Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

 Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Leistungsschalter/

Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker

Vollständiger Produktname: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector) 3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15 Model Decoding 3RV6 0 11-1 AA 15 3RV6: SIRIUS domestic motor protection circuit-breaker 0: Motor protection application 11: Frame size S00 (Width 45 mm) 1: Standard breaking capacity AA: Thermal overload setting ...

  • Produktdetails

Vollständiger Produktname: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector)

3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15

Modelldekodierung

3RV6 0 11-1 AA 15

3RV6: SIRIUS domestic motor protection circuit-breaker

0: Motor protection application

11: Frame size S00 (Width 45 mm)

1: Standard breaking capacity

AA: Thermal overload setting range 1.1-1.6 A

15: Built-in side auxiliary contacts 1NO+1NC (10 = without auxiliary contacts)

Technische Kernparameter

ArtikelSpezifikation
Thermal overload setting (A)1.1 … 1.6 A
Short‑circuit release N‑release21 A (13×In)
ReiseklasseCLASS 10 (Normal motor starting)
Hauptstromkreispole3P
NennbetriebsspannungAC‑690 V
Rated motor power @400V0.55 kW
Breaking capacity Icu@400V100 kA
BeendigungSchraubklemmen
HilfskontakteIntegrated side‑mounted 1NO + 1NC
Montage35 mm DIN‑rail, oder Schraubmontage
GesamtabmessungenW45 mm × H97 mm × D91 mm
SchutzgradIP20 (Front side)
Betriebstemperatur‑20 … +60 ℃
HS customs code85362010

Bestellung & Ersatz

  1. Imported OEM replacement: 3RV2011-1AA15 (identical functions and specifications, made in Germany)
  2. Version without auxiliary contacts: 3RV6011-1AA10
  3. Domestic 3RV6 and imported 3RV2 are fully interchangeable with identical mounting dimensions and wiring.

Typische Anwendungen

Protection for small-size three-phase motors, Bereitstellung von Überlastung, short-circuit and phase-failure protection. Widely used in control cabinets, Fans, pumps and small conveyors. Can be combined with contactors to form a motor starting unit.

Compatible Accessories (S00 frame size)

Side-mount auxiliary contacts: 3RV6901-1A

Side-mount auxiliary contacts: 3RV6901-1E (already integrated in this model)

Unterspannungsauslöser, Arbeitsstromauslöser, rotary operating handle and other expandable accessories.

Anwendungsszenarien von Siemens 3RV6011-1AA15

Strom einstellen: 1.1-1.6A, compatible with 0.55kW three-phase motor at 400V, Class 10 trip characteristic, built-in 1NO+1NC auxiliary contacts, S00 frame size (45 mm Breite). Bietet Überlastung, short-circuit and phase-failure protection. Auxiliary contacts can be used for fault alarm and PLC signal feedback.

  1. Typical Motor Load Applications
  2. Kleine Fans & cooling fan motors

Equipment cooling fans, cabinet ventilation fans, small HVAC fans. Continuous-run loads with moderate starting current. Offers phase-loss and overload protection; auxiliary contacts transmit fan fault signals.

  1. Miniature water pumps & Umwälzpumpen

Small process circulation pumps, Kühlwasserpumpen, laboratory pumps. Rapid thermal tripping upon pump stalling to prevent motor burnout.

  1. Small conveying & drive equipment

Mini belt conveyors, small rollers, feeding mechanisms, compact conveyor drives. For standard direct-on-line (DOL) starting. Combined with 3RT7 contactors for complete motor starter assemblies.

  1. Machine-tool auxiliary drive motors

Machine-tool coolant pumps, lubrication pumps, small feed auxiliary motors. Compact cabinet installation; fault signals sent to PLC for equipment alarm.

  1. Small actuators for packaging & Druckmaschinen

0.55 kW three-phase drive motors for compact packaging machines, labellers and printing auxiliary equipment.

  1. Non-motor & System-level Applications
  2. Protection for small three-phase control transformers

Overload and short-circuit protection for low-inrush small-size transformers. Not suitable for transformers with high magnetizing inrush current.

Notiz: Use 3RV64 series for transformers with heavy inrush to avoid nuisance tripping.

  1. Compact motor feeder circuits inside control cabinets

High-density DIN-rail layout for multi-loop small-motor cabinets. Built-in 1NO+1NC eliminates extra auxiliary contact modules; outputs trip/closed status signals to PLC and HMI.

  1. Motor protection inside standalone machines

Integrated protection for built-in machine motors. Can also serve as an isolating switch for maintenance.

  1. Industry Sectors

Industrielle Automatisierung: Custom special-purpose machinery, Prüfgeräte

HVAC: Unit internal small fans and circulation pumps

Werkzeugmaschinen: Coolant and lubrication pump motors

Materialhandhabung: Mini conveying mechanisms

Labor & Prüfgeräte: Small three-phase drive assemblies

Compact control cabinets & OEM export equipment (Domestic 3RV6, cross-compatible with imported 3RV2011-1AA15)

  1. Recommended System Configurations
  2. Direct-on-line (DOL) starter: 3RV6011-1AA15 + 3RT7 contactor. Complete motor protection-starter unit. 3RA1931 bus module enables fast assembly without inter-wiring, spart Platz im Schrank.
  3. Signal feedback configuration: NC contact for fault alarm; NO contact for closed-state feedback, connected to PLC digital input modules.
  4. Non-applicable Conditions
  5. Frequent heavy-duty starting and high-shock loads (incompatible with Class 10 trip characteristic)
  6. Motors with rated current outside 1.1-1.6 A range
  7. Transformers with high magnetizing inrush risk of unwanted tripping
  8. Outdoor environments with heavy dust or corrosive atmosphere (requires additional protective enclosure)

Rated Operational Voltage of 3RV6011-1AA15

Main-circuit rated operational voltage Ue: AC-690V (50-60 Hz)

Detaillierte Spezifikationen

  1. Common operating voltages for motors

AC400V: Standard three-phase motor operating condition, matches 0.55 kW motor

AC230V / AC500V / AC690V are permissible. Breaking capacity remains 100 kA at 690 V.

  1. Rated voltage for auxiliary contacts (1NO+1NC)

AC-15: Max. 230 V; DC-13: Max. 60 V

⚠️ Auxiliary contacts shall not be connected to 690 V main circuits. Reserved for low-voltage signal circuits only.

  1. Bemessungsstoßspannungsfestigkeit Uimp: 6 kV

Standards reference: IEC 60947-2, IEC 60947-4-1. Domestic 3RV6 and imported 3RV2011-1AA15 share identical voltage ratings.

Overall Dimensions of Siemens 3RV6011-1AA15 (S00 Frame Size)

ArtikelWert
Breite W45 mm (DIN‑rail footprint width in cabinet)
Höhe H97 mm
Tiefe D91 mm (Body depth, protrusion depth after DIN‑rail mounting)
RahmengrößeS00
NettogewichtCa. 0.29 kg

Mounting Instructions

  1. Montagemöglichkeiten: 35 mm DIN-rail snap-on mounting, or base-plate screw fastening
  2. Montageausrichtung: Any mounting position is allowed
  3. Clearance requirements:

Vertikaler Abstand: ≥50 mm

Seitlicher Spielraum: ≥30 mm

Rear clearance: 0 mm (flush against DIN-rail)

Imported replacement 3RV2011-1AA15 has identical dimensions for direct drop-in replacement.

Vorher:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen