Marca: LS Electrico | Producto: LA63N Series MCB
Descripción del modelo:
LA63N: código de serie, 6kA capacidad de corte
4PAG: 4-polo (3 fases + Neutral, 4 connection poles)
D10: D-curve trip, rated current In=10A
✅ Core Technical Data
| Artículo | Especificación |
| Modelo | LA63N 4P D10 |
| Corriente nominal en | 10A |
| Curva de viaje | tipo D: Instantaneous trip at 10~16In. Suitable for motors, transformers and inductive loads to avoid tripping on inrush current |
| Tensión operativa nominal Ue | CA 400 V (3-fase); DC 125V |
| Rated Short-circuit Breaking Capacity Icn | 6el (IEC60898) |
| polacos | 4PAG (L1/L2/L3+N, simultaneous pole disconnection) |
| Montaje | 35mm montaje en carril DIN |
| Clase de protección | IP20 (front face) |
| Estándares | IEC60898-1, GB/T10963.1 |
| Resistencia mecánica | 20,000 operaciones; Resistencia eléctrica: 10,000 operaciones |
| Temperatura ambiente | -5℃ ~ +40℃ |
📌 Aplicación
4P MCB with D-curve, for power circuits: 3-phase motors, inversor aporte, transformadores, solenoid valves and inductive load distribution. It protects 3 phases and neutral line simultaneously and prevents nuisance tripping caused by high starting inrush current. Not suitable for general lighting (C-curve preferred for lighting).
🧩 Equivalent Replacement Models
- Legacy LS model: BKN-4P D10 (LA63N is upgraded version of BKN)
- Alternativas domésticas: CHINT NB63-4P D10, Delixi DZ47s 4P D10
- Alternativas importadas: Schneider iC65N 4P D10, ABB S204M D10
⚠️ Selección & Notas de instalación
- D trip characteristic: Instantaneous trip at 10~16 times rated current, immune to motor starting inrush; curva C: 5~ 10 pulgadas; B-curve: 3~5In.
- 4P feature: Neutral line disconnects together with phase conductors for safe maintenance; 3P+N is available if neutral disconnection is not required.
- Capacidad de ruptura 6kA: Sufficient for factory end cabinets and small power panels; upgrade to LA63H (10el) when short-circuit current exceeds 6kA.
- No residual current protection. If earth leakage protection is needed, select LA63N series RCBO.
📦 Customs HS Code Reference
8536200000 (Bajo voltaje cortacircuitos, rated voltage ≤1000V)
🛠️ Solución de problemas
Viajes inmediatamente después del cierre: Cortocircuito / load earth fault
Trips when motor starts: Verify wrong C-curve selection or excessive line voltage drop
Viajes después de correr por un período: Sobrecarga, check if continuous load current >10A
Can Schneider MCB E9CN-4P-C16 directly replace LA63N-4P-D10?
Conclusión: Direct replacement is NOT allowed
Although the DIN rail dimension, pole count and breaking capacity allow physical fitting, rated current and trip curve are inconsistent, leading to mismatched protection characteristics.
Comparación de parámetros
| Artículo | ¿LA63N-4P-D10? (Original) | Schneider E9CN-4P-C16 (Candidate) | Riesgo |
| Corriente nominal en | 10A | 16A | Overload protection threshold increased, cable loses protection. The original circuit cable is sized for 10A. Replaced with 16A, cable may overheat without breaker tripping, peligro de incendio |
| Curva de viaje | tipo D: Instant trip 10~16In (100~160A) | tipo C: Instant trip 5~10In (80~160A) | Original for motor/inductive load. D-curve avoids starting inrush; C-curve tends to nuisance trip during motor startup |
| polacos | 4PAG | 4PAG | ✅ Matched, all poles disconnect together |
| Icn de rotura de cortocircuito nominal | 6el | 6el | ✅ Matched |
| Dimensión | 4PAG,72milímetros, Carril DIN35 | 4PAG,72milímetros, Carril DIN35 | ✅ Montable físicamente |
Dos opciones de reemplazo
✅ Opción 1: Reemplazo totalmente equivalente (Recomendado, protección sin cambios)
parte de schneider: E9CN-4P-D10
En=10A, viaje, 4PAG,6el; La protección eléctrica coincide completamente con LA63N-4P-D10 para intercambio directo..
⚠️ Opción2: Si se debe utilizar E9CN-4P-C16 (Rara vez aceptable)
Todas las condiciones siguientes deben cumplirse:
- Corriente de funcionamiento continuo de carga ≤10A
- Clasificación de cable y terminal revisada nuevamente para 16A
- La carga NO es un motor directo en línea / transformador o carga inductiva de alta irrupción (de lo contrario, se dispara al iniciar)
- Dibujos, calendario de protección y certificados de prueba actualizados y reaprobados
No recomendado para circuitos de energía industriales..
Notas adicionales
- La curva de sobrecarga térmica es idéntica para los tipos C y D.. La única diferencia radica en el disparo instantáneo por cortocircuito magnético..
- La capacidad de la terminal es similar, compatible con cableado de arriba hacia abajo.
- Mismo código SA: 8536200000.
Cómo identificar el tipo de carga para una selección adecuada de MCB
Flujo de trabajo principal: Clasificar el tipo de carga → Determinar la corriente de funcionamiento continua → Seleccionar la curva de disparo (B/C/D) → Elija la corriente nominal In → Verifique el poder de corte en cortocircuito Icn → Seleccione el número de polos
- Identificar el tipo de carga & Curva de viaje correspondiente
La protección contra sobrecarga térmica es idéntica para B/C/D; La diferencia es el disparo magnético instantáneo por cortocircuito/corriente de irrupción..
| Tipo de viaje | Rango de disparo magnético instantáneo | Aplicaciones típicas | Observaciones |
| tipo B | 3~5 pulgadas | Electrónica de bajo voltaje, dispositivos de precisión, pequeños circuitos de CC, bucles de sensores | Altamente sensible al cortocircuito; rara vez se utiliza para alimentación de CA industrial |
| tipo C | 5~10 pulgadas | Iluminación, tomas de corriente, cargas resistivas, pequeños fans, fuente de alimentación general del gabinete | Más común para distribución comercial/ordinaria.; carga de irrupción baja |
| tipo D | 10~16 pulgadas | Motores directos en línea, transformadores, válvulas solenoides, bancos de capacitores, cargas inductivas | Withstand high starting inrush and prevent nuisance tripping |
Quick reference:
Cargas resistivas (calentadores, lámparas incandescentes) → C-curve
Inductive loads with high inrush (motores, transformadores) → D-curve
Precision low-power DC/electronic circuits → B-curve
- Calculate Load Current and Select MCB Rated Current In
1) Carga resistiva (Calentador, Resistor) Monofásico
Simplified estimation for 380V 3-phase motor: ~2A per kW
Ejemplo: 3kW 3-phase motor, rated current≈6A; starting current ~6~8×In → D-curve selected.
Selection rule: MCB rated current ≥ motor rated current and withstand starting inrush.
Nota: MCB mainly provides short-circuit protection. Motor overload shall be protected separately by thermal relay. MCB is NOT intended as primary overload protection for motors.
Margin Rule
Continuous duty load: En ≥ 1.1 × continuous load current
Intermittent load: In ≥ continuous load current
❌ Never arbitrarily increase In: La ampacidad del cable debe coincidir con la clasificación del MCB. De lo contrario, el cable se quema sin que se dispare el disyuntor..
- Seleccionar recuento de polos
1PAG: Sólo fase de protección, conexión permanente neutral; para iluminación
1P+N: Fase y neutro conectados al disyuntor, fase protegida solamente; circuitos de enchufe
2PAG: Fase + neutro ambos protegidos, desconexión simultánea; equipo monofásico
3PAG: 3-fase 3 hilos, desconectar tres fases; 3-phase motors
3P+N: 3 fases + neutral, neutro no desconectado; distribución trifásica equilibrada
4PAG: 3 fases + neutral, el neutro se desconecta juntos; sistema TN-S, aislamiento total para mantenimiento, Entrada de UPS y inversor trifásico
LS LA63N-4P-D10 arriba: 4-polo, desconexión sincronizada del neutro.
- Capacidad de corte en cortocircuito Icn (A menudo se pasa por alto)
icn: Corriente máxima de cortocircuito que el disyuntor puede interrumpir de forma segura.
Gabinete final / distribución ordinaria de taller: 6el (LS LA63N, Schneider E9CN son 6kA) suficiente
Cerca de un transformador o panel principal con alta posible corriente de cortocircuito: Seleccione 10kA,15El modelo de kA.
Si la corriente de cortocircuito real MCB Icn: Breaker may fail and explode during short circuit, cannot cut fault.
- On-site Checklist for Load Identification
✅ Check equipment nameplate:
- Resistive or coil/motor/transformer load
- Tensión nominal, corriente nominal, potencia nominal
- Starting method: DOL / Estrella-triángulo / arrancador suave
DOL motor has maximum inrush → D-curve; soft starter reduces inrush, C-curve acceptable in some cases
✅ Field judgment:
Obvious hump and current surge at power-on → High-inrush inductive load → D-curve
Smooth startup without current spike → Resistive / general power supply → C-curve
- Common Pitfall Case (Matching previous model comparison)
Original circuit: ¿LA63N-4P-D10? (10A D-curve)
Carga: Small DOL 3-phase motor
If replaced with Schneider E9CN-4P-C16:
- In rises from10A→16A: Overload protection threshold increased, original cable loses overload protection
- C-curve magnetic trip at5~10In: La irrupción de arranque del motor puede caer en el rango de disparo instantáneo → Disparo inmediatamente al arrancar
- Procedimiento completo de selección de MCB
- Identificar el tipo de carga: Resistador / Inductivo (Motor/Transformador) / Electrónico
- Lea la potencia/corriente de la placa de identificación y calcule la corriente de funcionamiento continua
- Seleccione la curva de disparo B/C/D según la característica de irrupción
- Elija MCB clasificado en y verifique la ampacidad del cable correspondiente
- Calcule la posible corriente de cortocircuito en el punto de instalación y seleccione Icn
- Seleccione el número de postes según el sistema de distribución. (TN-S/TN-C) y requisitos de mantenimiento
- Comprobación de reducción de potencia: Temperatura ambiente y reducción de potencia para disyuntores montados densamente en gabinetes
Factores a considerar para la selección de polos MCB
Concepto central: El recuento de polos define qué conductores están conmutados y protegidos.. La selección deberá considerar el tipo de sistema de distribución., tipo de carga, seguridad de mantenimiento, Requisitos de protección y corriente de falla del neutro..
Postes disponibles:1PAG,1P+N,2PAG,3PAG,3P+N,4PAG
- Tipo de sistema de distribución (TN-C / TN-S / TN-C-S)
Criterio primario, Determina si la línea neutral se puede desconectar..
TN-C (PEN combinado): El conductor PEN NO debe desconectarse. NO utilice 2P/4P con conmutación neutral; PEN permanece continuo.
TN-S / TN-C-S (Separar N y PE): El neutro es independiente.. Decida si desea cambiar a neutral según los requisitos.
Si el neutro puede transportar sobretensión/corriente de falla y se requiere aislamiento total durante el mantenimiento → 4P (3-fase)/2PAG(monofásico)
Carga trifásica equilibrada con corriente neutra insignificante, Desconexión del neutro innecesaria →3P+N (El neutro pasa sin conmutar.)
- Carga Monofásica o Trifásica
Carga monofásica: 1PAG,1P+N,2PAG
1PAG: Sólo conductor de fase desconectado, El neutro permanece conectado.. Riesgo: El neutro puede energizarse si el neutro aguas arriba se rompe; principalmente para iluminación.
1P+N: Fase y neutro conectados al disyuntor, solo la fase tiene protección, Neutro sin protección contra sobrecarga/cortocircuito, los polos se abren simultáneamente.
2PAG: Tanto la fase como el neutro están protegidos y conmutados juntos.; preferido para enchufes y equipos monofásicos que requieren aislamiento total.
Carga trifásica:3PAG,3P+N,4PAG
3PAG: Proteja y desconecte conductores trifásicos únicamente.; Motores trifásicos equilibrados sin neutro..
3P+N: 3 fases protegidas, neutro conectado al disyuntor pero el neutro no tiene protección contra sobrecarga/cortocircuito, pueden cambiar juntos o pasar a través; para carga trifásica desequilibrada.
4PAG: L1/L2/L3+N todos protegidos, Desconexión de fase y neutro simultáneamente.. LS LA63N-4P pertenece a este tipo.
- Seguridad de mantenimiento (Crítico)
Se requiere aislamiento total: Todos los conductores desenergizados después de que el disyuntor se apague. Monofásico →2P; Trifásico →4P.
Ejemplo: Entrada del inversor, Unión Postal Universal, alimentación principal del gabinete de control. 4P Se requiere desconexión total de polos antes de abrir el gabinete para servicio..
Motor extremo ordinario sin neutro: Sólo tres fases necesitan aislamiento para mantenimiento; 3P es suficiente.
⚠️ Advertencia: 1El disyuntor P deja el neutro conectado al sistema aguas arriba. Si el neutro aguas arriba está roto, el equipo puede energizarse. 1P no se recomienda para acceso de mantenimiento.
- Sobrecarga neutral, Cortocircuito y corriente armónica
Carga trifásica desequilibrada, gran cantidad de VFD / fuente de alimentación conmutada: Corriente armónica intensa fluye por el neutro, neutral puede sobrecargar.
✅ El conductor neutro requiere protección → 4P MCB.
Carga de motor trifásico puro equilibrado, corriente neutra casi nula: 3P suficiente, no hay necesidad de 4P.
Escenario típico: Armario de control con muchos PLC., fuentes de alimentación CC. La suma del tercer armónico hace que la corriente del neutro sea incluso mayor que la corriente de fase → Se requieren 4P para proteger el neutro.
- Compatibilidad con protección diferencial (RCBO / MCB+ELM)
La detección de corriente residual requiere detectar todas las corrientes entrantes y salientes, incluido el neutro..
RCBO monofásico: Generalmente 1P+N o 2P
3-fuga a tierra de fase: 3P+N/4P. El neutro debe pasar por CT, de lo contrario falla la protección contra fugas.
Si se planea un módulo de fugas, La configuración del polo debe incluir un cable neutro..
- Sobretensión del sistema & Requisito de aislamiento
Riesgo de sobretensión, voltaje inverso, circuito de transferencia de potencia dual: Desconexión total de polos (2P/4P) Recomendado para evitar la retroalimentación de voltaje a través del neutro y daños al equipo aguas abajo..
Circuito eléctrico ordinario sin especial riesgo de sobretensión.: 3P aceptable.
- Costo y espacio del gabinete
Un mayor número de polos ocupa más espacio en el carril DIN:
3PAG:54milímetros; 3P+N:72milímetros;4PAG:72milímetros
Clasificación de costos:4P>3P+N>3P. 3Se prefiere P/3P+N para ahorrar espacio cuando la protección neutral no es necesaria.
- Distinguir 3P+N vs 4P (Más confuso para circuitos trifásicos)
| Tipo | Protección de fase | Protección neutra | Conmutación neutral | Solicitud |
| 3PAG | L1/L2/L3 protegido | Sin neutral | Sin neutral | Motor trifásico puro sin neutro |
| 3P+N | L1/L2/L3 protegido | Neutro sin protección contra sobrecarga/cortocircuito | Interruptores neutros junto con polos. | Carga trifásica desequilibrada, armónico bajo, neutral sin riesgo de sobrecarga |
| 4PAG | L1/L2/L3 todos protegidos | Neutro con sobrecarga & protección contra cortocircuitos | Fase + neutral abierto juntos | Alto armónico, riesgo de sobrecarga neutral, aislamiento total para mantenimiento, entrada inversor/UPS |
¿LA63N-4P-D10?: 4PAG, Neutro protegido y totalmente conmutado., Adecuado para entrada de inversor y circuitos trifásicos con neutro que requieren aislamiento de mantenimiento..
✅ Lista de verificación de selección rápida de polos
- Carga monofásica o trifásica?
- Sistema de distribución TN-C / TN-S? ¿Se permite la desconexión del neutro??
- Presente neutro? armónico pesado / corriente neutra desequilibrada? Se requiere protección neutra?
- Se requiere aislamiento total durante el mantenimiento?
- Accesorio de fuga a tierra previsto? (El neutro debe pasar por CT)
- Evaluación de espacio y costos.
Referencia de aplicación típica
- 3-motor de inducción de fase sin neutro: 3P MCB Curva D
- Alimentación principal del gabinete de control con muchas fuentes de alimentación conmutadas., alto armónico, apertura del gabinete para mantenimiento: 4MCB
- Iluminación ordinaria trifásica, carga desequilibrada con armónicos bajos:3Curva C P+N
- Circuito de toma monofásica:2P Curva C / RCBO 1P+N