Phoenix QUINT-DIODE40 Redundancy Module

QUINT-DIODE/40 (2938963) is a 24VDC diode redundancy module manufactured by Phoenix Contact. It is designed for parallel redundancy of two 20A power supplies or capacity expansion for a single 40A circuit. This model is discontinued. The official replacement is QUINT4-DIODE/12-24DC/2X20/1X40 (2907719). It features reverse polarity protection, low voltage drop (0.5V) and efficiency over 97%, ideal ...

  • Produktdetails

QUINT-DIODE/40 (2938963) is a 24VDC diode redundancy module manufactured by Phoenix Contact. It is designed for parallel redundancy of two 20A power supplies or capacity expansion for a single 40A circuit. This model is discontinued. The official replacement is QUINT4-DIODE/12-24DC/2X20/1X40 (2907719). It features reverse polarity protection, low voltage drop (0.5V) and efficiency over 97%, ideal for critical systems such as industrial automation and process control.

  1. Erklärung des Modellcodes
ModellsegmentBeschreibung
QUINTProduct line identifier for Phoenix QUINT POWER power supplies
DIODEDiode-type redundancy module (passive redundancy, no active current sharing)
40Maximum output current: 40A (supports 2×20A redundant input)
Bestell-Nr.2938963 (Unique factory part number)
Upgrade-ErsatzQUINT4-DIODE/12-24DC/2X20/1X40 (Bestell-Nr.: 2907719)
  1. Grundlegende technische Spezifikationen
KategorieSpezifikationen
Elektrische Eigenschaften
Eingangsspannung24VDC (Reichweite: 0~30VDC)
Nenneingangsstrom2×20A (Redundancy Mode) / 1×40A (Capacity Expansion Mode)
Max. Ausgangsstrom40A (bei 40°C, with 6mm² cable)
Voltage Drop0.5V (Input to Output)
Effizienz>97%
Reverse Polarity ProtectionJa (<60V)
Transient Surge ProtectionTransil Diode
Mechanische Eigenschaften
MontageartDIN-Schienenmontage (NS 35, konform mit EN 60715)
Abmessungen (B × H × T)62mm × 84mm × 102mm
GehäusematerialMetall (AlMg enclosure, GD-ZnAlCu cooling unit)
Gewicht600G (without packaging), 683G (with packaging)
Umwelteigenschaften
Betriebstemperatur-25°C ~ 70 °C (Derating required above 60°C)
Lagertemperatur-40°C ~ 85°C
Schutz vor EindringenIP20 (For installation inside enclosed control cabinets only)
SchutzklasseKlasse II (Double insulation)
Zertifizierungen & Zuverlässigkeit
MTBF (@40°C)28,571,428 Std. (ca. 3260 Jahre)
Marine CertificationsDNV GL (EMC A), ABS
UL-ZertifizierungUL/C-UL Listed (UL 508, UL 1604 Klasse I, Division 2)
ATEX CertificationII 3G Ex nA IIC T4 Gc
HS-Code85049090
  1. Cross-Brand & Old/New Model Replacement List

3.1 Original Manufacturer Replacements

Altes ModellStatusErsatzmodellBestell-Nr.Major Improvements
QUINT-DIODE/40AuslaufmodellQUINT4-DIODE/12-24DC/2X20/1X402907719Extended operating temperature: -40°C~60°C; 12-24VDC wide voltage range; optimized heat dissipation
QUINT-DIODE/12-24DC/2X20/1X40AktivQUINT4-DIODE/12-24DC/2X20/1X402907719In-series upgrade with enhanced performance
QUINT-DIODE/48DC/2X20/1X40AktivQUINT4-DIODE/48DC/2X20/1X402907720Upgrade for 48VDC version

3.2 Cross-Brand Compatible Replacements

MarkeModellNennstromSpannungsbereichMerkmale
WeidmüllerUR 24DC/2×20/1×4040A24VDCDiode redundancy, DIN rail mount
WAGO289-60240A24VDCKompaktes Design, geringer Stromverbrauch
WürthWE-DD-4040A24VDCHohe Zuverlässigkeit, industrial certifications
R. STAHLSerie 857940A24VDCExplosion-proof certified for hazardous areas
  1. Full Product Line List

4.1 QUINT-DIODE Series (Classic Models)

ModellBestell-Nr.NennspannungAktuelle BewertungMerkmale
QUINT-DIODE/40293896324VDC2×20A / 1×40AGrundmodell, eingestellt
QUINT-DIODE/12-24DC/2X20/1X40232015712-24VDC2×20A / 1×40AGroßer Spannungsbereich, commonly used
QUINT-DIODE/48DC/2X20/1X40232016048VDC2×20A / 1×40ADedicated for 48VDC systems
QUINT-DIODE/48DC/40286658548VDC40AProtective coating, geeignet für raue Umgebungen

4.2 QUINT4-DIODE Series (Verbesserte Modelle)

ModellBestell-Nr.NennspannungAktuelle BewertungMerkmale
QUINT4-DIODE/12-24DC/2X20/1X40290771912-24VDC2×20A / 1×40ABreites Temperaturdesign: -40°C~60°C
QUINT4-DIODE/48DC/2X20/1X40290772048VDC2×20A / 1×40AUpgrade for 48VDC systems

4.3 QUINT-ORING Series (Active Redundancy with ACB Current Sharing)

ModellBestell-Nr.NennspannungAktuelle BewertungMerkmale
QUINT-ORING/24DC/2X20/1X40232018624VDC2×20A / 1×40AActive current sharing, extended power supply service life
QUINT4-S-ORING/12-24DC/1X40290775212-24VDC40AIntelligent monitoring, compatible with QUINT4 power supplies
  1. Anwendungsumgebungen & Branchenfälle

5.1 Anwendbar & Non-Recommended Scenarios

Anwendbare SzenarienNon-Recommended Scenarios
Industrial automation control systems (SPS, DCS)Long-term high-load systems requiring active current sharing (ORING series recommended)
Prozesskontrollausrüstung (Petrochemie, Water treatment)Unstable power supplies with voltage fluctuation over ±25%
Infrastruktur (Kommunikationsbasisstationen, Rechenzentren)Explosionsgefährdete Bereiche (Select EX-certified models)
Marine & Offshore-Technik (Marine certifications available)Unprotected outdoor installation (IP20 rating only)
Medizinische Geräte (Compliant with SELV/PELV requirements)Ambient temperature above 70°C (Derate load or use high-temperature models)

5.2 Typische Anwendungsfälle

  1. Automobile Production Lines

Anwendung: Two QUINT-PS/1AC/24DC/20 power supplies connected in parallel with QUINT-DIODE/40 for redundancy.

Wert: Ensure continuous operation of welding robots and PLC systems, and reduce production downtime losses.

  1. Petrochemical Process Control

Anwendung: Redundant power configuration for Safety Instrumented Systems (SIS).

Wert: Konform mit IEC 61508, provides SIL 2 safety level and prevents safety accidents caused by power failure.

  1. Smart Grid Monitoring Systems

Anwendung: Dual power redundancy for Remote Terminal Units (RTU).

Wert: Maintain communication and data acquisition under extreme weather conditions to guarantee stable grid operation.

  1. Fehlerbehebung & Maintenance Manual

6.1 Häufige Fehler, Ursachen & Lösungen

FehlerphänomenMögliche UrsachenLösungen
Abnormally low output voltage1. Excessive forward voltage drop of internal diodes1. Verify input voltage within 0~30VDC
2. Insufficient input voltage2. Check and retighten terminals
3. Loose terminal connections3. Test internal diodes with multimeter diode mode
Severe overheating1. Overloaded current1. Ensure load current does not exceed 40A (derate per cable specification)
2. Schlechte Wärmeableitung2. Reserve sufficient clearance for heat dissipation (50mm top & bottom)
3. Zu hohe Umgebungstemperatur3. Lower ambient temperature or add ventilation
Failed parallel operation of power supplies1. Reverse wiring polarity1. Recheck wiring polarity
2. Excessive voltage difference between two inputs2. Keep voltage difference between two power supplies within 1V
3. Open-circuit internal diode3. Replace the faulty module
Malfunction of reverse current protection1. Damaged reverse polarity protection diode1. Limit input voltage below 30VDC
2. Input voltage over 60V2. Replace internal protection diode
3. Install external surge suppressor

6.2 On-site Quick Diagnosis Procedure

  1. Visuelle Inspektion

Check housing for burn marks, deformation or discoloration.

Inspect terminals for looseness, oxidation and corrosion.

Remove dust accumulated on heat sinks which impairs heat dissipation.

  1. Elektrische Prüfung

Measure input voltage to confirm it is within 0~30VDC.

Measure output voltage (normally input voltage minus 0.5V).

Test diode forward/reverse resistance: normal state is forward conduction and reverse cut-off.

  1. Function Verification

Disconnect one power supply and confirm the other works normally.

Restore dual power input and check uniform load distribution.

Measure temperature rise: shall not exceed ambient temperature +30°C.

  1. Auswahlrichtlinien & Kurzreferenzregeln
  2. Drei wichtige Auswahlfaktoren: Spannungsklasse (24/48VDC), Current demand (≤40A), Redundancy mode (2×20A or 1×40A)
  3. Ersetzungsregel: QUINT-DIODE/40 is replaced by QUINT4-DIODE/12-24DC/2X20/1X40 (2907719), fully backward compatible.
  4. Current Derating Rules:

6mm² Kabel: 39A @ 40°C, 32A @ 60°C

10mm² Kabel: 54A @ 40°C, 43A @ 60°C

16mm² Kabel: 60A @ 40°C, 48A @ 60°C

  1. Installationsanforderungen: Horizontal or vertical DIN rail mounting; reserve 50mm clearance top and bottom for heat dissipation, 5mm clearance on left and right sides.