| Modellsegment | Bedeutung | Detaillierte Beschreibung |
| UA | Series Code | Special capacitor switching contactor Serie, designed exclusively for reactive power compensation capacitor switching |
| 16 | Nennstrom | 16A (AC-6b, 400V capacitor load), corresponding to approx. 12.5kVar compensation capacity |
| 30 | Main Contact Configuration | 3-pole all normally open (NEIN) Hauptkontakte, suitable for 3-phase capacitor banks |
| 10 | Hilfskontaktkonfiguration | 1 Normalerweise geöffnet (NEIN) + 0 Normalerweise geschlossen (NC) Hilfskontakte, used for control circuit signal feedback |
| RA | Besonderheit | Built-in damping resistor (Resistor-Assisted), suppresses capacitor switching inrush current; no additional reactor required |
- Grundlegende technische Spezifikationen
| Parameterkategorie | Technical Data | Bemerkungen |
| Grundparameter | ||
| Marke | ABB | Product ID: 1SBL181024R8010 (220-230V) / 1SBL181024R8510 (380-400V) |
| Typ | 3-pole capacitor switching contactor | Block type design, konform mit IEC 60947-4-1 |
| Nennbetriebsspannung | 690V und (50/60Hz) | Maximum working voltage |
| Hauptstromkreisparameter | ||
| Nennstrom (AC-6b) | 16A @ 400V | Special rating for capacitor loads; inrush current withstand >100×In |
| Bewerteter Kurzzeitstrom | 140A (0.1S) / 100A (1S) | Low-voltage system short-circuit withstand capability |
| Elektrische Ausdauer | 250,000 Operationen (Ue<500V) / 100,000 Operationen (500V≤Ue≤690V) | Mechanical life for capacitor switching cycles |
| Parameter des Steuerkreises | ||
| Spulenspannung | Standard: 220-230V/380-400V (50Hz); 230-240V/400-415V (60Hz) | Custom voltage levels available |
| Spulenstromverbrauch | Pick-up: ca. 180VA; Holding: ca. 22VA | AC laminated magnetic circuit design |
| Control Circuit Protection | Recommended 10A gG fuse | Standard protection for auxiliary circuits |
| Körperlich & Umgebungsparameter | ||
| Montageart | 35mm DIN rail mounting | Self-locking structure, no screws required |
| Gesamtabmessungen | W44mm × H90mm × D74mm | Standardmäßiger modularer Aufbau |
| Schutzklasse | IP20 (Spule & auxiliary terminals) | Konform mit IEC 60529 |
| Betriebstemperatur | -25°C bis +60°C | Suitable for industrial environment range |
| Terminal Type | Schraubklemmen, main circuit compatible with 1/2×18-10 AWG wires | Drehmoment: 9 in·lb (main/auxiliary/control circuit) |
- Structural & Funktionsmerkmale
3.1 Core Structure
Built-in Damping Resistor Module: 3 independent resistors connected in series to the main circuit, realizing capacitor pre-charging and limiting switching peak current to a safe level.
Special Contact Design: Main contacts adopt anti-welding alloy material to enhance arc erosion resistance and withstand frequent inrush current impact.
Mechanical Interlock Mechanism: Ensures resistors close before main contacts and open after main contacts, completing a full current-limiting protection cycle.
Modular Accessory System: Supports expansion with auxiliary contacts, surge suppressors and other accessories.
3.2 Key Functions
Inrush Current Suppression: Built-in resistors reduce switching inrush current from 100×In to about 10×In, greatly lowering contact ablation risk.
Reactor-Free Design: RA series with inherent current limiting; no need for external series reactors, saving installation space and cost.
Sicherer Betrieb: Capacitor bank must discharge to ≤50V before re-energization to prevent secondary inrush current caused by residual charge.
Signal Feedback: 1NO auxiliary contact for status indication and interlock control.
- Optional Accessories List
| Zubehörtyp | Modellbeispiel | Funktionsbeschreibung |
| Auxiliary Contact Block | UA-01 / UA-10 | Add 1NC or 1NO auxiliary contact to expand control circuit functions |
| Surge Suppressor | RC1-230 / RC1-400 | Absorbs back EMF during coil breaking to protect control circuits |
| Mechanische Verriegelung | 2900000 | Interlocks two contactors to prevent reverse connection of capacitor banks |
| Montagehalterung | Compatible with 35mm DIN rail | Improves mounting stability for vibration-prone environments |
- Cross-Brand Equivalent & Replacement List
| Marke | Äquivalentes Modell | Hauptunterschied | Anwendungsszenario |
| Schneider | LC1DK1610 | Also with built-in current-limiting resistor, 16A rated, 1KEIN Hilfskontakt | Direct replacement with ABB in reactive power compensation cabinets |
| Siemens | 3RT2016-1BB41 | Special capacitor type with built-in resistor, 16A, 1NEIN, suitable for 400V systems | Industrielle Automatisierungssysteme; check mounting dimension differences |
| ABB | UA16-30-10 (Non-RA) | No built-in resistor; requires external reactor, geringere Kosten | Light-load applications with small inrush current or systems with existing reactors |
| Eaton | DILM17-10C | Capacitor contactor, 17A, 1NEIN, built-in current-limiting circuit | Replacement for 16A class with higher margin |
- Auswahlrichtlinien & Alternative Lösungen
6.1 Wichtige Auswahlparameter
Capacitor Capacity: UA16-30-10RA suitable for 3-phase capacitor banks ≤12.5kVar@400V / ≤20kVar@600V.
Spulenspannung: Must match control supply voltage; common 220V/380V to avoid coil burnout.
Montage: Confirm 35mm standard DIN rail; special bracket required for non-standard rails.
Umgebungsbedingungen: Derate for high temperature (>40°C) with derating factor 0.8~0.9.
6.2 Recommended Alternative Solutions
| Anwendungsszenario | Recommended Solution | Vorteile |
| Standard Reactive Compensation Cabinet | UA16-30-10RA (Standardversion) | Built-in resistor, Es werden keine zusätzlichen Teile benötigt, einfache Installation |
| High-Frequency Switching (>1200 cycles/h) | UA16-30-10RA + Surge Suppressor | Extend contact life, reduce electromagnetic interference |
| Large-Capacity Capacitor Bank (>12.5kVar) | UA25-30-10RA (25A) | Fits larger capacity with consistent protection level |
| Budget-Limited Retrofit Project | UA16-30-10 + External Reactor | Niedrigere Kosten, requires extra installation space |
6.3 Installation & Wartungshinweise
- Vor der Installation: Ensure capacitors are fully discharged to ≤50V to avoid residual charge hazards.
- Verdrahtung: Main circuit wire cross-section ≥1.5mm²; control circuit ≥0.75mm²; ensure terminals are fully tightened.
- Wartungszyklus: Inspect contact wear every 6 Monate; recommend replacement after 100,000 cumulative operations.
- Fehlerbehebung: If contactor fails to operate, first check coil voltage and control circuit fuse.
ABB UA16-30-10RA is a dedicated damping resistor built-in capacitor contactor designed for low-voltage reactive power compensation systems.
Three series resistors suppress switching inrush current, protecting contacts and extending service life.
With 16A AC-6b rating suitable for 12.5kVar capacitor banks at 400V, 3-pole NO main contacts plus 1NO auxiliary contact fully meet standard control requirements.
Compared with ordinary contactors, the RA series needs no external reactor and features simple installation, making it an ideal choice for industrial and building power distribution reactive compensation systems.
Complete Model List of ABB UA Series Capacitor Switching Contactors
- Modellbenennungsregel
ABB UA series capacitor contactors adopt a unified naming format for quick parameter identification:
| Modellsegment | Bedeutung | Available Options |
| UA | Series Code | Special capacitor switching contactor |
| XX | Nennstrom (A, AC-6b @400V) | 16, 26, 30, 50, 63, 75, 95, 110, 140 |
| 30 | Main Contact Configuration | 3-pole NO, designed for 3-phase capacitor banks |
| XY | Hilfskontaktkonfiguration | 00(0NO+0NC), 10(1NO+0NC), 01(0NO+1NC), 11(1NO+1NC) |
| RA | Besonderheit | Built-in damping resistor for inrush current suppression |
| -VV | Spulenspannung | 24V, 110V, 220V, 380V etc. (AC/DC optional) |
- Full Model List by Current Rating
2.1 16A Series (≤12.5kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA16-30-00 | UA16-30-00RA | 0NO+0NC | 220V/380V | 1SBL181022R8010(Standard) / 1SBL181024R8010(RA) |
| UA16-30-10 | UA16-30-10RA | 1NO+0NC | 220V/380V | 1SBL181022R8010(Standard) / 1SBL181024R8010(RA) |
| UA16-30-01 | UA16-30-01RA | 0NO+1NC | 220V/380V | 1SBL181022R8110(Standard) / 1SBL181024R8110(RA) |
| UA16-30-11 | UA16-30-11RA | 1NO+1NC | 220V/380V | 1SBL181022R8210(Standard) / 1SBL181024R8210(RA) |
2.2 26A Series (≤20kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA26-30-00 | UA26-30-00RA | 0NO+0NC | 220V/380V | 1SBL281022R8010 / 1SBL281024R8010 |
| UA26-30-10 | UA26-30-10RA | 1NO+0NC | 220V/380V | 1SBL281022R8010 / 1SBL281024R8010 |
| UA26-30-01 | UA26-30-01RA | 0NO+1NC | 220V/380V | 1SBL281022R8110 / 1SBL281024R8110 |
| UA26-30-11 | UA26-30-11RA | 1NO+1NC | 220V/380V | 1SBL281022R8210 / 1SBL281024R8210 |
2.3 30A Series (≤25kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA30-30-00 | UA30-30-00RA | 0NO+0NC | 220V/380V | 1SBL281022R8010 / 1SBL281024R8010 |
| UA30-30-10 | UA30-30-10RA | 1NO+0NC | 220V/380V | 1SBL281022R8010 / 1SBL281024R8010 |
| UA30-30-01 | UA30-30-01RA | 0NO+1NC | 220V/380V | 1SBL281022R8110 / 1SBL281024R8110 |
| UA30-30-11 | UA30-30-11RA | 1NO+1NC | 220V/380V | 1SBL281022R8210 / 1SBL281024R8210 |
2.4 50A Series (≤40kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA50-30-00 | UA50-30-00RA | 0NO+0NC | 220V/380V | 1SBL341022R8010 / 1SBL341024R8010 |
| UA50-30-10 | UA50-30-10RA | 1NO+0NC | 220V/380V | 1SBL341022R8010 / 1SBL341024R8010 |
| UA50-30-01 | UA50-30-01RA | 0NO+1NC | 220V/380V | 1SBL341022R8110 / 1SBL341024R8110 |
| UA50-30-11 | UA50-30-11RA | 1NO+1NC | 220V/380V | 1SBL341022R8210 / 1SBL341024R8210 |
2.5 63A Series (≤50kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA63-30-00 | UA63-30-00RA | 0NO+0NC | 220V/380V | 1SBL371022R8010 / 1SBL371024R8010 |
| UA63-30-10 | UA63-30-10RA | 1NO+0NC | 220V/380V | 1SBL371022R8010 / 1SBL371024R8010 |
| UA63-30-01 | UA63-30-01RA | 0NO+1NC | 220V/380V | 1SBL371022R8110 / 1SBL371024R8110 |
| UA63-30-11 | UA63-30-11RA | 1NO+1NC | 220V/380V | 1SBL371022R8210 / 1SBL371024R8210 |
2.6 75A Series (≤60kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA75-30-00 | UA75-30-00RA | 0NO+0NC | 220V/380V | 1SBL381022R8010 / 1SBL381024R8010 |
| UA75-30-10 | UA75-30-10RA | 1NO+0NC | 220V/380V | 1SBL381022R8010 / 1SBL381024R8010 |
| UA75-30-01 | UA75-30-01RA | 0NO+1NC | 220V/380V | 1SBL381022R8110 / 1SBL381024R8110 |
| UA75-30-11 | UA75-30-11RA | 1NO+1NC | 220V/380V | 1SBL381022R8210 / 1SBL381024R8210 |
2.7 95A Series (≤75kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA95-30-00 | UA95-30-00RA | 0NO+0NC | 220V/380V | 1SBL401022R8010 / 1SBL401024R8010 |
| UA95-30-10 | UA95-30-10RA | 1NO+0NC | 220V/380V | 1SBL401022R8010 / 1SBL401024R8010 |
| UA95-30-01 | UA95-30-01RA | 0NO+1NC | 220V/380V | 1SBL401022R8110 / 1SBL401024R8110 |
| UA95-30-11 | UA95-30-11RA | 1NO+1NC | 220V/380V | 1SBL401022R8210 / 1SBL401024R8210 |
2.8 110A Series (≤90kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA110-30-00 | UA110-30-00RA | 0NO+0NC | 220V/380V | 1SBL411022R8010 / 1SBL411024R8010 |
| UA110-30-10 | UA110-30-10RA | 1NO+0NC | 220V/380V | 1SBL411022R8010 / 1SBL411024R8010 |
| UA110-30-01 | UA110-30-01RA | 0NO+1NC | 220V/380V | 1SBL411022R8110 / 1SBL411024R8110 |
| UA110-30-11 | UA110-30-11RA | 1NO+1NC | 220V/380V | 1SBL411022R8210 / 1SBL411024R8210 |
2.9 140A Series (≤110kVar @400V)
| Standardmodell | RA Built-in Resistor Type | Hilfskontakt | Typical Coil Voltage | Product ID Example |
| UA140-30-00 | UA140-30-00RA | 0NO+0NC | 220V/380V | 1SBL421022R8010 / 1SBL421024R8010 |
| UA140-30-10 | UA140-30-10RA | 1NO+0NC | 220V/380V | 1SBL421022R8010 / 1SBL421024R8010 |
| UA140-30-01 | UA140-30-01RA | 0NO+1NC | 220V/380V | 1SBL421022R8110 / 1SBL421024R8110 |
| UA140-30-11 | UA140-30-11RA | 1NO+1NC | 220V/380V | 1SBL421022R8210 / 1SBL421024R8210 |
- Coil Voltage Options (Universal for All Series)
| Voltage Type | Common Ratings | Anwendungsszenario |
| Wechselstrom | 24V, 48V, 110V, 220-230V, 380-400V, 400-415V | Standard industrial control circuits |
| Gleichstrom | 24V, 48V, 110V, 220V | Explosion-proof, fire control or low-noise environments |
| Wide Voltage | 200-240V und, 380-440V und | Areas with large grid voltage fluctuation |
- Key Selection Instructions
4.1 Standard Type vs RA Built-in Resistor Type
Standard (Non-RA): Requires external reactor for inrush suppression; geringere Kosten, suitable for systems with existing reactors.
RA Built-in Resistor Type: 3 built-in damping resistors reduce switching inrush from 100×In to approx.10×In; no extra components needed for easy installation.
4.2 Auxiliary Contact Selection
00: No auxiliary contacts, for simple control loops.
10 / 01: 1 NEIN / 1 NC for status indication and interlock.
11: 1NO+1NC for complex control logic such as automatic switching systems.
4.3 Capacitor Capacity Reference (@400V)
| Contactor Rated Current | Max Compatible Capacitor | Anwendung |
| 16A | 12.5kVar | Small commercial buildings & residential |
| 30A | 25kVar | Medium industrial equipment & Bürogebäude |
| 63A | 50kVar | Large factories & Handelszentren |
| 110A | 90kVar | Large production lines & regional substations |
- Zubehör & Expansion Options
| Zubehörtyp | Modellbeispiel | Beschreibung |
| Auxiliary Contact Block | UA-01 / UA-10 | Add 1NC or 1NO; expandable up to 4 Hilfskontakte |
| Surge Suppressor | RC1-230 / RC1-400 | Absorbs coil reverse EMF to protect control circuits |
| Mechanische Verriegelung | 2900000 | Interlocks two contactors to prevent capacitor bank reverse connection |
| Montagehalterung | For 35mm DIN rail | Enhance stability for vibration environments |
ABB UA series capacitor switching contactors cover full current range 16A~140A, providing standard type and RA built-in resistor type.
Flexible auxiliary contact configurations (00/10/01/11) and global compatible coil voltages are available.
The RA series effectively reduces switching inrush current, protects contacts and extends service life, making it the ideal solution for low-voltage reactive power compensation systems.
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien










![NXC-65 aus der Kunlun-Serie von CHINT Electric ist ein 3-poliger AC-Schütz, Nennstrom 65 A in der NXC-Serie. Das vollständige Modell wird normalerweise als NXC-65 ausgedrückt [Spulenspannung] [Frequenz] NXC-65 from the Kunlun Series by CHINT Electric is a 3-pole AC contactor, rated at 65A in the NXC series. The full model is typically expressed as NXC-65 [Coil Voltage] [Frequency]](https://www.bestcontactor.com/wp-content/uploads/2026/04/ScreenShot_2026-01-30_132315_324-419x560.png)