Schneider RM17TG20 Phase Loss Monitoring Relay

Harmony Zelio Control RM17-T Modular Monitoring Relay Type: Three-phase power monitoring relay, ذاتية التشغيل (no external auxiliary power supply required), تركيب السكك الحديدية DIN, 17.5 mm width ✅ Monitoring Functions Phase Sequence Detection: Reverse phase protection (motor reverse rotation protection) Phase Loss Detection: Triggers a fault when ≥2 phases are lost Three-phase Voltage Asymmetry (Unbalance) Detection This ...

  • تفاصيل المنتج

Harmony Zelio Control RM17-T Modular Monitoring Relay

يكتب: Three-phase power monitoring تتابع, ذاتية التشغيل (no external auxiliary power supply required), تركيب السكك الحديدية DIN, 17.5 عرض ملم

✅ Monitoring Functions

  1. Phase Sequence Detection: Reverse phase protection (motor reverse rotation protection)
  2. Phase Loss Detection: Triggers a fault when ≥2 phases are lost
  3. Three-phase Voltage Asymmetry (Unbalance) Detection

This model has no adjustable over/undervoltage thresholds, no delay knob, no test button, fast response upon fault.

📋 Core Electrical Specifications

Monitoring voltage range: 208~480V AC, operating limit 183~484V AC

تكرار: 50/60هرتز (±10%)

Output contacts: 2 اتصالات التحول (2ج/س), rated 5A; max switching voltage 250V AC/DC

Fault response time: ≤130 ms

Power-on start delay: ≤650 ms

استهلاك الطاقة: الأعلى. 22فرجينيا (400فولت/50 هرتز)

الحياة الميكانيكية: 30 مليون عملية; الحياة الكهربائية: 100,000 العمليات

تصاعد: DIN35 rail, IP20 (الجانب الأمامي)

درجة حرارة التشغيل: -20℃~+50℃

📌 Terminal Definition

L1, L2, L3: Three-phase input (directly connected to the monitored three-phase power supply; the relay draws power here)

11, 12, 14: 1st changeover contact (11 common, 12 NC مغلق عادة, 14 لا مفتوحة عادة)

21, 22, 24: 2nd changeover contact (21 common, 22 NC مغلق عادة, 24 لا مفتوحة عادة)

Operating Logic

Normal three-phase condition & تسلسل المرحلة الصحيح: Relay energizes and pulls in, 11-14 و 21-24 conduct; 11-12 و 21-22 يفتح.

Reverse phase / خسارة المرحلة / severe three-phase unbalance: Relay de-energizes and drops out, normally closed contacts close, normally open contacts open, used to cut off contactor circuit or trigger alarm signals.

🛠️ Typical Application Scenarios

Three-phase motors, مضخات المياه, المشجعين, معدات الرفع, ضواغط الهواء, الناقلات; prevents motor reverse rotation and burnout due to phase loss, widely used for 380V three-phase equipment protection.

⚠️ Model Selection Comparison (RM17 Series)

RM17TG20: تسلسل المرحلة + خسارة المرحلة + unbalance, no upper/lower voltage limits, no adjustable delay

RM17TU: With overvoltage and undervoltage monitoring

RM17TE: متعددة الوظائف (تسلسل المرحلة + خسارة المرحلة + unbalance + أكثر من / انخفاض الجهد)

RM17TT: Version with adjustable delay

🧩 Troubleshooting Guidelines

  1. الأسلاك: L1/L2/L3 three phases must all be connected; relay is self-powered. Loss of one single phase will not necessarily trigger alarm, protection activates only when two or more phases are lost.
  2. Phase sequence swap: Swap any two incoming phases, relay will act immediately.
  3. اتصالات: Normally open contacts close under normal condition; normally open contacts open and normally closed contacts close under fault condition.
  4. Minor three-phase unbalance will not trigger alarm; only asymmetry exceeding internal threshold will activate protection.

شنايدر RM17TG20 Application Scenarios

Core protection capability: Phase sequence reversal, خسارة المرحلة (≥2 phases lost), three-phase voltage unbalance monitoring. No over/undervoltage thresholds, no adjustable delay, narrow DIN rail module, ذاتية التشغيل, 2 مجموعات من الاتصالات التحول. Applied for 380V-class three-phase equipment power protection to prevent motor reverse rotation, burnout caused by phase loss and load damage due to unbalanced voltage.

🏗️ Hoisting & Conveying Industry (Most Typical)

  1. Overhead cranes, gantry cranes, tower cranes, port hoists: Prevent reversed phase sequence after cable replacement or switching operation, which may cause reverse movement of suspended loads and safety accidents; cut off main contactor circuit upon phase loss to protect motors.
  2. Lifts, مصاعد, السلالم المتحركة: Phase sequence protection for elevator main traction motors; protection against phase sequence disorder after power maintenance.
  3. سيور ناقلة, material transport machines: Motor reversal on production lines causes material piling and mechanical collision damage.

💧 Water, التدفئة والتهوية وتكييف الهواء, مضخات & المشجعين

  1. Water supply/sewage pumps, submersible pumps, circulating pumps: Reversal of pump motors leads to no water output and impeller damage; phase loss easily burns motors.
  2. Chillers for central air conditioning, مراوح برج التبريد, المرجل الناجم عن مراوح السحب: Large three-phase fans, phase sequence protection during power maintenance or mains power switching.
  3. Pumping stations, water treatment complete control cabinets, centralized three-phase power monitoring inside low-voltage cabinets.

📦 Packaging, النسيج & Automation Production Lines

  1. ماكينات التعبئة والتغليف, معدات التعبئة, آلات النسيج (carding, spinning machines), protection for three-phase main drive motors.
  2. خطوط الإنتاج الآلي, external 3-axis drive units of robots; avoid mechanical collision caused by wrong phase sequence of power supply.
  3. Retrofit projects for old equipment: Hardwired directly into contactor control loop without PLC, simple modification.

🏭 Construction Machinery, Mobile Equipment & Backup Power Switching

  1. Construction site mobile equipment, large agricultural three-phase equipment, three-phase units for refrigerated trucks.
  2. Mains/generator dual power switching circuit: Monitor phase sequence matching when generator is switched on, prevent reverse rotation during paralleling or on-load operation; output fault alarm signals upon power abnormality to interlock ATS switching.
  3. Power supply monitoring for sensitive three-phase loads, provide power fault DI alarm signal to PLC (two contact sets: one for shutdown protection, one for alarm).

⚙️ Air Compressors, Refrigeration & المحركات الصناعية العامة

  1. Screw air compressors, scroll air compressors, main motor protection with phase loss/reverse phase protection.
  2. Industrial refrigeration units, three-phase compressors for cold storage.
  3. Complete electric control cabinets for all types of general three-phase asynchronous motors, suitable for compact control boxes (only 17.5 عرض ملم).

✅ Application Prerequisites & Selection Limitations (Must Read Before Selection)

Supply voltage range 208~480V AC, commonly used for domestic 380V three-phase systems

⚠️ No single-phase phase loss protection: Alarm only when two or more phases are lost; no over/undervoltage monitoring. Select RM17TE series if over/undervoltage protection is required.

موقع التثبيت: PLC control cabinet, local motor control box, DIN35 rail mounting

Contact usage: One set wired in series with contactor coil for shutdown protection; the other set connected to PLC or sound-light alarm for fault alarm.

❌ Not Recommended Applications

Applications requiring single phase loss protection (alarm when only one phase is disconnected)

Applications requiring overvoltage or undervoltage threshold monitoring

Applications requiring custom fault delay (this model has no delay knob)

RM17TG20 Phase Sequence / Reverse Phase Protection Working Principle

RM17TG20 is a self-powered three-phase monitoring relay. L1/L2/L3 serve both as sampling inputs and the power supply for the relay itself. Built-in analog phase detection circuit detects the phase timing of three-phase voltages to judge whether it follows the forward sequence L1-L2-L3.

