AJ65SBTB1-32D is a Mitsubishi MELSEC CC-Link compact remote DC digital input module
- Modellcode-Definition
AJ65: CC-Link remote I/O module series
SBTB1: Compact remote I/O main body
32: 32 I/O-Punkte
D: Digitaler Eingang (DC input)
- Wichtige Spezifikationen
| Artikel | Parameter |
| Network | CC-Link Ver.1/2 |
| Typ | Remote DC digital input module |
| Punkte | 32 input points |
| Occupied stations | 1 Station |
| Nenneingangsspannung | DC24V |
| Eingangsstrom | Ca. 7mA pro Punkt |
| Input response time | 1.5MS (OFF→ON / ON→OFF) |
| Input polarity | Sink/Source compatible (works with both NPN and PNP sensors) |
| Isolierung | Optocoupler isolation |
| Stromversorgung des Moduls | DC24V; Module power consumption approx. 45mA |
| ON threshold | ≥14VDC / ≥3.5mA |
| OFF threshold | ≤6VDC / ≤1.7mA |
| Gesamtabmessungen | W179 × H50 × D40 mm |
| Gewicht | 0.25 kg |
| Terminals | M3-Schraubklemmenblock |
| Schutzklasse | IP2X |
- Anwendungsszenarien
Remote sensor signal acquisition for production lines: fotoelektrische Sensoren, Näherungsschalter, Magnetschalter, pushbutton signals
Distributed I/O architecture to reduce bulk hardwiring from control cabinets to field devices via CC-Link bus networking
Compatible with Mitsubishi Q-series, FX3U/FX5U PLCs equipped with CC-Link master station
- Modellunterscheidung (Frequently Confused Models)
- AJ65SBTB1-32D: Standardversion, 1.5MS-Antwort, 32AUS
- AJ65SBTB1-32D1: High-Speed-Version, 0.2MS-Antwort, 32AUS, preferred for high-frequency sensors
- AJ65SBTB1-32T: 32-point transistor output module
- AJ65SBTB1-32DT: 16-input +16-output mixed I/O module
Lifecycle note: AJ65SBTB1-32D is discontinued. Only stock or used units available. Für neue Projekte, AJ65SBTB1-32D1 is the preferred replacement. Same mounting dimensions and terminal definitions; only faster response speed, keine Programmänderung erforderlich.
- Installation & Verkabelungsrichtlinien
- Stromversorgung: Independent DC24V supply for module itself; sensors also use DC24V signal
- CC-Link bus: DA/DB cables; 110Ω terminating resistors fitted at both ends of the bus
- Common terminals: 8 points per common group, supports NPN/PNP. Keep unified polarity during wiring
- Erdung: Reliable earthing on FG terminal to reduce bus interference
- Station number setting: DIP switches on module body to set CC-Link station number
- Häufige Fehlerbehebung
- RUN indicator off: Check DC24V supply, polarity and internal fuse
- ERR indicator flashing: CC-Link communication failure. Inspect DA/DB wiring, terminating resistors, duplicate station numbers, shield earthing
- No signal at input channel: Verify sensor power supply and common polarity; measure terminal voltage with multimeter; check for damaged optocoupler channel
- False signal triggering: Cable interference, use shielded cable; check response time. Für lange Kabel, select D1 high-speed variant
- Alternative Selection List
- Direkter Drop-In-Ersatz (gleiche Größe & Terminals): AJ65SBTB1-32D1 (Empfohlen für neue Projekte)
- Domestic compatible CC-Link 32DI remote I/O: Innovation, Inwell CC-Link remote input modules (verify CC-Link version and register mapping)
- Upgrade to CC-Link IE Field bus: NZ-series remote I/O (hardware architecture completely different; PLC program rewrite required)
- HS-Code-Referenz
8537101100 (Programmable controller digital input module, Nur zur Zollanmeldung; subject to customs final judgement)
CC-Link Master Station Parameter Configuration (for AJ65SBTB1-32D, Remote I/O Station, besetzt 1 Station)
Master module: QJ61BT11N (Q-series); Programmiersoftware: GX Works2; AJ65SBTB1-32D = Remote I/O Station, besetzt 1 Station, 32-point RX input, no RY output and no RW registers.
Master station fixed station number: Station 0. Slave AJ65SBTB1-32D station number set via DIP switch: 1~64. Station 1 is used in this example.
- Hardware DIP Switch (Set AJ65SBTB1-32D first!)
- Station number DIP switch: Binary DIP switch for station address (z.B. Station 1 = 00000001)
- Baud rate DIP switch: Must match master station baud rate
000 → 156kbps
001 → 625kbps
010 → 2.5Mbps (most commonly used on site)
011 → 5Mbps
100 →10Mbps
Fit 110Ω terminating resistors at both ends of the bus
- GX Works2 Q-series CC-Link Master Basic Parameters
Weg: Project Navigator → Parameters → Network Parameters → CC-Link
| Artikel | Setting Value | Bemerkungen |
| Modulmodell | QJ61BT11N | Master station module |
| Start I/O Address | 0000 (modify according to actual slot) | Module I/O address |
| Master Station No. | 0 | CC-Link master fixed at station 0 |
| Modus | Remote Net(Ver.1 Mode) | AJ65SBTB1-32D is Ver.1 compatible remote I/O |
| Total Connected Stations | 1 | For single AJ65SBTB1-32D network; update for multiple slaves |
| Kommunikationsgeschwindigkeit | 2.5Mbit/s | Must match slave DIP baud rate |
| Anzahl der Wiederholungen | 3 | Standard |
| Standby Master | Keiner | Standard single-master system |
| Scan Mode | Asynchron | Standard |
Station Information (Kritisch!)
Klicken [Station Information], add Station No.1:
| Artikel | Einstellung | |
| Station Nr. | 1 | DIP station number of AJ65SBTB1-32D |
| Station Type | Remote I/O Station | ⚠️ NOT Remote Device Station! |
| Occupied Stations | 1 | AJ65SBTB1-32D fixed as 1 Station |
| RX(Remote Input) | 32 Punkte | X0~X1F (corresponds to 32DI) |
| RY(Remote Output) | 0 Punkte | This module has inputs only, no outputs |
| RWw/RWr | 0 Worte | Remote I/O stations do not use registers |
Remote I/O station soft element mapping rule:
Station1: RX0~RX1F correspond to the 32 DI channels of AJ65SBTB1-32D
PLC internal soft elements for master station: RX mapped to PLC X addresses (auto-refreshed by GX Works)
- Soft Element Refresh Mapping (QJ61BT11N)
CC-Link automatic refresh:
RX: Remote input → PLC internal X
RY: PLC output → Remote module output
RWw: PLC writes to remote registers
RWr: Remote registers read into PLC
AJ65SBTB1-32D (Station 1)
RX0~RX1F (32bisschen) = 32 DC input channels of the module
Beispiel: Sensor ON → RXn=ON; read RX bit directly in program.
- FX5U + FX5-CCL-MS (FX5U CC-Link Master, GX Works2/3)
FX5U with FX5-CCL-MS master card can connect AJ65SBTB1-32D
- Project → Parameters → CC-Link Parameters, Master type: Master station, Ver.1 mode
- Add station entry for Station 1: Remote I/O Station, besetzt 1 Station, RX=32, RY=0
- Soft element refresh: RX mapped to FX5U X or M (customizable refresh address)
FX5U built-in Ethernet CC-Link IE Field Basic cannot directly connect old AJ65SBTB1-32D. This classic CC-Link uses RS485 bus and requires FX5-CCL-MS module.
- Herunterladen & Inbetriebnahmeschritte
- Complete all parameter settings, klicken [Überprüfen], confirm no errors;
- Schreiben [Parameter + Programm] to PLC; PLC reset;
- Power up remote modules with DC24V first, then power up PLC master station;
- Indikatoren beachten:
M/S: Master steady ON; LAUFEN: Slave steady ON;
ERR off = Communication normal; ERR flashing = bus fault;
- Online monitor RX soft elements; trigger sensors and verify corresponding RX bits turn ON/OFF.
- Häufige Fehler
- ❌ Wrong station type: selected as Remote Device Station → communication failure; must use Remote I/O Station
- ❌ Baud rate mismatch between master and slave
- ❌ Missing terminating resistors, random disconnection over long cables
- ❌ Duplicate station numbers, frequent in multi-slave networks
- ❌ Ver.2 mode enabled; old AJ65SBTB1-32D is Ver.1 compatible, use Remote Net Ver.1 Mode by priority
- Sample Program (ST / Ladder compatible)
Directly monitor RX0~RX1F, no special communication instruction required, CC-Link auto cyclic refresh.
Beispiel: LD RX0 reads channel 0 input of AJ65SBTB1-32D.
Optional extensions available upon request:
- Screenshot-style GX Works2 CC-Link parameter setup guide
- Batch parameters for multiple AJ65SBTB1-32D network (Station1, Station2, Station3…)
- Communication fault code (ERR lamp) reference table
- Ladder example to map RX to internal M relays for easier programming
CC-Link ERR Lamp + QJ61BT11N Fault Code Reference Table (For AJ65SBTB1-32D)
Two sections: Quick LED Indicator Diagnosis (On-site check) + Hex Fault Codes read from GX Works Diagnosis (Precise troubleshooting)
Master: QJ61BT11N; Sklave: AJ65SBTB1-32D
- LED Status Quick Reference (Master QJ61BT11N ERR Lamp)
| Master ERR Lamp | Fehlerbeschreibung | Fehlerbehebung |
| AUS | Communication normal | – |
| Ständig AN | All stations communication failure | Buspanne, DA/DB reversed, dual master conflict, Parameterfehler, baud mismatch, Abschlusswiderstand fehlt |
| Blinkt | Partial slave fault, faulty station exists | Single/multiple slave offline, duplicate station number, slave power off, slave hardware damage |
Slave AJ65SBTB1-32D L.ERR Indicator
| Slave L.ERR Lamp | Fehlerbeschreibung | Fehlerbehebung |
| AUS | Communication normal | – |
| Ständig AN | Slave communication error | Station number out of range, bus broken, power supply abnormal |
| Regular periodic flashing | DIP switch modified under power (station/baud) | Ausschalten, reset DIP switch, repower |
| Irregular random flashing | Noise interference / faulty terminating resistor | 110惟 resistors at both bus ends, shield earthing, Kabelschaden, parallel power cable interference |
PW lamp OFF: No DC24V supply to slave, check power terminals and fuse first.
L.RUN lamp OFF: Data link not established; master cannot detect this slave station.
- QJ61BT11N Master Hex Fault Codes (Read via GX Works CC-Link Diagnosis)
| Fehlercode(HEX) | Fehlername | Ursache | Action |
| B823 | Remote control mode error | Incorrect master mode setting | Set network parameter to Remote Net(Ver.1 Mode). AJ65SBTB1-32D does not support Ver.2 extended mode |
| B983 / B984 | Invalid module type | Mode incompatibility between master and slave | Old AJ65SBTB1-32D is Ver.1 remote I/O; disable Ver.2 mode |
| BA1B | All stations failure | Whole bus communication interruption | DA/DB wiring, 110惟 terminators, Baudrate, cable breakage |
| BBC2 | Station number setting error | Station number out of range or wrong station type | Station type must be [Remote I/O Station], not Remote Device Station; station range 1~64 |
| BBC5 | Duplicate master station (multi-master conflict) | 2 masters on the same CC-Link bus | Check bus and keep only one master module |
| BD85 | Master hardware failure | QJ61BT11N module damage | Power cycle, replace master module if fault persists |
| BFFE | CPU watchdog timeout | Communication error between PLC CPU and master module | Check QCPU backplane, module installation, PLC reset |
| C92E | Nichtübereinstimmung der Baudrate | Master baud differs from slave DIP setting | Set master baud equal to AJ65SBTB1-32D DIP baud |
| C932 | Duplicate station number conflict | Two slaves with identical station DIP setting | Check each module DIP and assign unique station number |
| C940 | Data link stop | Bus break / interference / missing terminator | Check DA DB wiring, shield earthing, terminating resistors |
- Q-series CC-Link Special Relay SW (Monitor in GX Works)
Identify offline station quickly via SW registers
- SW0080~SW0083: Link error bits, bit maps to station number. ON = fault at that station
SW0080 bit0 = Station1 fault; bit1 = Station2 fault, and so on
- SW006B: Detailed error type
0: Normal
1: Transmission line fault
2: Parameterfehler
3: CRC error (elektromagnetische Störungen)
4: Timeout error (slave no response)
5: Abort error
6: Setting error
- Reihenfolge der Fehlerbehebung vor Ort (AJ65SBTB1-32D)
- Check slave PW lamp: OFF → inspect DC24V supply
- Check slave L.RUN / L.ERR lamp
- Open GX Works → CC-Link Diagnosis, read fault code + SW0080 to locate faulty station
- Verifizieren: Stationsnummer, Baudrate, station type (Remote I/O Station)
- Check DA/DB polarity, 110Ω terminators at both bus ends
- Single-point earthing for shield; avoid both-end earthing to prevent ground loop
- Separate CC-Link cable away from power cables to reduce interference
- Common Pitfall Summary
- Remote I/O Station mistakenly selected as Remote Device Station → BBC2 station type error, ERR flashing
- Master Ver.2 mode enabled, old AJ65SBTB1-32D incompatible → B983 invalid module type
- Terminating resistor fitted only on one end → random flashing, intermittent disconnection
- DA DB wires reversed, entire bus down, master ERR steady ON
- Modify DIP switches while powered on, slave L.ERR flashes periodically; power cycle to recover
Mitsubishi AJ65SBTB1 Series (CC-Link Compact Remote I/O, Screw Terminal Block, all discontinued, 1 station occupancy)
Suffix definition
D: DC-Digitaleingang; D1: High-speed Input; D5: 5V Input
T: Sink transistor output; T1: High-speed transistor output; TE1: Source transistor output
DT: Mixed Input+Output; K: Special common terminal specification
All modules in this series are Remote I/O Stations (not Remote Device Stations), CC-Link Ver.1 compatible
- Pure DC Input Modules (AUS)
| Modell | Punkte | Brief Specification |
| AJ65SBTB1-8D | 8AUS | DC24V, standard response 1.5ms, NPN/PNP common terminal |
| AJ65SBTB1-16D | 16AUS | DC24V, standard response 1.5ms |
| AJ65SBTB1-16D1 | 16AUS | DC24V, high-speed 0.2ms |
| AJ65SBTB1-32D | 32AUS | DC24V, standard response 1.5ms (your target model) |
| AJ65SBTB1-32D1 | 32AUS | DC24V, high-speed 0.2ms, direct compatible replacement for 32D |
| AJ65SBTB1-32D5 | 32AUS | DC5V input, special signal acquisition for legacy projects |
| AJ65SBTB1-32KD | 32AUS | DC24V, special common terminal layout |
- Pure Transistor Output Modules (TUN)
| Modell | Punkte | Brief Specification |
| AJ65SBTB1-8T | 8TUN | DC24V sink transistor, 0.5Ein pro Punkt |
| AJ65SBTB1-8T1 | 8TUN | High-speed sink transistor output |
| AJ65SBTB1-8TE | 8TUN | Source transistor output |
| AJ65SBTB1-16T | 16TUN | DC24V sink transistor |
| AJ65SBTB1-16T1 | 16TUN | High-speed sink transistor output |
| AJ65SBTB1-32T | 32TUN | DC24V sink transistor output |
| AJ65SBTB1-32T1 | 32TUN | High-speed sink transistor output |
| AJ65SBTB1-32TE1 | 32TUN | Source transistor output |
- Mixed I/O Modules (DI+DO)
| Modell | E/A-Konfiguration | Brief Specification |
| AJ65SBTB1-16DT | 8D+8C | DC24V-Eingang + sink transistor output |
| AJ65SBTB1-16DT1 | 8D+8C | High-Speed-Version |
| AJ65SBTB1-16DT2 | 8D+8C | Positive common version |
| AJ65SBTB1-16DT3 | 8D+8C | Negative common version |
| AJ65SBTB1-32DT | 16D+16C | 16-in 16-out, Standardmodell |
| AJ65SBTB1-32DT2 | 16D+16C | Revised common terminal spec |
| AJ65SBTB1-32DT3 | 16D+16C | Improved revision |
| AJ65SBTB1-32DTE1 | 16D+16C | Source transistor output |
| AJ65SBTB1-32KDT2 | 16D+16C | Special common terminal |
| AJ65SBTB1-32KDT8 | 16D+16C | 12V I/O, special legacy project |
Distinguish other family series (AJ65SBTB2 / AJ65SBTB32 / AJ65SBTC connector type, NOT SBTB1 series)
Frequently confused during procurement, not part of SBTB1 series, reference only
- AJ65SBTB2: Relay output R, analog A modules
AJ65SBTB2-8R, AJ65SBTB2-16R (Relaisausgang); AJ65SBTB2-8A, 16A analog
- AJ65SBTB32: Compact small terminal block
AJ65SBTB32-8DT / 8DT2, AJ65SBTB32-16DT / 16DT2, AJ65SBTB32-16DR (mixed relay)
- AJ65SBTC: Quick connector type (not screw terminals)
AJ65SBTC1-32D, AJ65SBTC1-32T, AJ65SBTC1-32DT, field plug wiring, different form factor from SBTB1
Auswahlnotizen
- All AJ65SBTB1 series are discontinued. Not available for new project purchase, nur Lagerbestand / used units.
- Same mounting dimensions: same point count D/D1, T/T1, DT/DT modules support direct drop-in replacement with no program modification.
- Station type: Must select [Remote I/O Station] in GX Works parameter; behoben 1 occupied station.
- Analog modules are not in SBTB1 series: models AJ65SBT-64AD, AJ65SBT2B-64AD etc.
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter




















NH42-63-318x560.png)



