Marke: FRER (Italien)
Vollständiges Modell: MCOMV, Input 0~48VDC, DIN-Schienenmontage DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for SPS/DCS system acquisition.
Kernparameter (MCOMV;48VDC)
Eingang: 0 ~ 48V DC (50% Überlastfähigkeit)
Ausgabe: 0~20mA / 4~20mA (Standard industrial current loop)
Max Output Load: 750Oh
Auxiliary Supply: 20~60Vac/dc (Wide AC/DC power supply); 220VDC version available as option
Isolierung: Input-Output-Power three-way galvanic isolation
Montage: DIN rail snap mounting
Genauigkeitsklasse: 0.5
Ansprechzeit: <200MS
Anwendung: DC busbar, battery pack, -48V telecom power cabinet voltage measurement
Modelldefinition
MCOMV: FRER legacy model code for DC voltage transducer; new replacement series MCOVC
;48VDC: Input range 0~48V DC
Other ranges available in same series: MCOMV;60mV DC, MCOMV;60VDC, MCOMV;300VDC
Typische Anwendungen
- -48V battery bank voltage monitoring for telecom base stations
- DC panel & energy storage cabinet DC bus voltage acquisition
- Industrial power supply & electrochemical power source voltage transduction
- DC system signal isolation measurement in power plants & Fabriken
Ersatzmodelle
Original-Hersteller-Upgrade: MCOVC1 (for MCOMV 0~300V), MCOVC2 (Dual retransmission output)
Inländische Alternativen: Phoenix Contact, Pepperl+Fuchs, Suzhou Xunpeng and other DC voltage isolation transducers (0-48V-Eingang, 4-20mA-Ausgang)
Verkabelungsrichtlinien
- Input side: DC voltage signal, observe polarity strictly
- Output side: 4-20mA current loop, connect to AI module, normally 2-wire connection at PLC side
- Auxiliary power: 20~60V AC/DC wide range, compatible with 24V/48V DC panel & AC220V
Wichtiger Unterschied: MCOV (SPD maximum continuous operating voltage) ≠ MCOMV (FRER transducer). Abbreviation confusion frequently occurs.
FRER MCOMV;48VDC Complete Datasheet Parameter Table
Produkt: DC voltage isolation transducer (Obsolete legacy MCOMV, replacement series MCOVC)
Modelldefinition: MCOMV = DC voltage transducer; ;48VDC = Input range 0~48VDC
🔹 Electrical Specifications
| Parameter | Wert | Bemerkungen |
| Input Range | 0 ~ 48 VDC | Model MCOMV;48VDC |
| Kontinuierliche Überlastung | 1.5 × Un (50% Überlast) | Permanent withstand up to 72VDC |
| Transient Overload | 2 × Un | Short-term max 96VDC |
| Eingangsimpedanz | ≥100kΩ | High impedance, minimal loading effect on measured circuit |
| Ausgangssignal | 4~20mA DC (Standard current loop); 0~20mA optional | Single analog output |
| Max Output Load Resistance | 750 Oh | Higher load requires more auxiliary power margin |
| Genauigkeitsklasse | 0.5 | Max full scale error ≤ ±0.5%FS at 25℃ reference |
| Linearity Error | ≤ ±0.2% FS | |
| Temperaturdrift | ≤ ±100 ppm/℃ | Over full operating temperature range |
| Ansprechzeit | <200 MS (95% step response) | |
| Dielektrische Spannungsfestigkeit (Input ↔ Output ↔ Aux. Liefern) | 2.5kV Wechselstrom / 1min | Three-way galvanic isolation, Sicherheitsisolation |
| Auxiliary Supply | 20~60V AC/DC wide range | AC/DC universal; 220V DC customized version available |
| Stromverbrauch | ≤1,5W |
🔹 Environmental Conditions
| Parameter | Wert |
| Betriebstemperatur | -20℃ ~ +50℃ |
| Lagertemperatur | -40℃ ~ +80℃ |
| Relative Luftfeuchtigkeit | 5%~95 %, nicht kondensierend |
| Verschmutzungsgrad | Klasse 2 |
| Überspannungskategorie | KAT III |
🔹 Mechanical & Gehäuse
| Parameter | Wert |
| Montage | DIN 35mm rail snap mounting |
| Enclosure Material | Flame retardant plastic |
| Gehäuseschutz | IP20 (Körper); Terminal block IP00 |
