Schneider GVAE11 Hilfskontaktblock

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • Produktdetails

GVAE11 is a 1NO + 1NC instantaneous Hilfskontaktblock of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

CodesegmentBedeutungBeschreibung
GVAProduktkategorieAuxiliary contact block for GV series
EMontagepositionFront mounting, different from side-mounted models
11Kontaktkonfiguration1 Normalerweise geöffnet (NEIN) + 1 Normalerweise geschlossen (NC) instantaneous contacts with mechanical linkage

Vollständige Modelldefinition: GVAE11 = Schneider GV series, front-mounted, 1NO+1NC instantaneous auxiliary contact block

  1. Grundlegende technische Spezifikationen
KategorieSpezifikationenBemerkungen
General Characteristics
ProdukttypInstantaneous auxiliary contact blockMechanically linked, operates synchronously with main contacts of circuit breaker
Kontaktkonfiguration1NEIN + 1NC (Sofort)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, GV2ME, GV2P, GV2RT, GV3L, GV3P and other models
MontagemethodeFront snap-on installationTool-free assembly & quick removal with precise positioning
Elektrische Parameter
Nennbetriebsspannung24–240 V Wechselstrom, 24–60V DCSuitable for standard voltages of control circuits
Nennbetriebsstrom2.5A (Ith)Continuous current carrying capacity
Bemessungsisolationsspannung690V undComplies with insulation requirements for industrial control circuits
Mechanische Ausdauer100,000 BetriebszyklenHigh reliability for frequent operations
Elektrische Ausdauer100,000 Betriebszyklen (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
TerminaltypSchraubklemmenCopper wire cross-section: 0.5–1.5mm²; Anzugsdrehmoment: 0.8–1.2Nm
Körperlich & Umgebungsparameter
SchutzgradIP20Verhindert den Zugriff von Fingern auf spannungsführende Teile
Abmessungen (B × H × T)45 × 20 × 15mmKompakte Struktur, no extra installation space required for circuit breakers
Betriebstemperatur-25℃ ~ +60℃Großer Temperaturbereich für Industrieumgebungen
FarbeGrauMatches the appearance of GV series circuit breakers
ZertifizierungenCCC, UL, CSA, EACMulti-standard certifications for global application
Bestellinformationen
Manufacturer Part No.GVAE11Official Schneider model
Standard-BestellcodeGVAE11Original imported version
EAN-Code3.38911E+12International universal commodity code
  1. Vollständige Modellliste (GVAE Series Auxiliary Contacts)
ModellKontaktkonfigurationMontagepositionCompatible DevicesHauptanwendung
GVAE11NO or 1NC (Optional)FrontGV2/GV3 SeriesSimple status indication, single signal output
GVAE111NEIN + 1NCFrontGV2/GV3 SeriesStandard status monitoring, output open/close signals simultaneously
GVAE202NEINFrontGV2/GV3 SeriesControl circuits requiring multiple NO signals
GVAE022NCFrontGV2/GV3 SeriesControl circuits requiring multiple NC signals
GVAE141NEIN + 1NCSideGV2/GV3 SeriesSide mounting for space-limited installations
GVAE242NEINSideGV2/GV3 SeriesSide mounting for multiple NO signal demands
GVAE042NCSideGV2/GV3 SeriesSide mounting for multiple NC signal demands
  1. Ersatzmodelle & Konkurrenzvergleich

4.1 Internal Schneider Replacements

OriginalmodellErsatzmodellUnterschiedeAnwendungsszenarien
GVAE11GVAE14Different mounting position (side mounting)Insufficient front space, side mounting required
GVAE11GV2ME + Integrierte KontakteIntegriertes Design, no extra assembly neededNew equipment selection for integrated layout
GVAE11GV3P + Integrierte KontakteUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Markenübergreifender Wettbewerbervergleich

MarkeModellKontaktkonfigurationCompatible DevicesHauptunterschiede
SchneiderGVAE111NEIN + 1NCGV2/GV3 SeriesPrecise mechanical linkage, Schutzart IP20, high compatibility
ABBMS132-011NEIN + 1NCMS132 SeriesSide mounting, rated current 3A, ähnlicher Preis
Siemens3RV2091-1A1NEIN + 1NC3RV20 SeriesSteckmontage, rated current 2A, complete certifications
EatonPKZM0-AUX111NEIN + 1NCPKZM0 SeriesFront mounting, rated current 2.5A, spring terminals
ChintNXC-A111NEIN + 1NCNXC-SerieKostengünstig, reliable domestic alternative
  1. Anwendungsumgebungen & Typische Fälle

5.1 Empfohlene Anwendungen

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Interlock Control: Prevent simultaneous startup of multiple motors and realize sequence control

Fernüberwachung: Transmit status signals to SCADA system for remote diagnosis

Safety Circuit: Form safety protection circuits together with emergency stop buttons

5.2 Nicht empfohlene Anwendungen

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: Über 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: IP20 protection is insufficient; install extra enclosure or select higher protection grade products

5.3 Typische Anwendungsfälle

Fall 1: Pump Unit Control in Wastewater Treatment Plant

Ausrüstung: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

Konfiguration: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

Ergebnis: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

Fall 2: Conveyor System in Automotive Production Line

Ausrüstung: 12 conveyor lines, each equipped with GV2P32 + GVAE11

Konfiguration: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

Merkmale: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. Fehlerbehebung & Maintenance Manual

6.1 Häufige Fehler & Lösungen

FehlerphänomenMögliche UrsachenLösungen
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. Falsche Verkabelung4. Check wiring and confirm correct connection of NO/NC contacts
Kontaktschweißen1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Arc erosion3. Replace with a new contact block
Signal interference1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. Schlechte Erdung3. Inspect and ensure reliable grounding
Loose installation1. Clip not fully locked1. Reinstall until a click sound is heard
2. Loosening caused by vibration2. Fit shock-absorbing pads or reinforce installation

6.2 Maintenance Procedures

  1. Tägliche Inspektion (Wöchentlich)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. Routinewartung (Jeder 6 Monate)

Power off and remove dust on the contact block

Kontaktwiderstand messen (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Jährliche Wartung

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Quick Diagnosis Tips

No signal? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

Signal interference? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. Auswahl & Installationsrichtlinien

7.1 Auswahlregeln

Kompatibilität: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

Kontaktkonfiguration: Select 1NO+1NC (GVAE11), 2NEIN (GVAE20) or 2NC (GVAE02) according to control demands

Montageposition: Choose GVAE11 for front mounting, GVAE14 for side mounting

Aktuelle Übereinstimmung: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 Installationshinweise

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Verkabelungsstandard: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

Protection Measures: Install extra enclosures for dusty or humid environments

  1. Production Status & Ersatzlösungen

Current Status of GVAE11: In production, no discontinuation plan (as of June 2026)

Upgrade & Ersatzoptionen:

  1. Funktionserweiterung: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. Intelligent Upgrade: TeSys T series (with communication function for network-based status transmission)
  3. Inländische Alternative: Compatible domestic GVAE11 models (lower cost with equivalent performance)

Vorher: