum steps; N=contactor relay version; T=thyristor solid-state version

❌ Obsolete VarLogic Series (replacement reference only, not for new purchase)

หมายเลขคำสั่งซื้อ.แบบอย่างขั้นตอนรุ่นทดแทนหมายเหตุ
52448NR66-step commonVPL06NOld 6-step, ยกเลิกแล้ว
52449NR1212-step commonVPL12NOld 12-step, large stock in field
52450NRC1212-step, 690V capableVPL12NOld wide voltage VarLogic version

📌 Selection Quick Guide

  1. Contactor switching, common compensation only → VPL06N / VPL12N
  2. Contactor switching, split-phase / mixed compensation required → VPL18N
  3. Thyristor dynamic compensation, การสลับบ่อยครั้ง, split/mixed compensation → VPL18T / VPL24T
  4. Retrofit for old NR6/NR12 cabinets, cutout compatible, direct swap → VPL06N / VPL12N

📎 Shared Specifications for All VPL

แรงดันไฟฟ้า: 90~550V AC, 50/60เฮิรตซ์

CT secondary input: 0–5A

คัตเอาท์: 138×138mm, panel size 144×144mm

การสื่อสาร: RS485 Modbus RTU