Inovance H1E-1410MR-XP Compact PLC - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Inovance H1E-1410MR-XP Compact PLC - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

Inovance H1E-1410MR-XP Compact PLC

H1E: Inovance economical compact PLC series (upgraded version of H1U, dedicated to simple machinery) 14: 14 digital inputs X0~X13 (CC 24 V, sink/source compatible) 10: 10 relay outputs Y0~Y11 M: Main unit (CPU main body, not E-type expansion module) R: Salida de relé (compatible with AC/DC loads, contact capacity 2A) XP: Enhanced firmware, supports larger program capacity, alta velocidad ...

  • Detalles del producto

H1E: Inovance economical PLC compacto serie (upgraded version of H1U, dedicated to simple machinery)

  1. 14: 14 digital inputs X0~X13 (CC 24 V, sink/source compatible)
  2. 10: 10 relay outputs Y0~Y11
  3. METRO: Main unit (CPU main body, not E-type expansion module)
  4. R: Salida de relé (compatible with AC/DC loads, contact capacity 2A)
  5. XP: Enhanced firmware, supports larger program capacity, high-speed I/O and battery-free RTC clock

Total I/O Points: 24 (14 Entradas + 10 Salidas)

  1. Core Hardware Technical Specifications
ArtículoEspecificación
Fuente de alimentaciónCA 220 V. (L/N/PE terminals)
Input Circuit14-punto DC24V; 8 general-purpose channels, 2 channels of 60kHz high-speed counter, 4 channels of 10kHz high-speed input
Output Circuit10 relevos, max 2A per channel, resistive load AC220V/DC24V; No high-speed pulse output (only available on MT model)
Program Capacity16K steps, no memory card required
Data Registers8K-word D registers, data permanently retained after power failure
RTC Real-Time ClockIncorporado, ≥7 days power-off retention, no backup battery needed
Interfaces de comunicación1. Round MD8 programming port (RS422, for touch screen connection & program download)
2. Terminal RS485 (Modbus RTU master/slave)
3. Front Mini USB port (program download & online monitoring)
Capacidad de expansiónSupports CANLink bus for I/O modules and analog BD boards; máximo 32 remote expansion modules
High-Speed Functions2 channels of 60kHz quadrature counting, pulse capture, interrupt input; No pulse output (transistor model H1E-1410MT-XP supports 3-axis 100K pulse control)
Dimensiones generales93×90×75mm (Ancho×Alto×Profundidad)
Método de montajeDIN35 rail mounting
Clase de protecciónIP20 (for cabinet installation only)
Instruction Execution Speed250ns per logic instruction, 8μs for floating-point operation

III. Interfaz & Indicator Definition

  1. Front Panel Indicators

PWR: Green power light, steady on when powered up

CORRER: Green run light, steady on during program execution

ERR: Red fault light, lights up for program errors or hardware abnormalities

  1. Port Zones

Upper terminals: L/N power supply, S/S input common terminal, X0~X13 input points

Lower terminals: COM0~COM4 output common terminals, Y0~Y11 relay outputs

Right side: MD8 programming port, RS485 (DA+/DB-), USB download port

  1. Comparación de modelos & Selection Table for Same Series
ModeloEntradasTipo de salidaSalida de pulsoEscenarios de aplicación
H1E-1410MR-XP14 CC 24 VReléNingunoVálvulas solenoides, contactores, luces indicadoras, general digital equipment
H1E-1410MT-XP14 CC 24 VNPN Transistor3-axis 100K pulseStepper/servo positioning, pulse-controlled equipment
H1E-0806MR-XP8 En / 6 OutReléNingunoSimple control for small standalone machines
H1E-1614MR-XP16 En / 14 OutReléNingunoMulti-I/O assembly lines, conveying equipment
  1. Core Product Advantages
  2. High versatility of relay outputs: Directly drives AC220V solenoid valves and contactors without intermediate relays;
  3. Battery-free clock: RTC maintains time after power loss, eliminating battery replacement maintenance;
  4. Triple multiplexed communication: USB local download, RS422 touch screen connection, RS485 networking for inverters/instruments;
  5. Large program capacity: 16K steps to cover logic, recipe and alarm functions for medium & equipo pequeño;
  6. Supports Modbus RTU and CANLink networking, compatible with Inovance inverters, servos and IT-series touch screens;
  7. Program encryption function to protect intellectual property of equipment control logic.
  8. Escenarios de aplicación típicos

Pequeñas máquinas de embalaje, transportadores, assembly line sorting equipment

climatización & water treatment small control cabinets

Injection molding auxiliary machines, small stamping equipment, automated tooling fixtures

Admirador & bomba de agua, valve digital control (no positioning requirement)

VII. Instalación & Especificaciones de cableado

  1. Mandatory Installation Safety Requirements

Power supply AC220V, distinguish L/N terminals with reliable PE grounding;

Input S/S terminal connected to DC24V positive pole, X terminals connected to sensor negative pole (sink mode); source mode wiring is switchable;

Relay output COM terminals connected to AC220V or DC24V as required; single-channel load shall not exceed 2A;

Install 120Ω terminal resistors at both ends of RS485 bus; shielded cable single-point grounding.

  1. Strictly Forbidden Operations
  2. Directly drive high-power motors via relay outputs (risk of contact burnout);
  3. Route RS485 cables together with power cables without shielding;
  4. Plug/unplug MD8 programming port and USB port while powered on;
  5. Exceed the maximum limit of 32 módulos de expansión, causing bus communication lag.

VIII. Common Fault Troubleshooting Matrix

Fenómeno de fallaCausa principalSolución
Steady red ERR lightProgram error, I/O short circuit, expansion bus faultClear program, check output short circuit, power off and reinsert expansion modules
RUN light offNo valid user program, PLC in STOP modeRe-download program, switch to RUN mode
RS485 communication failureReversed A/B wiring, missing terminal resistor, slave address conflictSwap DA/DB wires, install 120惟 resistors at both bus ends, modify slave address
No signal on input X pointsS/S terminal without 24V supply, broken sensor cableCheck power supply for input common terminal, replace sensor wiring
No output from relay Y terminalsNo power supply on COM terminals, burned contactsMeasure voltage of COM circuit, replace PLC output point
  1. Alternative Model Instructions
  2. Same-spec replacement: H1U-1410MR-XP (old model with identical functions; H1E is preferred as the old model is discontinued);
  3. For positioning equipment: H1E-1410MT-XP (transistor pulse output model);
  4. More I/O points: H1E-1614MR-XP (16 entradas + 14 salidas);
  5. Higher performance upgrade: H2U/H3U series (supports EtherCAT and multi-axis motion control).

Full Application Overview of Inovance H1E-1410MR-XP PLC

This 24-point economical relay-output compact PLC has no pulse output, built-in RS485 Modbus and battery-free RTC clock. It is suitable for medium & small standalone equipment requiring only digital logic and networking with instruments/inverters without servo positioning. Its relay contacts can directly drive AC220V solenoid valves and contactors, featuring low cost and easy maintenance.

  1. Industria de maquinaria de embalaje (Most Widely Used)
  2. Small vertical packaging machines, simple powder/granule sealing machines
  3. Express label applicators, simple material distribution conveyors
  4. Small pillow packaging auxiliary machines, automatic silo feeding mechanisms
  5. Carton strapping machines, simple box sealers

Applicable logic: Photoelectric counting, sequential cylinder actions, conveyor start/stop, alarm indicator lights, timing delay, output statistics (RTC clock records shift output); matched with Inovance inverters for conveyor speed regulation, frequency read/write via RS485.

  1. Transmitir & Assembly Line Equipment
  2. Small belt conveyors, roller sorting lines, lifting transfer tables
  3. Material blocking, diverting and reversing mechanisms on production lines
  4. Small warehouse stockers, simple loading/unloading tooling

Applicable logic: Photoelectric sensor start/stop, multi-stage delay logic, emergency fault stop, audible & visual alarms, manual/automatic mode switch; multiple PLCs linked via RS485 networking.

III. climatización, aficionados, Bombas de agua & Water Treatment Small Control Cabinets

  1. Workshop circulating fans, ventiladores de escape, cooling tower pump control
  2. Small water purifiers, pure water machines, circulating water dosing devices
  3. Simple control of central air conditioning terminal air handlers and fresh air units

Applicable logic: Temperature/liquid level switch interlock, timed start/stop (built-in RTC schedule), protección contra sobrecarga, alarma de falla; RS485 connection to temperature instruments and pressure transmitters.

  1. Moldeo por inyección & Rubber Plastic Auxiliary Equipment
  2. Simple control of injection molding hopper dryers and mold temperature controllers
  3. Small pelletizers, shredders, feeding suction machines
  4. Simple winding and feeding auxiliary mechanisms for extruders

Applicable logic: High/low material level detection, heating timing, fan interlock, overload shutdown; relay outputs directly control heating contactors and fans.

  1. Hardware, Stamping & Automated Tooling Fixtures
  2. Small pneumatic tooling fixtures, pressing jigs, riveting machines
  3. Simple stamping feeding, material positioning and clamping mechanisms
  4. Small grinding and polishing standalone automation

Applicable logic: Two-hand safety start, staged cylinder clamping & releasing, position detection, counting, overtime fault alarm; pure digital logic without high-speed positioning.

  1. Agricultural & Environmental Protection Equipment
  2. Greenhouse ventilation fans, simple irrigation control cabinets for water & fertilizer integration
  3. Small waste compactors, dust removal fan control cabinets
  4. Fish pond water circulation and aerator timing control

Applicable logic: Timed start/stop, high/low liquid level interlock, grouped control of multi-way solenoid valves, water shortage/overload alarm.

VII. carpintería & Stone Small Processing Auxiliary Machines

  1. Feeding mechanisms for small sliding table saws, sanding machine conveying systems
  2. Simple stone cutting feeding and dust removal interlock equipment

Applicable logic: Conveyor start/stop, synchronous dust fan startup, safety door interlock, output counting.

VIII. Small Standalone Food Processing Equipment

  1. Small dough mixers, mixing tanks, simple cleaning machines
  2. Fruit & vegetable sorting conveyors, small drying lines

Applicable logic: Timed stirring, cleaning spray sequence control, temperature switch protection, automatic shutdown.

  1. General Non-Standard Simple Automation Equipment
  2. Auxiliary material weighing & sorting equipment, small test jigs
  3. Pneumatic tooling for door & window processing, small screw locking machines (servo-free version)
  4. Small elevator hall call control cabinets, simple cargo lift door logic control
  5. Small parking lot barrier gates, simple lifting bollard control

Unsuitable Application Scenarios for This Model

  1. Equipment requiring stepper/servo positioning and multi-axis pulse control (select H1E-1410MT-XP transistor model);
  2. Large-scale production lines and multi-axis synchronous motion control (upgrade to H3U/H5U series);
  3. Heavy analog signal acquisition (requires additional analog BD expansion boards);
  4. High-frequency pulse counting and high-speed synchronous control.

Matching Scenarios for Core Selection Advantages

  1. Salida de relé: Equipment with large quantities of AC220V solenoid valves and contactors, no intermediate relays required;
  2. Built-in RTC clock: Equipment needing timing control, shift output recording and scheduled start/stop (climatización, agriculture, embalaje);
  3. RS485 Modbus RTU: Complete sets of equipment connected to inverters, temperature controllers and weighing instruments;
  4. 24 small I/O points: Small standalone machines with limited I/O points and cost-sensitive demands;
  5. Battery-free clock: Equipment with long-term non-stop operation to reduce battery replacement maintenance.

Anterior:

Próximo:

Deja una respuesta