The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. تتميز بالتعثر الحراري والمغناطيسي, نطاق تيار قابل للتعديل من 37 إلى 50 أمبير, قدرة كسر تبلغ 100 كيلو أمبير وتصنيف حماية الدخول IP20, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.
| مقطع الكود | تعريف | وصف تفصيلي |
| GV3 | سلسلة المنتجات | TeSys GV3 range motor circuit breakers for three-phase motor protection |
| ص | نوع المنتج | Standard thermal-magnetic trip unit with rotary knob operation |
| 50 | التصنيف الحالي | Max adjustable trip current 50A; thermal trip setting range: 37-50 أ |
| النموذج الكامل | GV3P50 | 3-pole thermal-magnetic motor breaker, 37-50 أ, EverLink BTR screw terminals, IP20 |
| رمز الطلب | FD6887 | Schneider official standard part number |
- Core Technical Specification Table
| فئة المعلمة | البيانات الفنية | ملاحظات |
| المعلمات الأساسية | ||
| تكوين القطب | 3ص (3-القطب) | For three-phase AC circuits |
| نوع الرحلة | Thermal-Magnetic | Combines thermal overload protection & magnetic short-circuit protection |
| وضع التشغيل | Rotary Knob Control | Manual switching with ON/OFF marking |
| الإنهاء | EverLink BTR screw-clamp terminals | Fast wiring to reduce loose connection risks |
| المعلمات الكهربائية | ||
| Thermal Trip Adjustment | 37-50 أ | Compatible with motors of different rated powers |
| تصنيف الجهد التشغيلي (واجهة المستخدم) | 690الخامس و | 50/60هرتز |
| تصنيف الجهد العزل (إي) | 690الخامس و | متوافق مع IEC 60947-2 |
| تصنيف التشغيل الحالي (أي) | 50أ | الحد الأقصى لتيار التشغيل المستمر |
| تيار الرحلة المغناطيسي | 700أ | Short-circuit instantaneous tripping value |
| القدرة على كسر في نهاية المطاف (وحدة العناية المركزة) | 100ال | At 400V |
| Matched Motor Rating | 22كيلو واط @ 400 فولت | للمحركات غير المتزامنة ثلاثية الطور |
| ميكانيكية & المعلمات المحيطة | ||
| حماية الدخول | IP20 | Finger-touch safe against live components |
| تصاعد | تركيب السكك الحديدية DIN | Standard 35mm top-hat rail |
| وزن | تقريبا. 0.45كجم | تركيب سهل & transportation |
| درجة حرارة التشغيل | -25درجة مئوية ~ +60 درجة مئوية | Suitable for most industrial environments |
| درجة حرارة التخزين | -40درجة مئوية ~ +85 درجة مئوية | Wide storage temperature range |
| الشهادات | ||
| Main Approvals | م, أول, وكالة الفضاء الكندية, سي سي سي, مجموعة شرق أفريقيا | Globally certified per international standards |
| Eco Certifications | بنفايات, يصل | EU-compliant environmentally friendly design |
ثالثا. Full GV3P Series Model List
| نموذج | Thermal Trip Range | Matched Motor Power @400V | تيار الرحلة المغناطيسي | رمز الطلب |
| GV3P40 | 25–40A | 18.5كيلوواط | 600أ | FD6886 |
| GV3P50 | 37-50 أ | 22كيلوواط | 700أ | FD6887 |
| GV3P65 | 48–65A | 30كيلوواط | 800أ | FD6888 |
| GV3ME50 | 37-50 أ | 22كيلوواط | 700أ | FD6890 |
| GV3ME65 | 48–65A | 30كيلوواط | 800أ | FD6891 |
| GV3ME80 | 56–80A | 37كيلوواط | 1000أ | FD6892 |
| GV3ME100 | 70–100A | 45كيلوواط | 1200أ | FD6893 |
- Alternative Cross Reference (نماذج الاستبدال)
- In-house Schneider Replacement
| النموذج الأصلي | استبدال | وصف |
| GV3P50 | GV3ME50 | Identical performance; ME is enhanced version with better accessory compatibility |
| GV3P50 | New production GV3P50 | No functional change, only production batch update |
- معادلات عبر العلامات التجارية
| ماركة | النموذج المعادل | Matching Grade | المزايا |
| ايه بي بي | MS132-50 | ★★★★★ | Same current rating, interchangeable mounting dimension |
| سيمنز | 3RV2031-4KA10 | ★★★★☆ | رحلة حرارية مغناطيسية, fits 22kW motors |
| إيتون | PKZM0-50 | ★★★★☆ | 3-تصميم القطب, 100كا كسر القدرة |
| شينت | NDM2-63M/3300 | ★★★☆☆ | Cost-effective for bulk replacement |
| لذيذ | CDM1-63M/3300 | ★★★☆☆ | Well-known domestic brand with high cost-performance |
- بيئات التطبيق & القضايا الميدانية
- التطبيقات الموصى بها
الأتمتة الصناعية: الزائد & short-circuit protection for 3-phase asynchronous pumps, fans and compressors
تصنيع: Production line motor control & machine tool protection
كهرباء البناء: Central air-conditioning & fire-fighting pump control
Energy Sector: Front-end protection for small generator sets and inverters
بنية تحتية: Wastewater treatment equipment & bulk material conveying systems
- Non-Recommended Applications
DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply
Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)
High Altitude: Derating mandatory above 2000m elevation
Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings
- حالات التطبيق النموذجية
قضية 1: Fan System Protection for Food Processing Plant
معدات: 3×22kW centrifugal fans, 380فولت/50 هرتز
حل: GV3P50 + LC1D65 contactor combination
حصيلة: Triple protection against overload, ماس كهربائى & خسارة المرحلة; equipment failure rate reduced by 40%
قضية 2: Submersible Sewage Pump Control at Wastewater Plant
معدات: 4×22kW submersible sewage pumps, 380فولت/50 هرتز
حل: GV3P50 + اتصالات مساعدة + PLC interlock control
حصيلة: Full motor protection plus remote monitoring, lower maintenance expense
- الامتثال للشحن الجوي & شهادة CE
- الامتثال للشحن الجوي
UN38.3: غير مطلوب; no built-in lithium battery or supercapacitor inside
فئة الشحن: General commodity without special transport restriction
Packing: Standard industrial carton to avoid transit damage
Shipping Document: Copy of CE certificate + RoHS compliance declaration available
- تفاصيل شهادة CE
المعايير المعمول بها: اللجنة الانتخابية المستقلة 60947-2 (LV switchgear) & اللجنة الانتخابية المستقلة 60947-4-1 (motor control equipment)
Valid Region: المنطقة الاقتصادية الأوروبية (EEA) & global territories accepting CE marking
صحة: Permanently valid complying with current normative requirements
سؤال: Check Schneider official website product page or certification database
سابعا. استكشاف أخطاء الأخطاء الشائعة وإصلاحها
| أعراض الخطأ | Probable Causes | Remedial Actions |
| Frequent thermal tripping | 1. الزائد للمحرك | 1. Inspect motor load |
| 2. Underset trip current | 2. Adjust rotary knob to correct setting | |
| 3. Excess ambient temperature | 3. Improve ventilation or derate operating current | |
| Unable to close | 1. Tripping latch not reset | 1. Toggle knob OFF then ON to reset |
| 2. Short circuit in wiring | 2. Troubleshoot short-circuit faults | |
| 3. التشويش الميكانيكي | 3. Clean or replace breaker | |
| No protection upon phase loss | 1. الأسلاك الخاطئة | 1. Recheck three-phase cabling |
| 2. Damaged trip unit | 2. Replace trip component | |
| 3. Severe 3-phase unbalance | 3. Balance connected loads | |
| Overheated terminals | 1. Loose terminals | 1. Retighten terminal screws |
| 2. Undersized cable | 2. Upgrade to proper wire gauge | |
| 3. Terminal oxidation | 3. Clean terminals or replace unit |
ثامنا. Sizing Guidelines & قواعد الاختيار السريع
Quick Selection Formula Summary
> GV3P series 3-pole thermal-magnetic breakers;
> Suffix number denotes upper current limit;
> 40 = 25–40A, 50 =37–50A, 65 max at 65A;
> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.
القواعد السريعة
- المطابقة الحالية: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Power Reference: At 400V, GV3P50 matches 22kW motor (~44A nominal)
- Accessory Option: الاتصال المساعد: GV3AE11 (1لا + 1NC) / GV3AE20 (2لا)
- Mounting Spacing: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
- تثبيت & تعليمات الأسلاك
- خطوات التثبيت
Confirm standard 35mm DIN rail
Snap breaker firmly onto rail
Incoming power: top-feed or bottom-feed acceptable
Motor cable connection: terminal tightening torque 2.5Nm recommended
- مواصفات الأسلاك
Wire cross-section range: 1.5mm² min ~35mm² max
صالة: EverLink BTR screw terminal compatible with copper/aluminum conductors
Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)
- حماية إي إم سي
Maintain ≥50mm clearance between breaker and contactors
Separate control wiring from power cables to avoid cross-interference
Install EMC filter if needed for EMI suppression
Full Application Overview for Schneider GV3P50 Motor Circuit Breaker
- Core Application Summary
Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: الزائد المحرك, ماس كهربائى & phase-loss protection plus manual switching, widely used in below industries:
- Detailed Application Classification
- الأتمتة الصناعية & تصنيع
| طلب | معدات | Protection Requirement | Application Benefit |
| التحكم في خط الإنتاج | الناقلون, sorters, آلات التعبئة والتغليف | Continuous running protection against overload shutdown | Improve line stability & reduce breakdown loss |
| أدوات الآلة | Milling, lathe & grinder spindle motors | Protection for frequent start-stop & instant short-circuit breaking | Protect costly equipment and extend service life |
| Bulk Handling | Bucket elevators, screw conveyors | كشك & phase-loss protection | Prevent burnout & cut maintenance cost |
| الآلات العامة | الطباعة, نسيج & plastic processing machines | حماية الزائد + emergency manual cut-off | Simplify control circuit & enhance operational safety |
- Fluid Conveyance Systems
| طلب | معدات | Protection Feature | Typical Parameter |
| Pump Set | Industrial pump, fire pump, مضخة مياه الصرف الصحي | Dual overload + phase-loss protection, moisture-resistant | 22كيلوواط/380 فولت,50هرتز, setting 37–50A |
| Fan Unit | Centrifugal/axial/induced draft fans | Light-load startup protection against impeller jamming | Adapt to current fluctuation from variable duct resistance |
| ضاغط | Air & ضواغط التبريد | Heavy-start & الحماية من الحرارة الزائدة | Tolerate frequent loading/unloading cycles |
| Vacuum Pump | صناعي & water-ring vacuum pumps | Low-current idle-running damage prevention | Adjustable setting for light-load operation |
- مبنى & Municipal Infrastructure
| Sector | نظام | Key Demand | طريقة التركيب |
| التدفئة والتهوية وتكييف الهواء | Central air-con, air handler, cooling tower | Stable continuous-duty protection | DIN rail mounted with contactor interlock |
| أتمتة البناء | Fire control, حماية & elevator room equipment | Emergency cut-off safety | Remote monitoring via PLC |
| Wastewater | Aerator & sludge processing units | تراب & moisture resistance | Cabinet installation with IP20 protection |
| الطاقة الجديدة | Small gen-set & PV inverter | التيار الزائد & grid-fault isolation | Rated up to 690V high-voltage system |
- Other Industrial Sectors
| صناعة | معدات | Special Requirement | Matching Advantage |
| زراعة | Irrigation pump & feed processor | Outdoor installation against grid voltage swing | Wide operating temp: -25درجة مئوية~+60 درجة مئوية |
| التعدين | Small conveyor & mine ventilation fan | Heavy startup + high short-circuit withstand | 100kA high breaking capacity |
| طعام & المشروبات | Mixer & معدات التعقيم | Sanitary & easy-clean layout | No exposed live parts for hygiene compliance |
| Pharma | الصيدلانية & cleanroom machinery | تحكم دقيق & معدل فشل منخفض | High accuracy thermal-magnetic trip characteristic |
ثالثا. Non-Recommended Applications (Avoidance Guide)
| Unsuitable Condition | سبب | الحل البديل |
| DC Circuit | Abnormal tripping characteristic under DC (rated only AC 50/60Hz) | Dedicated DC-rated Schneider circuit breakers |
| >30 Starts/Hour | Accelerated trip unit ageing & shortened service life | GV3ME enhanced series or match with soft starter |
| Altitude>2000m | Performance derating required | High-altitude specified breaker or add upstream protection |
| Strong Corrosive Atmosphere | Uncoated terminals prone to oxidation | Anti-corrosion coated model or protective enclosure |
| Explosion Hazard Zones | Standard version without ATEX certification | ATEX certified explosion-proof breakers |
| Single-Phase Motors | 3-pole structure cannot provide single-phase protection | GV2 single-phase motor breaker series |
- Detailed Field Application Cases
Case1: 22kW Fan Protection in Food Factory
Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit
مخطط: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact
منطق: Manual/Auto switch; auto stop & alarm upon overload
نتيجة: Triple protection realized; failure rate -40%, maintenance cost -30%
Case2: Submersible Sewage Pump Control at WWTP
Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation
مخطط: GV3P50 + PLC interlock + level transducer
حالة: بيئة رطبة, 10~15 starts/hour frequent cycling
نتيجة: Anti-stall burnout + remote auto-switching, improved system reliability
الحالة3: Central Air-conditioning for Shopping Mall
Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz
مخطط: GV3P50 + العاكس + temperature sensor
ميزة: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload
نتيجة: ≥30% energy saving, service life doubled, superior system stability
- Recommended Matching Components & نصائح الاختيار
- Recommended Matching List
| ملحق | رقم الجزء. | وظيفة | قيمة |
| موصل التيار المتردد | LC1D65 | Remote control for frequent start-stop | Enable automatic control & reduce manual operation |
| الاتصال المساعد | GV3AE11 | 1NO+1NC signal output | Alarm feedback or PLC interlock |
| مرحل الحمل الزائد الحراري | LRD4363 | Optional secondary overload protection | Double motor protection for enhanced safety |
| Control Pushbutton | XB4 Series | Manual start/stop | واجهة المستخدم البشرية & emergency shutdown function |
- Sizing Rules
- Power Match: 22كيلوواط (~44A @400V) optimally paired with GV3P50 (37-50 أ)
- Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
- Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
- عزم الدوران الأسلاك: Cable terminal tightening torque fixed at 2.5Nm
- Ambient Derate: ديراتي 1% rated current per every 1°C rise above +40°C ambient temperature