The IP8000 is a classic SMC mechanical E/P electro-pneumatic positioner (non-smart, no HART). It is designed for linear-stroke pneumatic diaphragm actuators. It receives a 4~20mA current signal and converts it into supply air pressure to drive control valves. It replaces the older IP6000 series. The IP8100 in the same series is for rotary-stroke applications. The IP8001/IP8101 are smart versions with auto-tuning and share the same housing.
✅ Wichtige technische Spezifikationen
| Artikel | IP8000 (Hebeltyp) |
| Eingangssignal | DC 4~20mA, Eingangswiderstand: 235±15Ω |
| Supply Air Pressure | 0.14~0,7 MPa |
| Applicable Stroke | 10~85mm (linear valve stem) |
| Genauigkeit | Sensitivity ≤0.1%FS; Linearity ±1%FS; Hysteresis ≤0.75%FS; Wiederholgenauigkeit ±0,5 % FS |
| Schutz vor Eindringen | IP65 (IEC60529) |
| Umgebungstemperatur | -20~80℃ for standard model; ExdⅡBT5 explosion-proof: -20~60℃ |
| Air Ports | Rc1/4 / G1/4 / 1/4NVV; Gauge port Rc1/8 |
| Elektrischer Anschluss | G1/2, M20×1,5, 1/2NPT optional |
| Vibrationsfestigkeit | No resonance within 5~200Hz |
| Mounting Standard | Compliant with NAMUR, DIN/IEC 60534-6-1 brackets |
📌 Model Code Definition (IP8000-□□□)
IP8000: Lever-type mechanical electro-pneumatic positioner
- Pressure gauge specification: 0=0.3MPa, 3=1.0MPa
- Konstruktion: Standard housing / ExdⅡBT5 explosion-proof terminal box
- Zubehör: Restrictor pilot valve, yoke linkage, extended feedback lever, usw.
- Thread type, CE marking, special custom codes (z.B. X310=IP66)
🛠 Working Principle & Installationsrichtlinien
- Prinzip: A 4~20mA current energizes the torque motor. The nozzle-flapper amplifies the signal to control the output air pressure of the pilot valve. The feedback lever captures the actual valve stem position to form a closed loop, ensuring valve position matches the input signal.
- Key Installation Rule: Bei 50% Signal (12mA), the feedback lever should form a 90° right angle with the valve stem. Select the internal feedback spring according to single-acting or double-acting actuators.
- Einstellung: Mechanical Zero and Span knobs. Supports split range operation. Equipped with manual/auto switching screw for manual air supply during commissioning.
⚠️ Allgemeine Fehlerbehebung
- Valve fails to move
No supply air or insufficient air pressure; 4~20mA wiring reversed; nozzle/restrictor blocked by dust; torque motor damaged.
- Oscillation / Jagd
Incorrect feedback lever mounting angle; unstable supply air pressure; stuck pilot valve; excessive friction of valve packing.
- Poor linearity / Zero drift
Zero/span not calibrated; loose feedback linkage; air piping leakage; large ambient temperature variation.
- Insufficient output pressure
Foreign matter jamming pilot valve; leaking actuator diaphragm/cylinder; clogged air filter.
Maintenance Reminder: Unterbrechen Sie vor der Demontage die Luftzufuhr und lassen Sie den Druck vollständig ab. Reinigen Sie die Düsenöffnung mit einem 0,2 mm dünnen Draht. Tragen Sie beim Zusammenbau der O-Ringe leicht das Silikonfett TORAY SH45 auf.
📋 Modellauswahl & Alternativen
IP8000: Mechanisch, Linearhubhebel. Für herkömmliche Regelventile, niedrige Kosten, keine Kommunikation.
IP8100: Mechanisch, Drehnocke, für Absperrklappen und Kugelhähne.
IP8001: Intelligenter linearer Hub. Automatische Kalibrierung, HIRSCH, Fehlerdiagnose, Upgrade-Ersatz für IP8000.
Inländische Alternativen: Inländische E/P-Positionierer wie Wuzhong und Chuanyi. Halterung überprüfen, Luftanschluss und Hubanpassung.
📎 Typische Anwendungsszenarien
Kontinuierliche Regulierung des Durchflusses, Druck und Füllstand an linearen pneumatischen Membranregelventilen in der Chemie, Wasseraufbereitung, HVAC, Papier, Öl & Gasleitungen. Für explosionsgefährdete Bereiche stehen explosionsgeschützte Versionen ExdⅡBT5 zur Verfügung.
SMC IP8000 Elektropneumatischer Ventilpositionierer – Anwendungsszenarien
The IP8000 is a linear-stroke mechanical E/P positioner matching diaphragm linear pneumatic control valves. It converts 4~20mA analog signal into air pressure to drive valve stem for continuous process regulation. No HART communication.
🏭 Industry Applications
- Wasser / Abwasserbehandlung
Inlet flow regulation, pH dosing line, Flüssigkeitsstandkontrolle, aeration pressure regulation. Standard non-explosion model is sufficient; IP65 preferred for outdoor installation.
- HVAC & Heating Networks
Temperature control for primary/secondary side of heat exchangers, regulating steam/hot water linear control valves.
- Papierindustrie
Pulp concentration control, white water flow, steam pressure regulation. Dust-prone workshop; air filtration is mandatory to prevent nozzle blockage.
- Chemische Industrie (Use ExdⅡBT5 explosion-proof IP8000 for hazardous zones)
Kontinuierliche Regulierung des Durchflusses, pressure and level in process pipelines. Für explosionsgefährdete Bereiche mit Lösungsmitteln und leichten Kohlenwasserstoffen ist ein explosionsgeschütztes Gehäuse erforderlich.
Notiz: IP8000 ist mechanisch ohne intelligente Diagnose. Verwenden Sie IP8001, wenn HART und Auto-Tuning erforderlich sind.
- Essen & Getränk / Pharmazeutisch (Sanitärdienst)
Gereinigtes Wasser, Waschwasser- und Dampfregulierung, gepaart mit Sanitär-Linearregelventilen. Bevorzugen Sie saubere Instrumentenluft.
- Leistung & Wärmekraftwerke
Kesselspeisewasser, Enthitzung und Druckreduzierung, Kontrolle des Kondensatniveaus; Hilfsventile für die Prozesssteuerung.
- Öl & Gasspeicherung & Transport (Explosionsgeschützte Ausführung)
Druck- und Durchflussregelung für Rohöl-/Produktleitungen, Tankfüllstandskontrolle. Explosionsgeschütztes Exd-Modell für explosionsgefährdete Bereiche.
✅ Passende Ventiltypen
Einfachwirkend / Doppeltwirkende lineare pneumatische Membranregelventile (beste Übereinstimmung)
Käfiggeführte Ventile, Einsitzventile, Käfigregelventile
❗ Absperrklappen, Kugelhähne und andere Drehventile erfordern IP8100, IP8000 ist nicht anwendbar.
📌 Application Characteristics
Kontrolltyp: Continuous modulating (not on/off valve). 4~~20mA corresponds to 0~~100% valve travel.
Air source: Sauber, trocken, oil-free compressed air. Air filter regulator (AFR) must be installed upstream.
Vorteile: Einfache Struktur, einfache Wartung, good anti-EMI performance. Suitable for sites without bus communication requirements and limited budget.
Einschränkungen: Mechanical feedback, no auto-calibration. Manual zero and span adjustment required; no fault diagnosis.
❌ Nicht empfohlene Szenarien
- Severe oscillation, strong corrosive gas (extra housing protection required).
- Remote diagnosis, HART communication, auto-tuning required → upgrade to IP8001.
- Rotary butterfly / ball valves → select IP8100.
- Starker Staub, unpurified instrument air (high risk of nozzle clogging).
SMC IP8000 — Selection Checklist
Applicable to IP8000 linear mechanical electro-pneumatic positioner; Use IP8100 for rotary applications; IP8001 smart model has separate selection rules.
- Aktuator & Grundlegende Informationen zum Ventil
| Artikel prüfen | Auswahlvoraussetzungen & Bemerkungen |
| Aktuatortyp | Pneumatischer Membranantrieb mit linearem Hub (einfachwirkend / doppeltwirkend). Nicht für Dreh-/Kugelhähne. |
| Ventilschafthub | 10~85mm; Bestätigen Sie den tatsächlichen Hub. Reisen außerhalb des Bereichs ungültig; Ein zu kleiner Hub beeinträchtigt die Genauigkeit des Rückkopplungshebels. |
| Aktuatoraktion | □ Einfachwirkend (Federrückstellung), Ersetzen Sie die interne Rückführfeder im Stellungsregler |
| □ Doppeltwirkend (kein Frühling, bidirektionale Luftzufuhr), Ersetzen Sie die interne Rückkopplungsfeder | |
| Ventiltyp | Einzelsitz / Käfig / käfiggeführte modulierende Regelventile; modulierender Dienst, not on/off valve |
| Stammdurchmesser & Halterung | DIN/IEC 60534-6-1 / NAMUR-Standard. Überprüfen Sie die Rückkopplungsverbindung und das Jochzubehör. Übermäßiges Wackeln des Schafts führt zu Schwingungen. |
- Verfahren & Betriebsbedingungen
| Artikel prüfen | Auswahlvoraussetzungen & Bemerkungen |
| Prozessmedien | Wasser, Dampf, Luft, allgemeine chemische Flüssigkeiten. Bewerten Sie den Gehäuseschutz für stark korrosive Medien. |
| Explosionsschutzanforderung | □ Standardmäßig explosionsgeschützt (sicheren Bereich) |
| □ ExdⅡBT5 explosionsgeschützt (Gefahrenbereich, Temperaturgrenze: -20~60℃; standard model -20~80℃) | |
| Umgebungstemperatur | Standard: -20℃ ~ +80℃; Explosionsgeschützt: -20℃ ~ +60℃. Heat insulation required for over-temperature sites. |
| Enclosure Protection | Standard IP65; IP66 optional (suffix X310). IP65+ recommended for outdoor, feuchte und staubige Umgebungen. |
| Vibration | No resonance from 5~200Hz. Reinforce linkage under heavy vibration to avoid continuous hunting. |
| Control Requirement | 4~20mA analog continuous modulation; No HART, no auto-tuning. Manual zero/span calibration needed. |
- Air Supply System Check (Highest Failure Source)
| Artikel prüfen | Auswahlvoraussetzungen & Bemerkungen |
| Supply Pressure Range | 0.14~0,7 MPa. Stable pressure; pressure fluctuation easily triggers valve oscillation. |
| Air Quality | Trocken, sauber, oil-free compressed air. Pre-install air filter regulator (AFR) to remove water, oil and dust. Dust environment easily clogs nozzle. |
| Air Port Thread | G1/4 / Rc1/4 / 1/4NVV; gauge port Rc1/8. Confirm thread before ordering. |
- Electrical Check
| Artikel prüfen | Auswahlvoraussetzungen & Bemerkungen |
| Eingangssignal | DC 4~20mA; Input resistance 23515. Match signal source load capacity. |
| Electrical Entry | G1/2 / M20*1.5 / 1/2NVV. Explosion-proof model requires explosion-proof cable gland. |
| Verdrahtung | 2-wire 4-20mA. Polarity matters; Eine umgekehrte Polarität führt zu keinem Betrieb. Für große Entfernungen wird ein abgeschirmtes Kabel empfohlen, einseitige Erdung. |
- Auswahl an Zusatzzubehör
□ Manometer: 0=0.3MPa, 3=1.0MPa (Auswahl basierend auf dem Ausgangsdruckbereich)
□ Feedback-Hebel, yoke linkage (abgestimmt auf den Antriebshub)
□ Luftfilterregler, Luftschläuche
□ Montagehalterung und Befestigungselemente
□ Explosionsgeschützte Kabelverschraubung (obligatorisch für explosionsgeschützte Modelle)
- Ausschlusskriterien (Wählen Sie NICHT IP8000 aus, falls zutreffend)
- Zellenradschleuse (Schmetterling / V-Kugelventil) → IP8100 verwenden
- HART communication, Ferndiagnose, Autotuning erforderlich → IP8001 verwenden
- Ungereinigte Luftquelle mit starkem Staub, Öl und Kondensat
- Ventilhub >85mm bzw <10mm
- Starke Korrosion, starke Stoßvibrationen ohne Schutzmaßnahmen
- Auswahlbeispiel (Modellcode-Referenz)
IP8000-3 (1.0MPa-Messwert) + explosionsgeschützt + G1/4 Luftanschluss + Elektrischer Eingang M20
IP8000-301: 1.0MPa-Messwert, Standardgehäuse, Standardhebelbaugruppe
- Inspektion vor der Installation
- Luftleitungen vollständig gespült, um Schweißschlacke und Rückstände zu entfernen.
- Feedback lever near 90° at 50% Signal (12mA).
- No leakage on actuator; packing friction shall not be excessive.
- Shielded cable grounding; separate routing from power cables to avoid VFD interference.
SMC IP8000 Electro-Pneumatic Valve Positioner — Maintenance Manual
Applicable to IP8000 mechanical linear E/P positioner; Pre-work safety: Disconnect 4~20mA signal, shut off air supply and vent pressure. Never open housing under pressure.
- Wartungsintervalle (Täglich / Vierteljährlich / Jährlich)
1) Daily Routine Inspection (per shift / daily visual check)
- Check housing for air leakage, Kondensation, corrosion and loose fittings.
- Observe two pressure gauges for stable readings; watch for fluctuation/hunting.
- Check valve stem movement: smooth travel, no sticking or abnormal noise.
- Drain condensate from air filter regulator in a timely manner.
- Check mounting bracket, feedback linkage and bolts for looseness.
Warning sign: Messnadel springt ständig, Ventil schwingt → Überprüfen Sie zuerst den Rückkopplungsmechanismus oder die Düsenverstopfung.
2) Vierteljährliche Wartung (jeder 3 Monate)
- Filterelement des Luftfilterreglers prüfen; bei Verschmutzung ersetzen.
- Rückführhebel prüfen, Joch- und Stiftwellen: Tragen Sie nur minimales Fett auf (NICHT übermäßig schmieren! Überschüssiges Fett fängt Staub ein und verstopft die Düse).
- Hardware festziehen: Befestigungsschrauben des Stellungsreglers, Rohrverschraubungen und Klemmenblöcke.
- Funktionstest: Eingang 4mA, 12mA, 20mA, Zeichnen Sie die Nullpunkt- und Bereichsabweichung auf.
- Kabel und Kabelverschraubung prüfen; Stellen Sie sicher, dass die Dichtung intakt ist, kein Wassereintritt.
3) Jährliche Überholung (einmal im Jahr; jeder 6 Monate unter harten Bedingungen)
- Gerät demontieren, Innengehäuse reinigen, Konzentrieren Sie sich auf die Düse, Klappe und Vorsteuerventildrossel (höchster Fehlerpunkt).
- Zerlegen und überprüfen Sie die O-Ringe; Ersetzen Sie den vollständigen Dichtungssatz, wenn er veraltet ist, verhärtet oder rissig.
- Überprüfen Sie die Spule des Drehmomentmotors auf Verfärbungen durch Überhitzung; Überprüfen Sie den Spalt zwischen Düse und Prallplatte.
- Nullpunkt und Spanne neu kalibrieren, Kalibrierdaten aufzeichnen.
- Überprüfen Sie den Luftschlauch; Ersetzen Sie veraltete Schläuche.
- Zusätzliche Prüfung bei explosionsgeschützter Ausführung: Explosionsfugenoberfläche unbeschädigt, Dichtung intakt, druckfest, spaltkonform.
Harter Service (Staub, Luftfeuchtigkeit, Abwasser, Papier): Wartungsintervall um die Hälfte verkürzen.
- Wartung wichtiger Komponenten
✅ Düse & Flapper (Häufigste Fehlerquelle)
- Reinigung: Verwenden Sie 0,2 mm dünnen Nylon-/Kupferdraht, um die Düsenöffnung vorsichtig zu reinigen. Zerkratzen Sie die Düsenoberfläche nicht mit hartem Stahldraht.
- Staub mit trockener Druckluft bei niedrigem Druck blasen (≤0,2 MPa). Spülen Sie das Innere des Stellungsreglers niemals mit Flüssigkeit.
- Prallplattenoberfläche frei von Kratzern und Ölverschmutzungen. Kratzer verursachen ständiges Jagen; Ersetzen Sie die Düsen-Prallplatten-Baugruppe.
- Erfordernis: Die Instrumentenluft muss trocken und ölfrei sein. Der Ölfilm auf der Düsenklappe führt zu Drift und Schwingungen.
✅ Feedback-Hebelbaugruppe
- Tragen Sie nur eine kleine Menge Schmiermittel auf die Stiftschäfte und Drehzapfen auf; no heavy grease.
- Check linkage for deformation; no sticking during stem movement.
- Bei 50% Signal (12mA), lever should stay near 90°. Readjust mounting if angle deviates largely.
✅ Seals (O-rings)
O-rings age and harden under large temperature fluctuation and continuous operation.
Apply thin layer of TORAY SH45 silicone grease when replacing O-rings, avoid over-application.
Prevent scratches on O-ring grooves during assembly.
✅ Electrical Section
- Inspect 4~20mA 2-wire terminals for oxidation and looseness; single-end grounding for shielded cable.
- Explosion-proof model: power cut before cover removal. Do not damage flameproof mating surface; seal gasket and cable gland must remain sealed.
- Separate signal cables from power cables to avoid VFD interference.
- Long-Term Shutdown Preservation (Out of service >1 month)
- Shut off air supply and vent pressure; Trennen Sie das 4-20-mA-Signal.
- Ventil auf Mittelstellung stellen (50% Öffnung) um langfristige einseitige Federbelastungen zu reduzieren.
- Kondensat aus Luftfilter ablassen.
- Decken Sie das Gehäuse zum Schutz vor Staub ab, um Staubansammlungen auf der Düsenklappe zu vermeiden.
- Luftleitungen spülen und Null neu kalibrieren & Spanne vor der Wiederinbetriebnahme.
- Verbotene Operationen (Wichtige Warnungen)
❌ Öffnen Sie das Gehäuse des Stellungsreglers unter Druck oder unter Strom
❌ Düsen-Prallplatten-Baugruppe mit Hochdruck-Druckluft anstrahlen
❌ Tragen Sie eine große Menge Fett auf (Fängt Staub ein und verstopft die Düse)
❌ Innenteile mit Flüssigkeit spülen (Wischen Sie die Gehäuseaußenseite nur mit einem feuchten Tuch ab)
❌ Force-Feedback-Hebel; kann Torquemotor und Nocken verformen
❌ Instrumentenluft mit Öl verwenden, Wasser und schwere Verunreinigungen
- Verfahren zur Überprüfung nach der Wartung
Befolgen Sie die Reihenfolge nach der Wartung:
- Luftzufuhr anlegen, Überprüfen Sie, ob alle Luftverbindungen dicht sind.
- Connect 4~20mA signal generator.
- 4mA → zero calibration; 20mA → span calibration; repeat 2~3 cycles.
- Test linearity at midpoint 12mA; confirm no oscillation or lag.
- Record calibration data and file maintenance log.
- Quick Fault Reference During Maintenance
- Valve hunting / small cycling: Dirty nozzle/flapper; wrong feedback lever angle; unstable supply air.
- Zero drift: Condensate in air; minor O-ring leakage; slight nozzle clogging.
- Insufficient output pressure: Stuck pilot valve; clogged air filter.
- Large hysteresis: Pivot sticking and high friction; excessive packing friction of actuator.
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter




















NH42-63-318x560.png)