  1. حالة طبيعية (Correct Phase Sequence L1→L2→L3)

Peak values of three-phase voltages arrive sequentially following the standard timing L1, L2, L3. Internal phase logic confirms correct phase sequence:

Internal output electromagnetic relay pulls in

2 اتصالات التحول: 11-14, 21-24 (لا مفتوحة عادة) conduct; 11-12, 21-22 (NC مغلق عادة) يفتح

Panel indicator light is ON

دائرة التحكم: Normally open contact wired in series to contactor coil circuit, motor start is permitted.

  1. Reverse Phase Fault Condition (Any two phases swapped, reversed sequence L1-L3-L2)

When any two incoming phase wires are interchanged, the peak sequence of three-phase voltages is reversed (reverse phase sequence):

Internal phase detection circuit immediately identifies phase reversal

Output relay de-energizes and drops out (response ≤130 ms, لا تأخير)

Contact state flips: NO normally open opens, NC normally closed closes

Panel indicator light turns OFF

Control effect: Normally open contact wired in series with contactor coil opens, main motor contactor is cut off, motor start is prohibited to prevent reverse rotation; normally closed contact can be connected to PLC or sound-light alarm.

  1. Key Points
  2. Only detects phase timing, not motor rotation direction: It only checks the voltage phase sequence of incoming L1/L2/L3 power supply, not the actual rotation direction of the motor.
  3. No external auxiliary power required, powered directly from L1/L2/L3, الأسلاك البسيطة.
  4. تسلسل المرحلة, phase loss and unbalance share the same output: Reverse phase, خسارة المرحلة (≥2 phases lost) and severe three-phase unbalance all trigger the same action: relay dropout and contact state flip.
  5. This model has no adjustable thresholds and no adjustable delay; it acts instantly once reverse phase sequence is detected.
  6. Typical Wiring Logic

11/14 (لا مفتوحة عادة) wired in series with motor contactor KM coil circuit: When phase sequence is correct, circuit conducts and startup is allowed; upon reverse phase, circuit opens and startup is prohibited.

21/22 (NC مغلق عادة) connected to PLC digital input or sound-light alarm: Closes on fault to output fault alarm signal.

  1. التكليف & Verification Method

Field test: Under power-off condition, swap any two phase wires connected to the relay’s L1 and L2. تشغيل الطاقة, relay drops out immediately, indicator light goes off, contactor cannot pull in. Restore wiring to correct phase sequence, relay pulls in again and equipment startup is permitted.

⚠️Note: VFD-driven motors generally do not require this protection. The VFD rectifies power to DC bus, so incoming phase sequence will not affect motor rotation direction. لكن, this protection must be used for direct line-frequency driven equipment such as hoists and water pumps, for the bypass line-frequency circuit of VFDs, to avoid reverse rotation accidents after cable replacement during maintenance.

The phase sequence protection function of RM17TG20 cannot be set, disabled or threshold-modified. It is hardware fixed, with no DIP switches, potentiometers or software parameters.

وصف تفصيلي

  1. Fixed judgment logic

Factory preset: Only recognizes L1-L2-L3 forward phase sequence. Once incoming power becomes reverse sequence (L1-L3-L2), reverse phase fault is triggered immediately, relay drops out and contacts flip, response ≤130 ms, no adjustable delay.

حماية تسلسل المرحلة, خسارة المرحلة (≥2 phases lost) and three-phase unbalance monitoring are bound together. Any abnormal condition triggers the same output action; individual function cannot be disabled separately.

  1. No adjustable components on the body

There are no potentiometers, DIP switches or test buttons on the housing. No parameter modification can be made on the relay itself.

Phase sequence detection cannot be disabled

Phase sequence judgment criteria cannot be modified

Reverse phase action delay cannot be adjusted

  1. Only field workaround (NOT relay configuration)

If reverse phase sequence operation is required on site:

خيار 1: Swap L1/L2/L3 wiring connected to RM17TG20, change incoming wiring to L1-L2-L3 sequence, then relay judges as normal (only external wiring changed; relay function remains unchanged).

خيار 2: Bypass RM17TG20 contacts in the control circuit (electrical circuit modification, not recommended for long-term use, equivalent to abandoning protection).