| Gesamtdimension | W22.5mm × H90mm × D68mm (Narrow standard module) |
| Gewicht | Ca. 80G |
| Terminals | Schraubklemmen, max conductor cross-section 2.5mm² |
🔹 Model Portfolio (Available Ranges of MCOMV Series)
| Modellcode | Input Range |
| MCOMV;60mV DC | 0~60mV DC |
| MCOMV;48VDC | 0~48V DC |
| MCOMV;60VDC | 0~60V DC |
| MCOMV;300VDC | 0~300V DC |
🔹 Safety & Standards
Zertifizierung: CE, Konform mit EN 61010-1
Schutz: Output current limiting, limited reverse polarity protection for input
Anwendungskategorie: Industrial DC busbar, telecom -48V battery pack, DC panel voltage acquisition
🔹 Wiring Summary
- Eingang + / Eingang -: Measured DC voltage, strict polarity observation required
- Ausgabe + / Ausgabe -: 4~20mA current loop, two-wire connection to PLC AI channel
- Zu + / Zu -: Transducer auxiliary power supply 20~60V AC/DC
🔹 Model Change Note
MCOMV is legacy FRER code, eingestellt. Direkter OEM-Ersatz: MCOVC1 (single channel DC voltage transducer) with identical specs, pin assignment and mounting dimension.
🔹 Troubleshooting Reference
- Keine Ausgabe: Check auxiliary power, Klemmendichtheit, input polarity
- Fester 4-mA-Ausgang: Input open circuit or signal below lower limit
- Output stuck at 20mA: Eingangsbereichsüberschreitung oder kurzgeschlossene Eingangsverkabelung
- Lesedrift: Überprüfen Sie Erdungsinterferenzen und überprüfen Sie die Integrität der Isolierung
FRER MCOMV;48Beschreibung der VDC-Kalibrierung
Abschluss: Zur Zertifizierung steht eine messtechnische Kalibrierung zur Verfügung; Kein externes Nullpunkt-/Span-Trimmpotentiometer am Gerät. Das Öffnen und Justieren von Nullpunkt/Spanne vor Ort ist verboten. Es handelt sich um einen werkseitig kalibrierten analogen Isolationswandler.
- Genauigkeitsklasse & Kalibrierungsdifferenzierung
Typenschild mit der Aufschrift „Class“. 0.5: Maximal zulässiger Skalenendwert ±0,5 % FS unter Referenzbedingungen 25 °C.
✅ Metrologische Kalibrierung (Gestattet):
Verwenden Sie eine Standard-Gleichspannungsquelle + Hochpräzises Milliamperemeter für Mehrpunkt-Vergleichstests 0%, 25%, 50%, 75%, 100%. Kann für ein Kalibrierungszertifikat an ein Messlabor eines Drittanbieters gesendet werden, um zu überprüfen, ob die Leistung innerhalb der Klasse bleibt 0.5.
❌ Zuschnitt vor Ort (Nicht unterstützt):
Kein externer Nullpunkt / Überbrücken Sie das Zugangsloch im alten MCOMV-Gehäuse; PCB trim potentiometers are factory locked. Manufacturer does NOT recommend opening housing for on-site adjustment. Opening voids factory warranty and damages insulation isolation structure, degrading 2.5kV isolation safety rating.
- Calibration Test Procedure (Lab / Site Comparison, Test Only, No Adjustment)
DUT: MCOMV;48VDC (0~48VDC Input →4~20mA Output)
- Connect auxiliary power 20~60V DC, warm up ≥15 minutes
- Apply DC voltage sequentially via standard source: 0V, 12V, 24V, 36V, 48V
0V → Theoretical output 4.000 mA
48V → Theoretical output 20.000 mA
- Insert high precision milliammeter in series into current loop, record As-Found error for each point
- Pass Criterion: Error ≤ ±0.5%FS for all test points
Full scale span: 16mA corresponds to 48V; 1%FS = 0.16mA
- Remedial Actions If Drift Exceeds Tolerance
If calibration shows error out of Class 0.5 Toleranz:
- Replacement preferred (MCOMV discontinued). Recommended upgrade MCOVC1;48VDC, Stift & Dimensionskompatibel;
- Zur Neukalibrierung an das FRER-Werk zurücksenden (hohe Kosten & lange Vorlaufzeit);
- Inländische alternative Wandler: Ausgestattet mit externem Z/S-Potentiometer, Feld Null & Spanneneinstellung verfügbar.
- Kalibrierungsfunktion des neuen MCOVC (MCOMV-Ersatz)
Die MCOVC-Serie verfügt außerdem über kein externes Nullpunkt-/Spanne-Potentiometer, Nur werkseitig kalibriert, messtechnische Überprüfung zulässig, Kein Hardware-Beschnitt vor Ort.
- Empfohlenes Kalibrierungsintervall
Für DC-Panel, Telekommunikation -48V-Batterieüberwachung, Kraftwerksanwendungen, die eine rückverfolgbare Messtechnik erfordern: Jährliche Kalibrierung alle 12 Monate.
FRER MCOMV;48Vorsichtsmaßnahmen für die VDC-Genauigkeitskalibrierung
Kernzusammenfassung: Nur messtechnische Überprüfung zulässig (Genauigkeitsvalidierung). Kein externes Nullpunkt-/Span-Trimmpotentiometer. Das Öffnen des Gehäuses zum Justieren ist verboten; Klasse 0.5, Toleranz ±0,5 % vom Skalenendwert.
- Umgebungsbedingungen (Ungültige Kalibrierung, wenn nicht zufrieden)
- Umgebungstemperatur: Bevorzugen Sie eine konstante Temperatur von 25℃±2℃; record actual temperature if test off-nominal. Temperature drift ≤100ppm/℃ will introduce extra error.
- Luftfeuchtigkeit: 5%~95 % relative Luftfeuchtigkeit, Kondensation verboten. Condensation reduces isolation voltage, causes leakage error or permanent damage.
- EM Environment: Keep away from VFD, Schütze, high-power cables and strong magnetic field. Heavy interference leads to 4~20mA jitter and false failure judgement.
- Stabilisierung: Mount transducer on DIN rail, power on and warm up ≥15min until thermal stabilization before reading.
- Standard Instrument Requirements (Reference instrument accuracy better than DUT)
For Class 0.5 transducer, follow the 1/3 rule (instrument uncertainty ≤1/3 of DUT allowable error)
- Standard DC Voltage Source: Accuracy better than 0.15 Klasse, 0~48VDC output, low ripple
- Standard Milliammeter: DC current measurement accuracy better than 0.15 Klasse, connected in series in current circuit
- General multimeter cannot be primary standard (insufficient accuracy), only auxiliary reference
Instruments must be within valid calibration period with certificate to ensure metrology traceability.
III. Verdrahtung & Power Supply Notes
- Hilfsenergie: Stable 20~60V DC supply with low ripple. Avoid unstable switching power supply for temporary test. Fluctuating supply introduces output drift.
- Eingangsschaltung: Strict polarity for input +/-; limited reverse protection exists but long-time reverse energizing not recommended. Keep input wiring short; shielded cable with single-end grounding to reduce common-mode interference.
- Output Current Loop
Insert standard ammeter in series within 4~20mA loop
Total loop resistance shall not exceed 750Ω (ammeter internal resistance + cable resistance). Excessive load prevents reaching 20mA full scale and leads to false failure.
Tight wiring terminals; loose contact causes reading fluctuation.
- Erdung: Avoid multiple grounding for transducer, standard source and meters to prevent ground loop and common-mode voltage measurement error.
- Calibration Points & Betriebsrichtlinien
Recommended test points: 0V, 12V, 24V, 36V, 48V (0%, 25%, 50%, 75%, 100%FS)
- Upscale test: Ramp input from 0V up to full scale 48V, record output for each point
- Downscale test: Ramp down from 48V to 0V for return test and hysteresis error inspection
- Wait 3~5 seconds at each test point for reading stabilization before recording
- Do not continuously apply full 48V for long duration. Though 50% continuous overload is supported, long overvoltage accelerates aging. Transient 2× overload only for impulse test and not used for accuracy calibration.
- Error Calculation: FS =16mA full scale span. Error=(Measured Value − Theoretical Value)/FS ×100%. Criterion ±0.5%FS.
- Sicherheit & Geräteschutz
- Three-way Isolation: Eingang, output and power isolated at 2.5kV. Schließen Sie Ein- und Ausgang während des Tests NICHT kurz, Die Isolationsstruktur wird beschädigt.
- Gehäuseöffnung verboten: Internes PCB-Potentiometer werkseitig verriegelt. Beim Öffnen wird die Isolierung zerstört, führt zum Erlöschen der Garantie und beeinträchtigt die Isolationsbewertung mit Sicherheitsrisiko. Auch wenn beschnitten, Das FRER-Werk erkennt die Feldanpassung nicht, und das Metrologiezertifikat akzeptieren keine Hardwaremodifikationen vor Ort.
- Mäßiges Drehmoment an den Anschlussschrauben; Vermeiden Sie ein zu festes Anziehen, da sonst die Gewinde beschädigt werden und die Leiterplatte beschädigt wird.
- Datenaufzeichnung, Urteil & Anordnung
- Elemente aufzeichnen: Umgebungstemperatur & Luftfeuchtigkeit, Geräte-ID/Zertifikatsnummer, Hilfsversorgungsspannung, Vorwärts-/Rückwärtsablesungen aller Punkte und berechneter Fehler
- Pass Criterion: Alle vorwärts & Rückkehrtestpunktfehler ≤ ±0,5 % FS müssen qualifiziert sein; Hysteresefehler zusammen erfasst
- Handhabung außerhalb der Toleranz: Für dieses Gerät ist keine Vor-Ort-Korrektur möglich. Optionen: Durch MCOVC1 ersetzen;48VDC-kompatibles Modell oder senden Sie es zur Neukalibrierung an das Werk zurück. Verwenden Sie die Software-Offsetkompensation des SPS-AI-Kanals NICHT als Ersatz für die Wandlerkalibrierung (Dies ist nur eine vorübergehende technische Vergütung und wird nicht als Nachweis der messtechnischen Konformität akzeptiert).
VII. Häufige Fallstricke
❌ Verwenden Sie die in der SPS integrierte KI-Messung als Kalibrierungsreferenz: Das SPS-AI-Modul weist einen inhärenten Fehler auf und kann nicht als Messstandard dienen
❌ Lastwiderstand vernachlässigen: Gesamtwiderstand der Schleife > 750 Ω, Der volle Skalenwert kann 20 mA nicht erreichen und es kommt zu einem falschen Fehler
❌ Daten ohne Aufwärmen lesen: Komponenten thermisch instabil, Temperaturdriftfehler eingeführt
❌ Mehrfacherdung, Erdschleifenstörungen und Ausgangsschwankungen
❌ Gehäuse öffnen und internes Potentiometer einstellen: Von der Messtechnik nicht akzeptiert und die Isolierung ungültig gemacht
Markenübergreifende Modellvergleichstabelle für MCOMV;48VDC (FRER)
Original Spec: DIN-Schienenmontage, 0~48VDC input /4~20mA output, 3-Weg galvanische Trennung (Input/Output/Power), Klasse 0.5, Zu. Supply 20~60VAC/DC, Max Load 750Ω, No external zero/span adjustment
Auswahlpriorität: OEM Upgrade Import Equivalent Domestic Industrial Grade (Field Z/S adjustable, preferred for engineering replacement)
Brand Recommended Model Key Matching Points Differences Application Scenario
FRER (OEM) MCOVC1;48VDC Fully compatible;0~48VDC,4-20mA,3-Weg Isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;Stift & dimension match Still no external potentiometer, factory calibrated, no field trimming Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
Phoenix MACX MCR-VAC (Config: DC 0~48V,4-20mA) 3-Weg Isolation, Class0.5, DIN-Schiene, wide supply Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order PLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+Fuchs KFD2-VR4-EX1.20 (Custom input 0~48VDC) 3-Weg Isolation,4-20mA-Ausgang, high industrial noise immunity Standard model defaults to 0~10V, factory customized input range required;Class0.5;Higher price Explosion-proof area, Energiespeicher, telecom -48V monitoring
Acrel BM-DV/I, 0~48VDC input,4-20mA output 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer Domestic brand, Feld Null & span adjustable;Kostenvorteil;2.5kV isolation same as FRER Telecom -48V battery,DC panel,batch replacement,field calibration required
Suzhou Xunpeng WP-V,0~48VDC,4-20mA 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer Domestic, kostengünstig, metrology certifiable,short procurement lead time Factory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC) 1in1out voltage isolation transducer,3-Weg Isolation,4~20mA output,Class0.5 Programmable range,externally adjustable;Strong EMC 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional DCS cabinet,multi-signal centralized acquisition
| Marke | Empfohlenes Modell | Wichtige Matching-Punkte | Unterschiede | Anwendungsszenario |
| FRER (OEM) | MCOVC1;48VDC | Vollständig kompatibel;0~48VDC,4-20mA,3-Weg Isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;Stift & dimension match | Still no external potentiometer, factory calibrated, no field trimming | Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification |
| Phönix | MACX MCR-VAC (Config: DC 0~48V,4-20mA) | 3-Weg Isolation, Class0.5, DIN-Schiene, wide supply | Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order | PLC/DCS cabinet, high EMC environment, power station DC panel |
| Pepperl+Fuchs | KFD2-VR4-EX1.20 (Custom input 0~48VDC) | 3-Weg Isolation,4-20mA-Ausgang, high industrial noise immunity | Standard model defaults to 0~10V, factory customized input range required;Class0.5;Höherer Preis | Explosionsgeschützter Bereich, Energiespeicher, telecom -48V monitoring |
| Acrel | BM-DV/I, 0~48VDC input,4-20mA-Ausgang | 3-Weg Isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer | Inländische Marke, Feld Null & span adjustable;Kostenvorteil;2.5kV isolation same as FRER | Telecom -48V battery,DC panel,batch replacement,field calibration required |
| Suzhou Xunpeng | WP-V,0~48VDC,4-20mA | 3-Weg Isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer | Inländisch, kostengünstig, metrology certifiable,short procurement lead time | Factory technical renovation,bulk transducer replacement |
| CZ3076 (Custom range 0~48VDC) | 1in1out voltage isolation transducer,3-Weg Isolation,4~20mA output,Class0.5 | Programmable range,externally adjustable;Strong EMC | 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional | DCS cabinet,multi-signal centralized acquisition |
Selection Priority Description
- Minimum modification replacement (no terminal rewiring recommended)
FRER MCOVC1;48VDC, direct plug-in replacement for MCOMV;48VDC, identical housing width, terminal assignment and electrical parameters; Einschränkung: still no field zero/span trimming, Nur messtechnische Überprüfung im Labor.
- Bevorzugt für die Feldwartung (Acrel BM-DV/I empfohlen)
Passende Spezifikationen, eingebautes Nullpunkt-/Span-Potentiometer, Kalibrierung vor Ort möglich, wenn außerhalb der Toleranz, Lösung der MCOMV-Einschränkung, dass keine Feldanpassung erforderlich ist; 2.5kV-Isolierung trifft auf DC-Panel & Anforderungen an die Telekommunikations-Strommesstechnik.
- Importierte Premium-Anwendung mit hoher EMV
M-SYSTEM, Phoenix MACX-Serie mit überlegener EMV-Leistung, aber unterschiedliches Klemmenlayout und Modulbreite, Neuverkabelung der Schrankklemmen erforderlich, lässt sich nicht einstecken & spielen.
Zusammenfassung der wichtigsten Unterschiede (Zum Vergleich der technischen Spezifikationen)
- Kalibrierungsfähigkeit
FRER MCOMV / MCOVC: Kein externes Z/S, Nur messtechnische Überprüfung, Keine Hardwareanpassung vor Ort
Acrel/Xunpeng/CZ: Externer Nullpunkt & Span-Potentiometer, Feldkalibrierung verfügbar
Phoenix/M-SYSTEM: Kalibrierung der Softwarekonfiguration
- Stromversorgung
FRER: 20~60V AC/DC wide range; Am meisten importiert & Inländische Standardmodelle verwenden standardmäßig 24 VDC, wide voltage version must be specified at order.
- Modulbreite
FRER original unit: 22.5mm; Phönix & CZ slim type:12.5mm, less DIN rail slot consumption.
Mandatory Order Remarks (Prevent Wrong Range Shipment)
Must specify below items on PO for all replacement models:
DC Voltage Input:0~48VDC; Ausgabe:4~20mA; 3-Weg galvanische Trennung; DIN-Schienenmontage; Genauigkeitsklasse 0.5; Hilfsenergie:20~60VAC/DC