Disyuntor de aire Chint NA1-3200X-3200M/3P

  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 Corriente nominal del marco: 3200A (maximum current specification of the breaker) X Breaking capacity grade: Class X (100el); distinguished from standard type (80el) and Class H (120el) 3200 Corriente de funcionamiento nominal: 3200A (actual set working current) M Trip unit type: Intelligent trip ...

  • Detalles del producto

 

Segmento de códigoDescripción
NA1Series code for Chint air circuit breakers (ACB)
3200Corriente nominal del marco: 3200A (maximum current specification of the breaker)
incógnitaGrado de capacidad de ruptura: Class X (100el); distinguished from standard type (80el) and Class H (120el)
3200Corriente de funcionamiento nominal: 3200A (actual set working current)
METROTipo de unidad de disparo: unidad de viaje inteligente (micrológico); distinguished from standard Type L and high-breaking Type H
3PAGNúmero de polo: 3-polo (3-protección del circuito de fase, without neutral pole)
  1. Especificaciones técnicas básicas
Categoría de parámetroDatos técnicos
Tipo de productoIntelligent low-voltage air circuit breaker (ACB)
Tensión operativa nominalAC 400V/690V, 50Hz
Marco actual (Iu)3200A
Corriente de funcionamiento nominal (En)3200A
Rated Ultimate Short-circuit Breaking Capacity (uci)100el (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (ics)100el (equal to Icu)
Rated Short-time Withstand Current (icw)80el (1s)
Unidad de viajeType M intelligent trip unit, con sobrecarga de retardo prolongado, cortocircuito de retardo de corta duración y protección instantánea contra cortocircuito
Tipo de montajeDraw-out or fixed type (X series is generally draw-out)
Modo de operaciónManual or motorized (motor operating mechanism optional)
Control Circuit VoltageAC 220V/380V or DC 220V (opcional)
Contactos auxiliaresEstándar: 5NO + 5CAROLINA DEL NORTE (ampliable)
Protección de ingresoIP30 (compatible con GB/T 4942.2)
Applicable StandardsGB/T 14048.2, CEI/EN 60947-2
Dimensiones (Alto×Ancho×Profundidad)Draw-out type: aprox. 600mm×400mm×1000mm (refer to official manual for exact data)
PesoAprox.. 80~100kg (varies by mounting type and accessory configuration)
  1. Características principales

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Protección de falla a tierra: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 Diseño de alta confiabilidad

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Long service life: Mechanical durability up to 10,000 operaciones; electrical durability up to 5,000 operaciones.

Vibration and shock resistance: Cumple con GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Ampliabilidad flexible

Rich optional accessories: viaje de derivación, undervoltage trip, closing solenoid, motor charging mechanism, contactos auxiliares, contactos de alarma, key lock, etc..

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Escenarios de aplicación

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Large motor: Incoming switch for Motor Control Center (MCC)

UPS system: Protection switch for UPS input and output circuits

Escenarios de aplicación

  1. Distribución de energía industrial: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Centros de datos: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infraestructura: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Comparación de modelos
ModeloCapacidad de rupturaCorriente nominalUnidad de viajeSolicitud
NA1-3200-3200M/3P80el (Estándar)3200AType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100el (Class X)3200AType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120el (Clase H)3200AType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100el (Class X)2500AType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100el (Class X)3200AType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
chintsiemensSchneiderTEJIDOmitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Capacidad de ruptura100el100el100el85el
Unidad de viajeType M IntelligentETU25B Intelligentmicrológico 5.0 InteligenteStandard Intelligent Trip
Tipo de montajeDraw-out / FijadoDraw-out / FijadoDraw-out / FijadoDraw-out / Fijado
ComunicaciónOptional Modbus / ProfinetOptional Profinet / Ethernet/IPOptional Modbus / ProfinetOptional CC-Link / Profinet
  1. Selección & Application Guidelines
  2. Breaking capacity matching: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000A, 2500A, 3200A.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Mounting type: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Operation mode: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Select shunt trip, undervoltage trip, auxiliary contacts and communication modules as required by control and protection logic.
  8. Mantenimiento: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Viaje de derivación (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TipoModeloTensión nominalConsumo de energíaSolicitudSelection Code
Continuous (Por defecto)NA1-F-3200XAC220V/230V460Virginia(CA 220 V.)control industrial general, infrequent operationF-AC220
AC380V/400V400Virginia(CA380V)F-AC380
DC110V70W.(DC110V)F-DC110
DC220V140W.(DC220V)F-DC220
Pulse Type (Recomendado)NA1-FP-3200XAC220V/230V880Virginia(CA 220 V.)Wind & solar power, ATS system, frequent operationFP-AC220
AC380V/400V1800Virginia(CA380V)FP-AC380
DC110V850W.(DC110V)FP-DC110
DC220V880W.(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, máximo 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Disparo por subtensión (q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TipoModeloTensión nominalOperating CharacteristicDelay TimeSelection Code
Instant Suction (Por defecto)NA1-Q-3200XCA 230 V.Trip at 70% Us, reliable trip at 35% UsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XCA 230 V.Igual que arriba1s/3s/5s (Fijado)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XCA 230 V.Igual que arriba0.3s~7.5s (Ajustable)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1CA 230 V.Automatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (incógnita) / Closing Coil

For remote closing, matched with motor charging mechanism.

TipoModeloTensión nominalConsumo de energíaSolicitudSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (METRO)

Stores energy for breaker closing and provides closing power.

ModeloTensión nominalFuerzaCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kilovatios≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. Control inteligente & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModeloCaracterísticasSolicitudSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3METRO
Type HAdvanced protection with extended parameter settingsComplex power distribution systems & precise protectionh
Type 3HHighest configuration, full 3M+H functions + event loggingCritical circuits & fault analysis3h

2.2 Communication Modules (Monitoreo remoto)

Module TypeModeloProtocolFunciónMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUAdquisición de datos & mando a distanciaNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetEthernet communicationPSU-1 power moduleCOM-PN+PSU-1
Ethernet/IPNA1-COM-ENIPEthernet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NombreModeloFunciónSolicitudSelection Code
Unidad de fuente de alimentaciónPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Indicación de estado & Control)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), ampliable.

TipoModeloConfiguración de contactoClasificaciónSolicitudSelection Code
3 sets TransferNA1-AX-3Z3NO+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Por defecto)NA1-AX-4Z4NO+4NCAC230V/5AConfiguración estándarAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NO+3NCNA1-AX-333NO+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AConfiguración estándarAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AControl complejoAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Enclavamiento mecánico & Safety Accessories

4.1 Enclavamiento mecánico (Misoperation Prevention)

TipoModeloFunciónSolicitudSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2metroATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TipoModeloFunciónSolicitudSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NombreModeloFunciónSolicitudSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
CounterNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceConnecticut
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montaje & Connection Accessories

5.1 Main Circuit Accessories

NombreModeloClasificaciónSolicitudSelection Code
Horizontal BusbarNA1-BUS-H3200AStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200AVertical installation & ahorro de espacioBUS-V
Rotatable BusbarNA1-BUS-R3200AFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NombreModeloFunciónSolicitudSelection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6A, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Ejemplo:

NA1-3200X-3200M/3P, motorized draw-out type, CA 220 V., with shunt trip / undervoltage trip / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, undervoltage trip, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 