📌 Model Selection Comparison

RM17TG20: Fixed functions (تسلسل المرحلة + phase loss ≥2 phases + unbalance), غير قابل للتكوين

RM17TE / RM17TT: Multi-function versions with adjustable unbalance thresholds, أكثر من / انخفاض الجهد; some advanced models support function selection.

Supplementary Reminder

If your project requires disableable phase sequence protection or alarm for single-phase loss, RM17TG20 is not suitable. Replace with RM17TE series or other models.

Schneider RM17T Three-phase Monitoring Relay (Harmony Zelio RM17T Series) قائمة النماذج الكاملة

All models are self-powered three-phase monitoring relays, powered from L1/L2/L3, DIN35 rail mount, 17.5 مم العرض الضيق, monitoring voltage: 208~480V AC, commonly used for domestic 380V systems.

  1. RM17TG (Fixed function type, no adjustment knobs, your target subseries)

RM17TG00: 1ج/س (1 الاتصال التحول), تسلسل المرحلة + خسارة المرحلة (≥2 phases) + unbalance, غير قابل للتعديل

RM17TG20: 2ج/س (2 اتصالات التحول), تسلسل المرحلة + خسارة المرحلة (≥2 phases) + unbalance, غير قابل للتعديل (your current model)

✅Feature: No potentiometer on housing, fixed firmware function, phase sequence protection cannot be disabled, no adjustable delay.

  1. RM17TA (تسلسل المرحلة + خسارة المرحلة + عدم التوازن على ثلاث مراحل, adjustable unbalance threshold)

RM17TA00: 1ج/س, تسلسل المرحلة, خسارة المرحلة, three-phase asymmetry (unbalance), adjustable unbalance threshold, no over/undervoltage

  1. RM17TU (تسلسل المرحلة + خسارة المرحلة + undervoltage monitoring, adjustable undervoltage)

RM17TU00: 1ج/س, تسلسل المرحلة, خسارة المرحلة, حماية الجهد المنخفض, adjustable undervoltage threshold, no overvoltage, no unbalance

  1. RM17TT (تسلسل المرحلة + خسارة المرحلة + unbalance + adjustable fault delay)

RM17TT00: 1ج/س, تسلسل المرحلة, خسارة المرحلة, unbalance; adjustable unbalance threshold + fault delay, no over/undervoltage

  1. RM17TE (Full-function flagship model, maximum adjustable items)

RM17TE00: 1ج/س, تسلسل المرحلة, خسارة المرحلة, عدم التوازن على ثلاث مراحل, الجهد الزائد + undervoltage window monitoring; adjustable unbalance threshold, over/undervoltage and delay, frequency deviation monitoring available.

  1. RM17UB (With neutral wire monitoring, نظام ثلاث مراحل بأربعة أسلاك)

RM17UB30: ثلاث مراحل + neutral line monitoring, neutral loss, phase over/undervoltage, suitable for distribution circuits with N line.

Model Function Comparison Table

نموذجAdjustable Thresholdاتصالات
RM17TG00❌1ج/س
RM17TG20❌2ج/س
RM17TA00Unbalance1ج/س
RM17TU00انخفاض الجهد1ج/س
RM17TT00Unbalance + تأخير1ج/س
RM17TE00Unbalance / زيادة&انخفاض الجهد / تأخير1ج/س
RM17UB30Voltage Threshold1ج/س

ملاحظات تكميلية

  1. Common features of RM17T series: All are self-powered, L1/L2/L3 three phases must be connected; phase loss logic: protection triggers only when ≥2 phases are lost, single phase disconnection will not trigger alarm.
  2. تصنيف الاتصال: 5أ, 250VAC for all models.
  3. Distinguish RM17 / RM22 / RM35: RM17 is 17.5mm narrow type; RM22 is wider; RM35 is large-size multi-function relay and not part of RM17T series.
  4. Quick selection guide:

Only phase sequence + phase loss required, two contact sets needed → RM17TG20

Full protection including over & undervoltage → RM17TE00

Undervoltage protection only → RM17TU00

Unbalance + delay required → RM17TT00