Samwha EOCR from Korea, integrated into the Schneider EOCR product line, made in Korea, exclusively for EOCR motor protection relays.
- Definición del modelo
3Connecticut: Three-phase integrated transformador de corriente with three through-hole cores
H2: Código de talla, corresponding to the cable window for 200A model
200: Primary rated current: 200 A
do: Old version suffix; Z is the new replacement model (3CT-H2-200-Z). Electrical parameters are identical, only version revision, reemplazo directo plug-and-play.
- Especificaciones eléctricas básicas
Transformation ratio: 200/5 A
Clase de precisión: Clase 3.0
Rated burden: 1.25 Virginia (Version C) / 5 Virginia (New Version Z)
Frecuencia: 50/60 Hz
Tensión soportada: 1150 V
Short-time thermal stability: 40Ith / 1 segundo
Resistencia de aislamiento: ≥10 MΩ @ 500 En DC
Circuito aplicable: C.A. 600 V motor circuit
Peso: aprox. 580 gramo
- Dimensiones generales
W150 mm × H55 mm × D71 mm
Integral epoxy encapsulation, three circular cable holes; Carril DIN / montaje en panel
Secondary terminals: Q1, K2 (three independent windings for each phase); secondary wire: 1.5~4 mm² flexible cable
- Solicitud & Pareo
✅ Designed exclusively for: EOCR-3DE, FDE, SSD, 3MZ and other digital motor protection relays. It samples three-phase current to implement overload, pérdida de fase, locked rotor and current unbalance protection.
✅ Application scenarios: Three-phase asynchronous motor control cabinets, fans, bombas de agua, compressors and conveyor power circuits.
❌ Not suitable for energy metering (Clase 3 accuracy for protection only, not for measurement).
- Selección de modelo & Reemplazo
New in-stock replacement: 3CT-H2-200-Z, direct replacement for 3CT-H2-200-C
Other models in the same series:
3CT-H1-100-Z: 100/5 A
3CT-HH-150-Z: 150/5 A
3CT-H3-300-Z: 300/5 A
3CT-H4-400-Z: 400/5 A
- Pautas de instalación
- Run the main power cable directly through the three holes; P1 = supply side, P2 = motor side. Polarity reversal will cause phase error and false phase-loss tripping. CT secondary circuit must never be open-circuited.
- Use only identical 3CT models with one relay; do not mix CTs with different transformation ratios.
- Temperatura ambiente: -20 ~ +60 ℃; Altitud máxima: 2000 metro.
- Wiring Instruction for 3CT-H2-200-C (Nuevo modelo: 3CT-H2-200-Z)
Three-phase integrated CT with independent secondary windings for R/S/T phases, secondary output 5 A. Only compatible with EOCR motor protectors; cannot be connected to ordinary ammeters or metering devices.
Definición de terminal
Primary side: Three holes for L1(R), L2(S), L3(t) cables de alimentación
Polarity rule: P1 (fuente de alimentación) → P2 (carga del motor); arrow points toward the load. Reversed polarity leads to phase fault and incorrect phase-loss alarm.
Secondary terminals (3 groups from top to bottom):
R phase: Q1, K2
S phase: Q1, K2
T phase: Q1, K2
Secondary cable: 1.5~4 mm² flexible wire; shielded twisted pair is recommended; cable length ≤ 15 metro.
Cableado estándar (EOCR-3DE / FDE / 3MZ / iFMZ / i3MZ)
- R-phase K1 → EOCR I1; R-phase K2 → common COM terminal
- S-phase K1 → EOCR I2; S-phase K2 → common COM terminal
- T-phase K1 → EOCR I3; T-phase K2 → common COM terminal
✅ All three K2 terminals are tied together to the protector’s current COM; single-point grounding at the COM terminal is recommended.
❌ Never allow secondary open circuit (will cause accuracy drift and insulation breakdown).
Note on mechanical life: El término “vida mecánica” only applies to devices with moving contacts and mechanical structures (contactores, disyuntores, relevos). Current transformers (Connecticut) and voltage transformers (PT) are static components without moving parts. Their service indicators are insulation life, thermal stability and environmental durability only.
Mantenimiento & Ciclo de reemplazo (On-site O&M Reference)
Normal environment (admirador & bomba, clean indoor cabinet): Evaluate replacement after 8~12 years
Ambiente áspero (temperatura alta, polvo, VFD circuits, frequent direct-on-line motor starting): Check insulation and transformation ratio every 5~7 years
After short-circuit heavy current impact: Test or replace immediately. The iron core will suffer hidden performance degradation, resulting in current sampling deviation and false tripping of the protector.
Nota complementaria
New model 3CT-H2-200-Z shares the same mechanical structure, iron core and encapsulation as version C, with identical durability. Only the rated burden is upgraded from 1.25 VA to 5 Virginia, making it more stable for long secondary cables and VFD applications. Mounting holes are fully interchangeable with no cabinet modification required.
- Naming Rule for 3CT-H Series Three-Phase Integrated CT
Formato: 3CT-XX-XXX-Suffix
3Connecticut: Transformador de corriente combinado trifásico (EOCR dedicated)
H1/HH/H2/H3/H4: Código de talla (cable window dimension)
Numeral: Primary current (secondary output 5 A)
Sufijo: C = Old version (interrumpido); Z = New version (active replacement)
Exactitud: Clase 3.0; Secondary output: 5 A; Compatible with all EOCR motor protectors.
- Lista completa de modelos (Old C-version + New Z-version, one-to-one match)
Full Specifications (ascending current rating)
- 3CT-HS-75, Relación: 75/5 A
Viejo: 3CT-HS-75-C (interrumpido)
Nuevo: 3CT-HS-75-Z (en producción)
- 3CT-H1-100, Relación: 100/5 A
Viejo: 3CT-H1-100-C (interrumpido)
Nuevo: 3CT-H1-100-Z (en producción)
- 3CT-HH-150, Relación: 150/5 A
Viejo: 3CT-HH-150-C (interrumpido)
Nuevo: 3CT-HH-150-Z (en producción)
- 3CT-H2-200 (Tu modelo), Relación: 200/5 A
Viejo: 3CT-H2-200-C (interrumpido)
Nuevo: 3CT-H2-200-Z (direct interchange)
- 3CT-H3-300, Relación: 300/5 A
Viejo: 3CT-H3-300-C (interrumpido)
Nuevo: 3CT-H3-300-Z (en producción)
- 3CT-H4-400, Relación: 400/5 A
Viejo: 3CT-H4-400-C (interrumpido)
Nuevo: 3CT-H4-400-Z (en producción)
- Key Differences between C-version & Z-version
Old suffix -C: Rated burden 1.25 Virginia, limited short secondary wiring length
New suffix -Z: Rated burden upgraded to 5 Virginia, better stability for long cables and VFD circuits; mounting footprint fully compatible for drop-in replacement without cabinet changes.
- EOCR Protector Matching Table (Rango actual)
75 A → 3CT-HS-75
100 A → 3CT-H1-100
150 A → 3CT-HH-150
200 A → 3CT-H2-200 (este modelo)
300 A → 3CT-H3-300
400 A → 3CT-H4-400
- Suplementario: Zero-Sequence Split-Core CT in the Same Series
ZCT-035-z, ZCT-050-z, ZCT-080-z, used for earth-fault protection and paired with 3CT series.