OMRON NX102-1020 Modular CPU Unit - المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول

ويشات: +86-13184948252 واتس اب: 0086-13811255435 بريد إلكتروني: كينت@bestcontactor.com

عن اتصال |

 OMRON NX102-1020 Modular CPU Unit - المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول

بلك/

OMRON NX102-1020 Modular CPU Unit

OMRON NX1 Series Machine Automation Controller (MAC, Modular CPU Unit) Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment. ✅ Model Code Explanation NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, المجموع 6 physical axes (الأعلى. 15 axes including virtual axes), ...

  • تفاصيل المنتج

اومرون NX1 Series Machine Automation Controller (MAC, Modular CPU Unit)

Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment.

✅ Model Code Explanation

NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, المجموع 6 physical axes (الأعلى. 15 axes including virtual axes), supports direct database connection.

📌 Core Specifications

غرضمواصفة
ذاكرة البرنامج5 ميغابايت
Variable Memory33.5 ميغابايت (Retain area:1.5 ميغابايت, Non-retain area:32 ميغابايت)
Minimum Primary Task Cycle1 آنسة
Synchronous Axes (Interpolation Axes)2 محاور
PTP Point-to-Point Axes4 محاور
الأعلى. Axes including Virtual Axes15 محاور
إيثركاتMaster station, ما يصل الى 64 EtherCAT nodes; supports EtherCAT ring redundancy
Local Expansionحتى 32 NX units on NX local bus (الإدخال/الإخراج, أمان, رابط الإدخال والإخراج, إلخ.)
Local I/O Points1024 نقاط; قابلة للتوسيع ل 8960 points with NX coupler
الموانئPORT1/PORT2: إيثرنت/IP + TCP/IP; PORT3: إيثركات
Built-in ProtocolsOPC UA Server, Direct SQL Database Connection, MQTT
برامج البرمجةSysmac Studio; Languages: شارع (نص منظم), إل دي (مخطط السلم), FB (Function Block)
تصاعدتركيب السكك الحديدية DIN; أبعاد:100(ح)×66(دبليو)×100(د) مم; وزن:470 ز
مزود الطاقةNX power supply unit sold separately (NX-PF series); No built-in battery; Variables backed up by capacitor

🧩 Key Features

  1. التحكم في الحركة

EtherCAT bus servo, supports 2-axis synchronization (linear/circular interpolation) + 4-axis independent point-to-point. Suitable for transferring, picking, simple flying shear and synchronous conveying.

  1. IT Integration (Sysmac Unique Feature)

Direct SQL Connection: Read/write MySQL, SQL Server, Oracle and other databases directly without upper computer relay

OPC تعميم الوصول إلى الخدمات: Native OPC UA server for connecting to MES and SCADA

MQTT: Connect to cloud platform for equipment data upload

  1. توسيع النظام

NX local bus can mount digital/analog modules, safety controller NX-SL, IO-Link master station; EtherCAT can connect servos, remote I/O and sensors.

  1. Battery-free Design

Capacitor backup for retaining variables. No regular battery replacement required to reduce maintenance cost.

🛠️ Typical Application Scenarios

Medium and small automation equipment: آلات التعبئة والتغليف, labeling machines, transfer manipulators, lithium battery front-end equipment, inspection machines and small production lines.

📊 NX102 Series Comparison (For Selection Reference)

NX102-1020: 2 synchronous axes + 4 PTP axes, المجموع 6 physical axes (هذا النموذج)

NX102-1100: 4 synchronous axes + 4 PTP axes, المجموع 8 physical axes

NX102-1200: 8 synchronous axes + 4 PTP axes, المجموع 12 physical axes

⚠️ ملاحظات

  1. No built-in power supply for CPU, NX-PF power supply module must be equipped separately;
  2. SD card slot for program backup and log recording;
  3. Direct database connection and MQTT require corresponding firmware version of Sysmac Studio;
  4. Second-hand inspection points: Check firmware version, EtherCAT port, Ethernet port and SD card slot upon power-on; back up programs and test axis control.

📎 Alternative Solutions Reference

Same brand upgrade: NX102-1100 (more synchronous axes)

Lower version on same platform: NX1P series (integrated type, no NX local bus expansion capability)

OMRON NX102-1020 Troubleshooting Checklist

Troubleshooting Principle: Check LED indicators first → Read Event Log online via Sysmac Studio → Distinguish Fatal Fault (Machine Stop) / Minor Fault (Continue Running) / Information Event. Eliminate root cause before resetting instead of clearing fault codes directly. Reference Manual: W503 (NJ/NX Fault Manual), NX102 Hardware Manual

  1. Power-on Failure, CPU Not Running (POWER Off / Solid Red)
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
POWER LED offDamaged NX-PF power module, no power supply, الأسلاك فضفاضة, excessive DC24V voltage drop1. Measure AC/DC input of power module; 2. Check backplane power terminals on DIN rail; 3. Test by replacing NX-PF power unit; 4. Check grounding and short circuit
POWER solid red, cannot enter RUNSerious CPU hardware fault, internal bus error, non-volatile memory damage, على درجة الحرارة1. Power off and cool for 30 minutes then power on; 2. Check event log: 00110000(Overtemp)/000D0000(Internal Bus)/000E0000(Flash End-of-Life); 3. Remove all NX expansion modules, run minimal system with only CPU + مزود الطاقة; 4. If fault persists under minimal system → CPU hardware failure, replace CPU
Repeated reboot after power-onInsufficient power rating, backplane short circuit, EMC noise interference1. Calculate total power consumption of NX rack; 2. Check metal debris on backplane; 3. Separate power cables and control cables and improve grounding
  1. Cannot Connect via Sysmac Studio (PORT1/PORT2 Ethernet Port)
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
Ping failure, NET ERR redIP mismatch, Windows firewall, damaged cable/connector, hardware damage of Ethernet port1. Set PC IP to same subnet, turn off Windows firewall; 2. Replace shielded cable, check L/A link lamp of PORT1/PORT2; 3. Reset CPU IP via BOOTP; 4. Test with PORT2; single port failure mostly indicates hardware damage
Ping OK but online download failedMismatched engineering version, CPU write protection, SD card abnormality1. Ensure Sysmac Studio firmware compatible with CPU firmware; 2. Check whether CPU write protection is enabled; 3. Remove SD card and retry; 4. Verify hardware configuration matches actual rack
Project download error, configuration verification failedMismatched model/quantity of NX local bus modules in project1. Verify model and position of NX modules on rack; 2. Remove redundant modules and test minimal rack; 3. Upload hardware configuration again
  1. EtherCAT Bus Fault (PORT3, Most Common in Motion Control)

NX102-1020 built-in EtherCAT master; axis control and remote I/O run on this bus. For EtherCAT fault, use Sysmac EtherCAT diagnosis and frame error counter to locate faulty segment

  1. NX Local Backplane Bus Fault (NX Rack Expansion I/O, Safety Module NX-SL)
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
ERR lamp on NX expansion unit, Event Log 000D0000اتصال ضعيف باللوحة الخلفية, damaged module, mismatched module model in configuration1. خارج السلطة, re-plug NX modules and ensure buckles locked; 2. Remove modules one by one to locate faulty unit; 3. Verify module model and position in project; 4. Replace damaged NX unit
  1. Motion Control Fault (NX102-1020: 2 Interpolation Axes +4 PTP Axes)
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
Axis homing failedWiring of home sensor, limit signal, home parameter, servo not ready1. Monitor status of home, positive/negative limit I/O; 2. Check servo ready signal; 3. Verify homing mode and offset parameters; 4. Confirm no hardware limit triggered
Motion error alarm during point-to-point / الاستيفاءSoft limit, over speed/acceleration, axis lock, servo fault, insufficient task cycle1. Check motion event code; 2. Verify soft limit parameters; 3. Reduce acceleration; 4. Confirm no stop/lock command on axis
Large multi-axis synchronization deviation, flying shear synchronization failureEtherCAT cycle fluctuation, abnormal encoder feedback, incorrect sync parameter1. Monitor position feedback of each axis; 2. Check encoder wiring; 3. Adjust synchronization control parameters; 4. Eliminate bus interference
  1. Built-in Communication Fault (OPC تعميم الوصول إلى الخدمات / MQTT / Direct SQL Database Connection)
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
OPC UA client connection failedميناء, security policy, certificate, IP routing, firewall1. Confirm CPU OPC UA service enabled; 2. Verify certificate trust; 3. Check port open status; 4. Confirm network route reachable
MQTT cloud upload failedWrong Broker address/port, network unreachable, certificate, heartbeat parameter1. Ping MQTT server; 2. Verify account, password and TLS setting; 3. Check MQTT event codes in event log
SQL database read/write failureDatabase IP/port, account permission, driver, packet loss1. Confirm database allows external access; 2. Verify table name, field and SQL statement; 3. Check CPU firmware version (old firmware does not support partial databases)
  1. SD Card Related Fault
ظاهرةالسبب المحتملخطوات استكشاف الأخطاء وإصلاحها
SD card ERR alarm, backup/log recording failedDamaged SD card, incorrect format, exceeded capacity limit, اتصال ضعيف1. Take out SD card and reinsert; 2. Use FAT32 format and OMRON recommended industrial SD card; 3. Replace damaged card; 4. Avoid consumer SD cards which easily cause log loss
  1. البيئية & Aging Hardware Faults
  2. Overtemperature Alarm (00110000): Poor cabinet heat dissipation, dust-clogged fan, ambient temperature out of range. Clean dust, تحسين التهوية; protection shutdown triggered above 60℃.
  3. Non-volatile Memory Life Warning (000E0000): Flash write/erase cycles exhausted. Prepare CPU replacement; frequent variable/log writing accelerates aging.
  4. Accidental shutdown due to noise interference: Power cables run in parallel with control cables, poor grounding, no shielding. Separate wiring, single-point grounding and add surge absorber.
  5. Fast Troubleshooting Workflow (On-site Operation Sequence)
  6. Power off → Visual inspection: الأسلاك, module buckles, damaged cables, تراب, short-circuit traces
  7. Power on and record all LED status (POWER/RUN/ERR, إيثركات, Ethernet L/A)
  8. Go online with Sysmac Studio, read Event Log and record hex event codes
  9. Minimal system test: NX-PF power + NX102-1020 only, remove all NX expansions and EtherCAT slaves to judge whether fault lies in CPU or external peripherals
  10. Segmented isolation: Disconnect EtherCAT segment by segment / remove NX modules one by one to locate faulty unit/cable
  11. Fix root cause → Clear fault → Reset CPU and retest
  12. اليد الثانية / Used NX102-1020 Special Inspection Checklist
  13. مظهر: Burn marks, oxidized backplane metal contacts, dents or deformation on housing
  14. Power on minimal system, confirm normal POWER without fatal hardware fault
  15. Go online to read firmware version and event log, check historical faults (flash life, overtemperature records)
  16. SD card slot read-write test
  17. Link test for PORT1/PORT2 Ethernet and PORT3 EtherCAT port
  18. Download blank project to confirm no configuration download error
  19. Connect EtherCAT servo to test axis enable and basic point-to-point motion

OMRON NX102 Full Series Model List (NX1 Modular Machine Automation CPU)

قاعدة ترميز النموذج:

NX102-ABCD

أ.ب: Axis specification; قرص مضغوط: Function version

لاحقة -00 = Standard Version (No direct database connection)

لاحقة -20 = DB Database Version (Support direct SQL connection & time-series data acquisition, same as NX102-1020)

All models share identical base hardware: 5MB program memory / 33.5MB variable memory (1.5MB retain area), EtherCAT master, dual EtherNet/IP ports, NX local backplane bus, minimum task cycle 1ms

  1. الإصدار القياسي (-00, No Direct SQL Database Connection)
نموذجSynchronous Interpolation AxesPTP Axesالأعلى. Physical Axesوصف
NX102-12008 محاور4 محاور12 محاورHigh-end model, تزامن متعدد المحاور, flying shear, electronic cam, for multi-axis equipment
NX102-11004 محاور4 محاور8 محاورMedium synchronous axes, for transfer and synchronous conveying
NX102-10002 محاور4 محاور6 محاورBasic interpolation model, same axis capability as NX102-1020, without database function
NX102-90000 axis4 محاور4 محاورNo interpolation, only 4 independent point-to-point axes; for general sequence control + simple point motion, no synchronous interpolation
  1. Database Connection Version (-20, Support Direct SQL & Time-series Data, SD Card Included)
نموذجSynchronous Interpolation AxesPTP Axesالأعلى. Physical Axesوصف
NX102-12208 محاور4 محاور12 محاورTop model, multi-axis sync + direct database connection, MES docking and data acquisition
NX102-11204 محاور4 محاور8 محاور4 synchronous axes + database, for packaging and lithium battery mid-stream equipment
NX102-10202 محاور4 محاور6 محاورThis model, 2-axis interpolation + 4 PTP, supports SQL, MQTT, OPC تعميم الوصول إلى الخدمات
NX102-90200 axis4 محاور4 محاورNo interpolation, only PTP axes, with database, for production line data acquisition + simple point motion
  1. Derivative Suffix Model (DH Version, Enhanced Time-series Data, Special Order)

NX102-1220-DH / NX102-1120-DH / NX102-1020-DH / NX102-9020-DH

DH suffix: Enhanced time-series data acquisition, designed for massive data logging projects, special order item, rarely used in standard domestic projects

  1. Special Supplementary Model

NX102-1D00: High-capacity logic CPU, no motion axes, focused on large-volume logic processing, no EtherCAT motion control. Used for logic and communication management of large production lines.

✅ Quick Selection Comparison Points

  1. 1000 /1020: 6 physical axes (2 الاستيفاء +4 PTP). Same axis performance. The only difference: NX102-1020 supports direct SQL database connection, NX102-1000 does not.
  2. 9000/9020: No interpolation function, only single-axis point motion; linear/circular interpolation and electronic cam synchronization are unavailable.
  3. All NX102 CPUs require separate NX-PF power supply module, no built-in power supply. Terminal cover NX-END02 is delivered together with CPU.
  4. Maximum total axes including virtual axes: 15 محاور (sum of physical + virtual axes).
  5. Cross-reference on Same Platform (Other NX1 Series CPUs for Selection)

NX1P: Economical integrated CPU, no NX local backplane expansion, for small standalone machines

NX701: High-end NX series, أداء أعلى, more axes, for large-scale equipment

السابق:

التالي: