Nro. de orden: 2905471
- Desglose del modelo
`FLT-SEC-T1-350/25-P`
FLT: FLASHTRAB surge protection series
SEGUNDO: SEC PLUS pluggable modular SPD platform
T1: Tipo 1 (Clase I) lightning current module; compatible for T1+T2 combined surge protection
350: Maximum continuous operating voltage Uc = 350 V y, suitable for 230/400 V low-voltage distribution systems
25: Iimp (10/350 μs) = 25 el
PAG: Plug-in replaceable module (surge protection cartridge without base)
Protection path: LN / L-PEN (Línea a neutro / Line to PEN)
❗The N-PE path requires an additional module: FLT-SEC-P-T1-N/PE-350/100-P (2905473)
- Key Electrical Specifications
| Parámetro | Clasificación |
| SPD Class | Tipo 1 / Clase I (combinable with T2 modules for T1+T2 coordination) |
| Nominal system voltage Un | 240 V y (Tennesse / sistemas TT) |
| Maximum continuous operating voltage Uc | 350 V y |
| Lightning impulse current Iimp (10/350 µs) | 25 el |
| Nominal discharge current In (8/20 µs) | 25 el |
| Maximum discharge current Imax (8/20 µs) | 50 el |
| Charge transfer Q (10/350) | 12.5 As |
| Specific energy W/R | 160 kJ/Ω |
| Voltage protection level Up | ≤1.5 kV |
| Follow current interrupt capacity Ifi | 25 kA @264 VAC; 3 kA @350 VAC |
| Zero leakage current design | ✅ Suitable for upstream metering installations |
| Indicación de estado | Visual colour window (Green = Normal; Red = Fault) |
- Dimensiones mecánicas & Construcción
Ancho: 35.5 milímetros (2 modules for DIN rail mounting)
Altura: 46.4 milímetros
Profundidad: 59.4 milímetros
Alojamiento: PA6.6-GF flame retardant UL94 V-0, RAL7035 light grey
Instalación: Must be plugged into a dedicated SPD base; direct wiring without base is prohibited
- Important Matching Information
- Requisito de solicitud
Official specification: este tipo 1 module is recommended to be coordinated with VAL-SEC-T2-350-P (Tipo 2 varistor module) to achieve proper energy coordination for T1+T2 combination.
- Reference complete assembled models (unit = base + 4 plug-in modules)
Single-phase 1S system: FLT-SEC-T1+T2-1S-350/25-FM (Base No. 2905466)
3-phase 3S TN-S system: FLT-SEC-T1+T2-3S-350/25-FM (Base No. 2905470)
Internal configuration of complete unit: 3 × FLT-SEC-T1-350/25-P + 1 × FLT-SEC-P-T1-N/PE-350/100-P
- Meaning of suffix FM: The base is equipped with remote signalling contacts (passive dry contact for fault alarm)
- Ámbito de aplicación
Main distribution rooms of buildings, primary surge protection at utility meter inlet (LPZ0→LPZ1 boundary)
230/400 V TN-S, TN-C-S, TT low-voltage AC power grids
Grid connection points of photovoltaic systems, main incoming surge protection for large factories and data centres
Industrial power distribution systems requiring zero leakage current and hot-swappable maintenance
- Model Selection Pitfalls
- Distinguish two similar models
FLT-SEC-T1-350/25-P (2905471, legacy designation)
FLT-SEC-P-T1-350/25-P (2905422, new SEC PLUS designation, parámetros eléctricos idénticos, base compatible)
- Purchasing this model separately only supplies the pluggable cartridge, DIN base excluded; energisation without base is not allowed.
- Additional earthing conditions are required for IT systems; TN wiring schemes cannot be directly adopted.
- If prospective short-circuit current of the system exceeds 3 el (en 350 V operating condition), short-circuit protection fuses must be fitted upstream.
Application Scope of FLT-SEC-T1-350/25-P (Phoenix Type 1 Plug-in SPD Cartridge)
Fundamental specification: Tipo 1 (Clase I) Dispositivo de protección contra sobretensiones, Iimp=25 kA (10/350 μs), Uc=350 V AC, para 230/400 V low-voltage AC systems. Plug-in module requiring matching base; frequently combined with Type 2 SPD for T1+T2 primary & secondary coordinated protection.
- Escenarios de aplicación recomendados
1.1 Low-Voltage Power Distribution for Buildings (LPZ0→LPZ1 Lightning Protection Zone Boundary)
1) Main distribution rooms of commercial & edificios residenciales, main incoming cabinets at utility meter front end for primary surge protection
Applicable for TN-S, TN-C-S distribution systems.
Typical projects: Edificios de oficinas, centros comerciales, hoteles, hospitales, main distribution cabinets of residential communities.
2) Main incoming cabinets of industrial plants, low-voltage side of factory main substations.
1.2 Infrastructure Industry
Tránsito ferroviario: Power distribution rooms, mains incoming protection for signal rooms
Communication base stations, edge data centres, external mains incoming cabinets of IDC computer rooms
Aeropuertos, puertos, low-voltage main power distribution in logistics parks
1.3 AC Side of New Energy Facilities
Low-voltage grid connection cabinets for commercial & industrial photovoltaic power stations (surge protection on 400 V AC incoming side)
⚠ Not applicable for PV DC circuits; special DC SPDs shall be adopted for direct current applications.
Power distribution cabinets at AC output of energy storage PCS units
1.4 Critical Automation & Security Projects
Main power incoming cabinets for DCS and PLC control systems in large factories;
Smart parks, large pump stations, main control power cabinets of wastewater treatment plants.
- Applicable Earthing System Types
✅ Supported: TN-S, TN-C-S 230/400 V 3-phase 5-wire / 3-phase 4-wire systems
✅ TT earthing systems (the N-PE circuit must be equipped with FLT-SEC-P-T1-N/PE-350/100-P neutral SPD)
❌ Not recommended for direct use in IT systems (neutral-less system; technical verification with Contacto Fénix support is mandatory)
- Suitable Lightning Risk Environment
Iimp=25 kA fits the following conditions:
- Buildings located in moderate thunderstorm regions (annual thunderstorm days: 30~60 days)
- Buildings without complete external lightning rods and down conductors with high direct lightning strike risk
- Projects mandatorily requiring Type 1 tested SPDs as specified in national standard GB 50057.
For severe thunderstorm areas (high lightning density zones, isolated factories in open areas), upgrade to the 50 kA Iimp variant.
- Application Advantages Derived from Product Features
- Hot-swappable module replacement
Ideal for facilities that cannot sustain long power outages: Hospitals with critical loads, continuous manufacturing plants, 7×24-hour operating computer rooms. Cartridge can be replaced directly without removing the complete SPD during faults.
- Zero continuous leakage current
Suitable for upstream metering positions (no extra power consumption for electricity meters).
- Optional FM base with remote signalling
Applicable for remotely monitored computer rooms and intelligent projects to transmit SPD fault alarms to upper control systems.
- Unsuitable Application Scenarios (Critical Warnings)
- ❌ DC circuits (PV DC, battery DC, 24 V industrial control DC power supply; mismatch of specifications)
- ❌ Terminal distribution boxes at load side (only Type 2 secondary SPD is required for terminals; Tipo 1 leads to excessive cost and over-specification)
- ❌ Non-standard low-voltage power grids of 110 V or 600 V (Uc=350 V does not match operating voltage)
- ❌ Explosion-hazardous areas (this series has no explosion-proof certification; Phoenix Contact explosion-proof SPD series shall be selected)
- ❌ Sole purchase of cartridges without original base for direct wiring (violates electrical safety specifications)
- ❌ Small buildings and low lightning risk projects where only Type 2 SPD is required per code; Tipo 1 installation is unnecessary.
- Reference Standard Configuration
Standard 3-phase TN-S 400 V main incoming configuration:
3 pcs × FLT-SEC-T1-350/25-P (L1/L2/L3 phases)
+1 pc × FLT-SEC-P-T1-N/PE-350/100-P (N-PE)
Mounted on FLT-SEC series base to form a complete Type 1 protector contra sobretensiones. In engineering practice, Tipo 2 SPDs are generally installed downstream to realise T1+T2 energy coordination.
Dimension Specifications for FLT-SEC-T1-350/25-P (Número de pedido. 2905471)
⚠ Distinction must be made between plug-in cartridge (this single component) and complete assembly (base + módulos). Dimensions shall be differentiated for cabinet layout and panel design.
6.1 Standalone Plug-in SPD Cartridge (FLT-SEC-T1-350/25-P)
- Dimensiones generales (Ancho × Alto × Fondo)
Ancho: 23.5 milímetros
Altura: 46.4 milímetros
Profundidad: 59.4 milímetros
- DIN rail module width: 2 módulos (2 Div.)
- Peso neto: 151.8 gramo
Only replaceable plug-in cartridge. Installation without dedicated base is prohibited.
6.2 Dimensions of Complete Assemblies with Base (Reference for Cabinet Layout)
All bases fit standard 35 carril DIN mm:
1) FLT-SEC-T1+T2-1S-350/25-FM (Single-phase 1S, 2-module base)
W.: 71.2 mm|H: 95.2 mm|D: 74.5 milímetros
2) FLT-SEC-T1+T2-2S-350/25-FM (2-phase 2S, 6-module base)
W.: 106.8 mm|H: 95.2 mm|D: 74.5 milímetros
3) FLT-SEC-T1+T2-3S-350/25-FM (Most commonly used for 3-phase TN-S, 8-module base)
Ancho: 142.4 milímetros
Altura: 95.2 milímetros
Profundidad: 74.5 milímetros
6.3 Cabinet Layout Guidelines
- A full 3-phase TN-S set (3 × FLT-SEC-T1-350/25-P + 1 × FLT-SEC-P-T1-N/PE-350/100-P) installed on an 8-module base occupies a total width of 142.4 milímetros.
- Ingress protection rating: Assembled unit IP20, suitable for indoor installation inside electrical cabinets only.
- Heat dissipation clearance: Maintain minimum 25 mm free space above and below the SPD.
- Terminal cable specification: 2.5~35 mm² solid conductors; tightening torque = 4.5 Nuevo Méjico。
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares






















NH42-63-318x560.png)



