Tipo de producto: SIRIUS 3RV2 series frame S2 disyuntor de protección del motor (protector de motor), active production model, hecho en alemania
- Explicación del código del modelo
3RV 2 0 31 4 K A 10
3RV: SIRIUS motor protection circuit breaker
2: 2nd generation of 3RV2 series
0: Versión estándar, no pre-fitted auxiliary contacts
31: Frame size S2
4: Trip current rating code
k: Thermal setting range 62~73A
A: Terminales de tornillo
10: Capacidad de ruptura estándar (without additional contacts)
- Datos técnicos básicos
| Artículo | Presupuesto |
| Tamaño del marco | T2, width 55mm, Montaje en carril DIN |
| polacos | 3PAG |
| Rango de ajuste de sobrecarga térmica | 62 ~ 73A (adjustable via front knob) |
| Instantaneous electromagnetic short-circuit trip | 949A (fijado) |
| clase de viaje | Clase 10 (for normal motor starting; trips within 10s at 7.2× rated current) |
| Tensión operativa nominal | CA 690V, CC 250 V. |
| Rated ultimate short-circuit breaking capacity Icu@400V | 65el |
| Tipo de conexión | Terminales de tornillo |
| Contactos auxiliares incorporados | Ninguno; auxiliary contact modules must be fitted separately |
| Potencia del motor aplicable (CA 400 V.) | Aprox.. 37kW 3-phase motor |
| Peso neto | 1.172kilos |
| Código Aduanero SA | 85362090 |
- Funciones de protección
- Protección contra sobrecarga: Inverse-time thermal trip via bimetallic strip, motor overload protection and phase loss protection
- Protección contra cortocircuitos: Instantaneous electromagnetic trip for rapid short-circuit disconnection
- Front-mounted TEST pushbutton for manual tripping test of the mechanism
- Handle position indication: EN / APAGADO / fault trip position; padlockable for lockout
- Alambrado & Especificaciones de instalación
Main circuit conductor: máx.. 1×35mm² solid/stranded cable; máximo. 1×25mm² fine-stranded cable with ferrule
Par de apriete para terminales principales: 3.0~4.5 N·m, tornillos m6
Accepts top-in or bottom-in wiring; DIN35mm rail mounting
Can be assembled with SIRIUS 3RT contactor to form a direct-on-line starter, constituting a motor protection starter unit
- Selección & Información de reemplazo
Same-series Replacement (Misma calificación)
3RV2031-4KA15: Version with pre-fitted auxiliary contacts (1NO+1NC)
Nota: 3RV2031-4KA10 has no built-in auxiliary contacts. For feedback signals, 3RV2901 auxiliary contact accessory must be mounted externally.
Referencia alternativa nacional
siemens local China 3RV5/3RV6 series equivalent: 3RV5031-4KA10 (domestic frame S2, 62~73A, terminales de tornillo, largely identical parameters)
- Aplicaciones típicas
3-motores asíncronos de fase, fans, bombas de agua, compresores, protección del circuito del motor del transportador
Circuitos de arranque de motor dentro de gabinetes de control., combinado con contactores como conjuntos de arranque
Protección de motores para máquinas herramienta., climatización, embalaje, equipo de automatización química
- Guía de solución de problemas
- Se dispara inmediatamente después del arranque del motor.: Generalmente disparo por cortocircuito. Compruebe los devanados y cables del motor en busca de cortocircuito entre fases o a tierra..
- Tropiezos después de correr durante algún tiempo.: Sobrecarga. Vuelva a verificar la corriente nominal del motor y reinicie la perilla de ajuste.; inspeccionar para detectar atascos mecánicos.
- no se puede cerrar: Fallo del mecanismo, o el disparo por cortocircuito anterior no se restableció completamente. Presione el botón TEST para restablecer antes de cerrar..
- Lista de verificación de inspección de segunda mano
- Apariencia: Sin carcasa agrietada, marcas de quemaduras, o decoloración por sobrecalentamiento en los terminales
- Operación mecánica: Operación suave del mango; El botón TEST activa el disparo correctamente y se reinicia correctamente
- Continuidad: Los contactos principales conducen cuando están cerrados y aíslan cuando están abiertos.; sin cortocircuito interno
- Aislamiento: Mida la resistencia de aislamiento entre fases y a tierra usando un megger
Siemens 3RV2031-4KA10 (Marco S2) Dimensiones de instalación
Todos los modelos 3RV2031 de bastidor S2 comparten dimensiones exteriores idénticas
Dimensiones generales de la unidad (Ancho × Alto × Fondo)
Ancho W: 55 milímetros (55mm de espacio en gabinetes por unidad)
Altura H: 140 milímetros
Profundidad D: 149 milímetros (desde la superficie de montaje del riel hasta el frente de la manija de operación)
Método de montaje
Carril: Carril estándar DIN de 35 mm (TU ÚNICO 60715), montaje con clip; bloqueo de tornillo opcional
Orientación de montaje: cualquier orientación (vertical, Se permite la instalación horizontal.)
Espacios libres del gabinete (Disipación de calor / Liquidación eléctrica)
Montaje lado a lado: 0mm de espacio permitido para unidades adyacentes
Parte superior con espacio libre vertical & abajo: ≥50 mm en las zonas terminales superior/inferior
Distancia a la estructura metálica del gabinete conectada a tierra: Espacio libre lateral ≥10 mm
Recorte del gabinete (si se utiliza la manija de extensión de la puerta)
La unidad 3RV2 está montada en carril DIN dentro del gabinete.. Si una manija de operación de puerta extendida (se vende por separado) se requiere:
Ancho de corte: aprox. 48milímetros, altura de corte: aprox. 130milímetros
Nota: No se requiere recorte en el gabinete sin manija de extensión; unit is fully installed inside enclosure on DIN rail.
Notas complementarias
With 3RV2901 side-mounted auxiliary contact: overall width unchanged, slight increase in depth
When back-to-back assembled with 3RT contactor as starter: total depth equals sum of both components
Siemens 3RV2031-4KA10 Weight
✅ Net weight (unit only, no packaging): 1.17 kilos (manufacturer nominal 1.172 kilos; use 1.17kg on engineering drawings)
All S2 frame 3RV2031 models have similar weight, range 1.07~1.18 kg. Variations come from internal trip components; standard value for 3RV2031-4KA10 is 1.17 kilos.
Notas complementarias
- Sin accesorios: No 3RV2901 auxiliary contacts, door extension handles or other attachments. Weight increases slightly when accessories are fitted.
- Gross weight with factory carton: aprox. 1.30 kilos (for logistics estimation)
- Unit conversion: 1.17 kg ≈ 2.58 libras
Siemens 3RV2031-4KA10|Cross-brand Comparison + MPCB Product Series List
Reference device: 3RV2031-4KA10, frame S2, 55mm de ancho, 3PAG, 62~73A, terminales de tornillo, Clase 10, Icu@400V=65kA, sin contactos auxiliares incorporados, for 37kW@400V motor
⚠️ Important notice: No fully pin-to-pin drop-in replacement available. The below are function/rating/frame equivalent selections. Montaje en gabinete, accesorios, breaking capacity and instantaneous trip values must be verified. Protection coordination validation is mandatory before formal project replacement.
- Siemens Internal Cross-reference (Reemplazo preferido)
| Modelo | Descripción | Difference vs 3RV2031-4KA10 |
| 3RV2031-4KA10 | Unidad de referencia, imported Germany frame S2, 62~73A, terminales de tornillo, sin contactos auxiliares incorporados | Unidad básica |
| 3RV2031-4KA15 | Misma calificación actual, fitted with 1NO+1NC auxiliary contacts | Comes with built-in aux contacts; parámetros de resto idénticos |
| 3RV5031-4KA10 | Siemens China local frame S2, 62~73A screw terminals | Parameters largely identical, slightly lower Icu, economical domestic version |
| 3RV1031-4KA10 | Legacy 3RV1 frame S2, misma calificación actual | Older generation, eliminado gradualmente; similar outline but accessories not fully compatible |
3RV2 frame size overview
S00: 45milímetros, max 16A, motor ≤7.5kW
S0: 45milímetros, max 40A, motor ≤18.5kW
T2: 55milímetros, max 80A, motor ≤37kW (frame of this model)
T3: 70milímetros, max 100A, motor ≤45~55kW
- Imported Brand Equivalent Cross-reference (62~73A, S2 frame class MPCB)
| Marca | Serie de productos | Modelo equivalente | Key Parameter Notes & Diferencias |
| Schneider | TeSys GV3 (GV3ME) | GV3ME80 | 56~80A adjustable, mando giratorio, 3PAG, terminales de tornillo; 55marco de mm, Clase 10. GV2 max 40A, GV2 cannot replace this model. Icu to be checked; instantaneous trip differs from Siemens |
| TEJIDO | MS series motor protection circuit breaker | MS165-73 | 60~73A adjustable, 3PAG, Carril DIN, 55marco de mm; MS165 is ABB equivalent to S2 frame. MS132 max 32A, insufficient rating, not suitable |
| Eaton (Möller) | PKZ2 motor protector | PKZ2-73 | 62~73A, 3PAG, rotary operation, S2 frame, Clase 10. PKZ1 small frame; PKZ2 corresponds to 3RV2 S2 |
| Omrón | BM series motor protection breaker | BM6R-63 | Adjustment range near 62~73A, 3PAG; limited domestic adoption, verify breaking capacity during selection |
- Alternativas de marcas nacionales (Cost Reduction for Projects)
| Marca | Serie | Modelo equivalente | Observaciones |
| chint | NS2 series | NS2-80 62~73A | NS2 motor protection breaker, 55milímetros, Clase 10, terminales de tornillo |
| Delicioso | CDV6 series | CDV6-80 62~73A | Same function MPCB, economical domestic type, lower Icu vs imported brands |
| Nader | NDM2-M | NDM2-M80 62~73A | High-end industrial domestic, mayor capacidad de rotura, suitable for critical circuits |
- MPCB Product Portfolio Overview by Brand (Thermal-Magnetic DIN Rail Motor Protection Circuit Breaker)
siemens
3RV2 (SIRIUS main import range: S00/S0/S2/S3, 0.1~100A)
3RV5 / 3RV6 (domestic economical range, S00/S0/S2)
3RV1 (modelo heredado, eliminación gradual)
3VU (old compact type, máx. 63A)
Schneider
GV2: Small frame 45mm, 0.1~40A
gv3: Medium frame 55mm, 40~80A (counterpart to 3RV2 S2)
GV7: Marco grande, 80~150A
TEJIDO
MS116: Marco pequeño
MS132: Marco mediano, max 32A
MS165: 55mm frame up to 80A (counterpart to 3RV2 S2)
MO series (high breaking capacity version)
Eaton (Möller)
PKZ0 / PKZ1: Baja corriente
PKZ2: S2 frame up to 80A
PKZ3: Marco grande
Main Domestic Brands
Chint NS2
Delixi CDV6
Nader NDM2-M
Changshu CM1-M (motor protection variant)
- Risks for Replacement Selection (Critical for Engineering)
- Different instantaneous short-circuit trip (N factor): 3RV2031-4KA10 fixed at 949A. Schneider GV3 and ABB MS165 have different electromagnetic trip thresholds. Cambios en la coordinación de la protección contra cortocircuitos.. El reemplazo directo puede causar pérdida de selectividad..
- Capacidad de rotura máxima Icu: 3RV2 es 65 kA a 400 V. Los modelos domésticos generalmente tienen una Icu más baja y NO deben usarse para circuitos con alta posible corriente de cortocircuito..
- Enclavamiento mecánico & conjunto de contactores: 3RV2 puede encajar directamente en el contactor 3RT para formar un arrancador. Los dispositivos de varias marcas no se pueden unir mecánicamente, Se requieren soportes de montaje separados..
- Los sistemas de accesorios de contactos auxiliares son incompatibles; profundidad de montaje, El par de apriete y la sección transversal máxima del cable difieren.
- Certificado UL/CE: No hay reemplazo arbitrario de marca para las máquinas de exportación.
- Reglas de selección recomendadas
Modernización del gabinete, modificación mínima: Siemens 3RV5031-4KA10 (reemplazo nacional de la misma marca)
Importar sustitución de marca: Schneider GV3ME80 / ABB MS165-73, Se requiere una nueva verificación de la coordinación de la protección contra cortocircuitos.
Ahorro de costes en circuitos domésticos no críticos: Chint NS2-80 / Delixi CDV6-80
contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor