Definición del modelo: NU5-I+II = Type T1+T2 combined SPD; 15 = Iimp 15kA (10/350μs); 275 = Uc=275V
✅ Core Parameters
Estándares: GB/T 18802.11, CEI 61643-11
Test Class: Class I+II (T1+T2). Applied as primary lightning protection and secondary voltage limiting for main incoming cabinets
Tensión máxima de funcionamiento continuo Uc: 275V y (for 230V single-phase systems)
Impulse Current Iimp (10/350μs): 15 el
Corriente de descarga nominal en (8/20μs): 25 el
Corriente máxima de descarga Imax (8/20μs): 50 el
Nivel de protección de voltaje elevado: 1.5 kV
Montaje: Standard TH35-7.5 DIN rail
Construcción: Pluggable module. Base remains in place; only replace the failed module
Indicación de estado: Visual window (Verde = Normal, Red = Fault); Remote alarm contact optional
Temperatura ambiente: -35℃ ~ +70℃
Certificaciones: CCC, CE, CB, RoHS
Available Poles: 1PAG / 2PAG / 1P+N / 3PAG / 4PAG / 3P+N
✅ Wiring & Accesorios
Sección del conductor: 2.5~25 mm², tightening torque 2~3 N·m
Required back-up protection: NSCB5-I+II dedicated SPD back-up protector (ordinary MCBs are not recommended)
Protection Modes: L-PE, LN, N-PE
✅ Application Scenarios
Main incoming distribution cabinets of buildings, boundary of lightning protection zone LPZ0→LPZ1. Used for simultaneous discharge of direct lightning current (10/350 waveform) and induced surge (8/20 waveform). Widely used for 230V single-phase and 400V three-phase TN-S systems.
✅ Same Series Comparison
NU5-I+II 12.5-275: Iimp=12.5kA
NU5-I+II 15-275: Iimp=15kA (este modelo)
NU5-I+II 25-275: Iimp=25kA
✅ Equivalent Alternatives
CHINT upgraded replacement: NXU-I+II series;
Other brand equivalents: Delixi DXH01-FS, Schneider iPRD1 15r, ABB OVR T1+2 15-275, etc..
Application Scenarios for CHINT NU5-I+II 15-275
Posicionamiento: T1+T2 combined SPD, Uc=275V, suitable for 230V single-phase / 400V three-phase TN-S distribution. Installed at LPZ0→LPZ1 lightning boundary on main incoming cabinet to discharge direct lightning energy and induced surge in one unit.
✅ Building Applications (Más común)
- Main incoming distribution panel of buildings (at main equipotential bonding point): Edificios de gran altura, complejos comerciales, edificios de oficinas, hoteles, hospitales, escuelas. Eliminates the need for separate Type T1 SPD and saves cabinet space.
- Class II & Class III lightning protection buildings that require Type T1 SPD at power inlet per codes; preferred in high lightning density areas.
- Main distribution boxes of residential compounds and incoming cabinets in power distribution rooms.
✅ Industrial Applications
- Main power incoming cabinets and general power cabinets of factories; for systems with downstream PLCs, VFD, servoaccionamientos, instrumentos, DCS and other low-voltage automatic control equipment requiring surge protection at source.
- Outdoor independent control rooms, casas de bombas, fan rooms, sewage treatment station power incoming cabinets.
- Low-voltage outgoing cabinets of box-type transformers (sistema TN-S).
✅ New Energy Applications
- Grid-tie cabinets of residential and small commercial PV systems (AC side 230/400V). PV sites are vulnerable to surges induced by nearby lightning strikes.
- AC inlet side of small energy storage systems.
✅ Other Applications
- Main incoming feed of monitoring rooms and computer rooms (Nota: This SPD can be installed upstream of UPS; additional T2/T3 SPD shall be fitted downstream of UPS output for graded protection).
- Outdoor base stations, centralized street light distribution boxes, weather stations, remote field monitoring equipment power inlet.
- Power supply cabinets for fire alarm hosts and fire pumps (fire distribution lightning protection).
✅ System Compatibility
Adecuado para: TN-S (privilegiado), TN-C-S, 230V monofásico, 400V three-phase AC 50Hz
Uc=275V, NOT suitable for TT systems or grids with elevated line-to-earth voltage (TT systems generally select 385V versions)
Not for DC circuits
⚠️ Not Recommended Applications
- Sub-distribution cabinets inside LPZ1 zone (NU5-II Type T2 SPD is normally used here; I+II models cost more)
- Terminal sockets and equipment side (use T3 fine protection)
- 10kV high voltage side, DC side of PV arrays, inverter DC terminals
- Grids with sustained overvoltage or severe neutral drift (switch to Uc=385V variant)
✅ Key Installation Notes
NSCB5-I+II dedicated SPD back-up protector is mandatory. Ordinary miniature circuit breakers shall not be used as back-up protection. Equipotential bonding is recommended and earth resistance shall meet lightning protection requirements of the project.
Graded Lightning Protection Scheme for CHINT SPD (Matching NU5-I+II 15-275)
Sistema aplicable: AC230/400V 50Hz TN-S / TN-C-S, Class II / III lightning protection buildings, industrial automation rooms, data rooms, PV AC side; Lightning Zones LPZ0→LPZ1→LPZ2→LPZ3
Principio: Stepwise voltage limiting & energy coordination. Front-end T1+T2 diverts heavy lightning current; downstream T2/T3 further suppress residual voltage to withstandable levels for sensitive electronics.
Full Graded Configuration List
| Lightning Zone | Ubicación de instalación | SPD Model | Tipo | Parámetros clave |
| LPZ0 → LPZ1 | Main incoming cabinet in distribution room (main equipotential) | NU5‑I+II 15‑275 | T1+T2 combined | Iimp=15kA(10/350μs), Uc=275V, Up=1.5kV |
| LPZ1 → LPZ2 | Floor / workshop sub-distribution cabinet | NU5‑II 40‑275 | T2 | In=40kA, Uc=275V, Up≤1.2kV |
| LPZ2 → LPZ3 | UPS inlet of computer room, Gabinete del PLC, fire host cabinet | NU5‑II 20‑275 | T2 | In=20kA, Uc=275V, Up≤1.1kV |
| LPZ3 Equipment Terminal | Servidores, cameras, sensores, VFD control power, circuitos de enchufe | NU5‑III 10‑275 | T3 fine protection | Uc=275V, Up≤0.8kV |
Pole Selection Guide:
Single-phase circuit: 1P+N
Three-phase TN-S: 3P+N (privilegiado)
TN-C-S: Convert to 3P+N at main inlet before branch distribution
Two Simplified Versions
Esquema A: Full Standard Scheme (Preferred for Computer Rooms, Automatización, DCS, Inspection Acceptance)
Main Inlet: NU5-I+II 15-275 → Sub-distribution: NU5-II 40-275 → Low-voltage cabinet: NU5-II 20-275 → Equipment terminal: NU5-III
✅ Ventajas: Good energy coordination, surge energy attenuated stage by stage, highest safety for precision equipment, easy to pass lightning inspection
✅Adecuado para: Projects equipped with PLC, VFD, instrumentos, Unión Postal Universal, servers and fire alarm systems
Esquema B: Economy Simplified Scheme (Ordinary Office Buildings, Residential Districts, General Lighting & Fuerza)
Main Inlet: NU5-I+II 15-275 → Sub-distribution: NU5-II 40-275
No separate T3 at terminals; add T3 only for critical equipment as required
✅Adecuado para: Systems dominated by lighting and power loads with few low-voltage devices, control de costos
⚠️ Critical Coordination Rules (Key for Acceptance)
- Cable Length Requirement for SPD Energy Coordination
Cable length between T1+T2 (NU5-I+II) and next-stage T2 SPD ≥5m; Decoupler must be fitted if less than 5m. Otherwise front SPD may not operate and downstream SPD will fail first.
Recommended ≥5m between T2 and T3; decoupler is also required if insufficient.
- Toma de tierra & Alambrado
SPD earthing conductor: corto, straight and thick, ≥16mm² copper recommended, avoid looping and sharp bends
PE terminal of all SPDs connect to same equipotential bar, daisy-chain earthing is forbidden
- Precondition for Uc=275V
Stable grid voltage with minimal neutral drift. For TT systems or grids with high voltage, upgrade the whole set to Uc=385V series (NU5-I+II 15-385)
- No Mixing of Back-up Protectors
NSCB5-I+II must be used for I+II SPD instead of ordinary MCB; NSCB5-II for T2 SPD. De lo contrario, SPD fire hazard cannot be reliably isolated.
📌 Application Example (Three-phase TN-S Automation Workshop)
Transformer low-voltage incoming cabinet: 3P+N NU5-I+II 15-275 + NSCB5-I+II
→ Workshop power sub-cabinet: 3P+N NU5-II 40-275 + NSCB5-II
→ PLC control cabinet inlet: 1P+N NU5-II 20-275 + NSCB5-II
→ VFD control power & sensor power supply: NU5-III
Suplementario: Signal Surge Protection (A menudo se pasa por alto)
After power surge protection, separate signal SPDs are required for Ethernet, RS485, 4-20mA analog signals. All SPDs share the same equipotential bonding; otherwise surge may damage modules through signal lines.
CHINT Low-voltage Power SPD Full Model List (Common Engineering Models by Series)
Naming Note: Suffix F = with remote alarm contact; polacos: 1PAG / 1P+N / 2PAG / 3PAG / 3P+N / 4PAG; Uc options 275V / 385V
- NU5 Series (Mainstream established series; NU5-I+II 15-275 belongs here)
NU5-I+II (T1+T2 combined, main inlet primary lightning protection)
NU5-I+II 12.5-275 (Iimp=12.5kA)
NU5-I+II 15-275 (Iimp=15kA, este modelo)
NU5-I+II 25-275 (Iimp=25kA)
NU5-I+II 12.5-385
NU5-I+II 15-385
NU5-I+II 25-385
Remote alarm variant: NU5-I+II-F xxx-xxx
NU5-II (T2 secondary, sub-distribution cabinet)
NU5-II 20-275 / 20-385
NU5-II 40-275 / 40-385
NU5-II 65-275 / 65-385
NU5-II 80-275 / 80-385
NU5-II 100-275 / 100-385
NU5-II 120-275 / 120-385
Remote alarm variant: NU5-II-F
NU5-III (T3 fine protection, equipment terminal)
NU5-III 10-275
NU5-III 10-385
- NXU Series (New upgraded series to replace NU5, tamaño compacto, rendimiento mejorado)
NXU-I+II (T1+T2 combined)
NXU-I+II 12.5-275
NXU-I+II 25-275
NXU-I+II 12.5-385
NXU-I+II 25-385
NXU-I+II 50-275/385
Remote alarm variant: NXU-I+II-F
NXU-II (T2 secondary)
NXU-II 20, 40, 65, 80, 100, 120, 160-275 / 385
Remote alarm variant: NXU-II-F
NXU-III (T3 terminal)
NXU-III 10-275 / 385
III. NU6 Series (Economical T2, widely used in real estate & civil projects)
NU6-ⅡG (T2, G = pluggable modular, remote alarm optional)
NU6-IIG 40, 65, 80, 100-275 / 385 / 440
Remote alarm variant: NU6-IIGF
NU6-III (T3 terminal, enchufe / weak current box)
NU6-III 10-275
- Other Low-volume Power SPDs
NU210-40: Non-pluggable economical T2
NUH-40B: Legacy stock model, eliminado gradualmente
- Matching SCB Back-up Protectors (Must match SPD type, cross-type use forbidden)
NSCB5 (For NU5 series)
NSCB5-I+II: Exclusively for NU5-I+II T1+T2
NSCB5-II: Exclusively for NU5-II T2
-Current ratings: 20A, 40A, 65A, 100A, 120A; Poles 1P/2P/3P/4P
NXSCB (For new NXU series)
NXSCB-I+II: Back-up for NXU-I+II
NXSCB-II: Back-up for NXU-II
- Signal Surge Protectors (For automation: RS485 / Ethernet / Cosa análoga)
NVS-RJ45: Ethernet surge protection (CCTV, interruptores)
NVS-485: RS485 bus surge protection (instrumentos, SOCIEDAD ANÓNIMA)
NVS-AI: 4-20mA analog signal surge protection
NVS-BNC: Coaxial video surge protection
✅ Guía de selección rápida
- Main inlet LPZ0→LPZ1: NU5-I+II / NXU-I+II
- Floor / workshop sub-panel LPZ1→LPZ2: NU5-II / NXU-II / NU6-IIG
- Inside PLC & UPS cabinet: NU5-II 20kA class
- VFD, camera, sensor terminal: NU5-III / NXU-III
- Back-up rule: NSCB5-I+II only for I+II SPD; NSCB5-II for T2 SPD
⚠️ Discontinued Model Note
Legacy NU1, NU2, NU3, NU4, Ex9UE series are discontinued. New projects are recommended to adopt NU5 or NXU series.
contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor



















NH42-63-318x560.png)



