The C120N belongs to the Acti9 series high-current disyuntor miniatura (MCB). It is an upgraded high-current variant of the standard C65N, with a maximum rated current of 125A and isolation function. Widely used for power distribution in industrial and building terminals, as well as outgoing circuits in power cabinets.
- Definición del modelo
C120: Serie de productos, high-current MCB (63~125A)
norte: Clase de capacidad de ruptura, Icn=10kA @ 400V AC
125A: Rated working current In=125A (reference temperature: 30℃)
Full model requires additional [número de polo + curva de disparo]
curva C: Instantaneous tripping at 5~10In, para distribución general de energía, lighting and resistive loads (Número de pieza. A9N18359 / A9N18363 / A9N18369)
D-curve: Instantaneous tripping at 10~14In, for loads with inrush current such as motors and transformers (Número de pieza. A9N18389)
- Especificaciones eléctricas básicas
| Artículo | Parámetro |
| Corriente nominal en | 125A (a 30 ℃) |
| Tensión de funcionamiento UE | AC 230/400V |
| Tensión nominal de aislamiento Ui | 500V |
| Rated short-circuit breaking capacity Icn | 10el (IEC60898-1) |
| Poder nominal final de corte en cortocircuito Icu | 10kA @400V (IEC60947-2) |
| Tipo de disparo | do / D optional |
| Función de protección | Thermal overload trip + magnetic short-circuit trip, con función de aislamiento (green contact indicator) |
| Resistencia mecánica | 20,000 operaciones |
| Resistencia eléctrica | 5,000 operaciones (range 80~125A) |
| Método de montaje | 35mm montaje en carril DIN |
| Clase de protección | IP20 (lado terminal) |
| Temperatura ambiente de funcionamiento | -25℃ ~ +70℃ |
- Especificaciones de cableado
Solid copper cable: máx.. 50mm²
Flexible copper cable: máx.. 35mm²
Optional aluminum terminal: For 16~50mm² aluminum cables
- Escenarios de aplicación
- High-current outgoing circuits in factory buildings, computer rooms and building distribution cabinets
- Main power incoming, fan and water pump circuits (D-curve recommended)
- Alternative to small-frame moulded case circuit breakers to save cabinet space
Accesorios opcionales: Vigi C120 residual current module, contacto auxiliar, fault alarm contact, liberación de derivación
- Directrices de selección & Alternative Products
Notas de selección
- Derating is required when ambient temperature exceeds 30℃;
- D-curve is preferred for motor loads; C-curve for general distribution;
- C120N with 10kA breaking capacity; select C120H (15el) / C120L (25el) for circuits with higher short-circuit current.
Alternativas nacionales
chint: NM1-125 compact MCCB / NB1-125 MCB
Delicioso: CDB2 125 series miniature circuit breaker
- Solución de problemas comunes
- Viajes inmediatamente después del cierre: Short circuit on downstream side, check cable insulation and load earth fault;
- Trips after period of loaded operation: Sobrecarga, actual load exceeds 125A, or high ambient temperature causes derating;
- no se puede cerrar, handle stuck: Damaged internal mechanism, or Vigi residual current module triggered;
- Green indicator does not appear: Main contacts are not fully disconnected. Maintenance on downstream circuits is prohibited.
- Referencia del código HS
85362000 Low-voltage circuit breaker (for customs declaration reference only, subject to customs verification)
Schneider Acti9 C120N 125A Product Manual (Compiled from Original Datasheet)
Serie: Acti9 C120N High-current Miniature Circuit Breaker (MCB)
Corriente nominal: 125A (reference at 30℃)
Capacidad de ruptura: Icn=10kA @400V AC
Reference part numbers:
2P C-curve: A9N18363
3P C-curve: A9N18369
4P C-curve: A9N18376
3P D-curve: A9N18389
The C120N is part of Schneider Acti9 high-current MCB family covering 63~125A. It features isolation function. The green contact indicator provides direct visual confirmation that main contacts are open, meeting maintenance safety requirements. It provides thermal-magnetic protection against overload and short-circuit for high-current power distribution in industrial and building distribution cabinets. Compatible with add-on accessories including Vigi C120 residual current module, contactos auxiliares, alarm contacts and shunt releases.
Estándares: GB10963.1, IEC/EN60898-1, IEC/EN60947-2; CCC, certificado CE
- Especificaciones eléctricas
| Artículo | Parámetro |
| Corriente nominal en | 125A (reference ambient temperature:30℃) |
| Tensión nominal de funcionamiento Ue | AC 230/400V; máximo. 440V y |
| Tensión nominal de aislamiento Ui | 500V |
| Tensión nominal soportada al impulso Uimp | 6kV |
| Poder nominal final de corte en cortocircuito Icu | 10kA @400V AC |
| Capacidad nominal de corte en cortocircuito de servicio Ics | 75% of Icu =7.5kA |
| Rated short-circuit breaking capacity Icn | 10el (IEC60898-1) |
| Tipo de disparo | curva C: 5~10In instantaneous magnetic trip; D-curve:10~14In instantaneous magnetic trip |
| Principio de protección | Thermal trip (sobrecarga) + viaje magnético (cortocircuito) |
| Resistencia mecánica | 20,000 operaciones |
| Resistencia eléctrica | 5,000 operaciones (range 80~125A) |
| Current limiting class | Clase 3 |
| Función de aislamiento | ✅ Available, green indicator for contact open status |
- Mecánico & Especificaciones de cableado
- Montaje: 35carril DIN estándar mm, tipo de complemento, mountable in any orientation
- Clase de protección: IP20 (front terminals)
- Capacidad de cableado
Solid copper cable: Max.50mm²
Flexible copper cable (with cable lug): Max.35mm²
Optional aluminum terminals: For 16~50mm² aluminum cables
- Par de apriete: 3.5 Nuevo Méjico
- Dimensiones generales (18mm por polo)
2PAG: 36mm de ancho; 3PAG: 54mm de ancho; 4PAG:72mm de ancho
- Entorno operativo
Temperatura ambiente: -25℃ ~ +70℃; derating required above 30℃
Temperatura de almacenamiento: -40℃~+85℃
Altitud: No derating ≤2000m; reducción de potencia requerida por encima de 2000 m
Humedad relativa: 5~95%, sin condensación
- Características de disparo
- Thermal overload trip (tiempo inverso)
1.13En: No tripping within 1h (estado frio)
1.45En: Tripping within 1h
- Magnetic instantaneous trip
curva C:5~ 10 pulgadas, distribución de energía, iluminación, cargas resistivas
D-curve:10~14In, motores, transformadores, capacitor loads with inrush current
- Accesorios opcionales
- Vigí C120: Add-on residual current protection module, forms RCD+MCB combination
- OF Auxiliary contact: Circuit ON/OFF status signal
- SD Fault alarm contact: Tripping signal for short-circuit / sobrecarga
- MX Shunt release: Remote electrical trip
- MN Undervoltage release: Loss-of-voltage protection
- barra colectora: Comb-type busbar for multi-pole parallel incoming connection
- Instalación & Notas de operación
- Reducción de potencia: Derate rated current when ambient temperature >30℃. Derating also required for multiple devices installed side by side inside enclosed cabinets.
- Isolation verification: When handle is set to OFF position, the green indicator visible confirms main contacts are fully open before downstream maintenance. Handle position alone cannot be used as isolation confirmation.
- Alambrado: Top-in or bottom-in wiring is acceptable. Cable lugs are recommended. Tightening torque 3.5N·m to prevent overheating.
- Model differentiation
C120N:10el; C120H:15el; C120L:25el. Select H/L version for circuits with high short-circuit current.
- Solución de problemas
- Viajes inmediatamente después del cierre: Short circuit or earth fault on downstream side. Test breaker separately after disconnecting load to verify breaker integrity.
- Trips after loaded operation: Actual load exceeds rated current, or high ambient temperature causes derating.
- no se puede cerrar, handle stuck: Damaged mechanism or locked residual current module.
- Overheating when closed: Insufficient terminal torque, undersized cable, oxidized terminals.
- Model Selection Table (C120N 125A)
| Polo | Curva de disparo | Número de pieza |
| 2PAG | do | A9N18363 |
| 3PAG | do | A9N18369 |
| 4PAG | do | A9N18376 |
| 3PAG | D | A9N18389 |
Schneider Acti9 C120N 125A Overall & Dimensiones de montaje (Original Datasheet)
Referencia: Height H=81mm, Depth D=73mm, height and depth are consistent for all pole types; width varies with pole count
Carril de montaje: 35mm standard symmetrical DIN rail, snap-in installation
| Polo | Ancho × Alto × Fondo | DIN module (9mm/unit) | Peso neto |
| 1PAG | 27 × 81 × 73 milímetros | 3 unidades | 0.205 kilos |
| 2PAG | 54 × 81 × 73 milímetros | 6 unidades | 0.410 kilos |
| 3PAG | 81 × 81 × 73 milímetros | 9 unidades | 0.615 kilos |
| 4PAG | 108 × 81 × 73 milímetros | 12 unidades | 0.820 kilos |
Common model: 3P C120N 125A (A9N18369): 81(W.) × 81(h) ×73(D) milímetros
Related Mounting Dimensions
- Cable stripping length: 15 milímetros
- Par de apriete de terminales: 3.5 Nuevo Méjico
- Max terminal wiring: Solid wire 50mm² / Flexible wire 35mm²
- Cabinet clearance: ≥20mm wiring space reserved at top and bottom terminals; keep heat dissipation gap for side-by-side installation at high temperature (reducción de potencia)
Notas complementarias
Depth 73mm: Total depth from DIN rail backplate to front handle of breaker body; cabinet door cutout needs clearance allowance
Height 81mm: Overall vertical height of device body, excluding cable bending allowance
If Vigi C120 residual current module is fitted, overall depth increases, refer to separate accessory datasheet for dimension