Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

cortacircuitos/

Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker

Tipo de producto: SIRIUS 3RV2 series frame S2 motor protection circuit breaker (protector de motor), active production model, made in Germany Model Code Explanation 3RV 2 0 31 4 K A 10 3RV: SIRIUS motor protection circuit breaker 2: 2nd generation of 3RV2 series 0: Versión estándar, no pre-fitted auxiliary contacts 31: Frame size S2 4: Viaje ...

  • Detalles del producto

Tipo de producto: SIRIUS 3RV2 series frame S2 disyuntor de protección del motor (protector de motor), active production model, made in Germany

  1. Explicación del código del modelo

3RV 2 0 31 4 K A 10

3RV: SIRIUS motor protection circuit breaker

2: 2nd generation of 3RV2 series

0: Versión estándar, no pre-fitted auxiliary contacts

31: Frame size S2

4: Trip current rating code

k: Thermal setting range 62~73A

A: Terminales de tornillo

10: Capacidad de ruptura estándar (without additional contacts)

  1. Datos técnicos básicos
ArtículoPresupuesto
Tamaño del marcoT2, width 55mm, Montaje en carril DIN
polacos3PAG
Thermal overload setting range62 ~ 73A (adjustable via front knob)
Instantaneous electromagnetic short-circuit trip949A (fijado)
clase de viajeClase 10 (for normal motor starting; trips within 10s at 7.2× rated current)
Tensión operativa nominalCA 690V, CC 250 V.
Rated ultimate short-circuit breaking capacity Icu@400V65el
Tipo de conexiónTerminales de tornillo
Contactos auxiliares incorporadosNinguno; auxiliary contact modules must be fitted separately
Potencia del motor aplicable (CA 400 V.)Aprox.. 37kW 3-phase motor
Peso neto1.172kilos
Código Aduanero SA85362090
  1. Funciones de protección
  2. Protección contra sobrecarga: Inverse-time thermal trip via bimetallic strip, motor overload protection and phase loss protection
  3. Protección contra cortocircuitos: Instantaneous electromagnetic trip for rapid short-circuit disconnection
  4. Front-mounted TEST pushbutton for manual tripping test of the mechanism
  5. Handle position indication: EN / APAGADO / fault trip position; padlockable for lockout
  6. Alambrado & Especificaciones de instalación

Main circuit conductor: máx.. 1×35mm² solid/stranded cable; máximo. 1×25mm² fine-stranded cable with ferrule

Tightening torque for main terminals: 3.0~4.5 N·m, tornillos m6

Accepts top-in or bottom-in wiring; DIN35mm rail mounting

Can be assembled with SIRIUS 3RT contactor to form a direct-on-line starter, constituting a motor protection starter unit

  1. Selección & Información de reemplazo

Same-series Replacement (Misma calificación)

3RV2031-4KA15: Version with pre-fitted auxiliary contacts (1NO+1NC)

Nota: 3RV2031-4KA10 has no built-in auxiliary contacts. For feedback signals, 3RV2901 auxiliary contact accessory must be mounted externally.

Domestic Alternative Reference

siemens local China 3RV5/3RV6 series equivalent: 3RV5031-4KA10 (domestic frame S2, 62~73A, terminales de tornillo, largely identical parameters)

  1. Aplicaciones típicas

3-motores asíncronos de fase, fans, bombas de agua, compresores, conveyor motor circuit protection

Motor starter circuits inside control cabinets, combined with contactors as starter assemblies

Motor protection for machine tools, climatización, embalaje, chemical automation equipment

  1. Guía de solución de problemas
  2. Trips immediately upon motor start: Usually short-circuit trip. Check motor windings and cables for phase-to-phase or earth short circuit.
  3. Trips after running for some time: Sobrecarga. Recheck motor rated current and reset the adjustment knob; inspect for mechanical jamming.
  4. no se puede cerrar: Fallo del mecanismo, or previous short-circuit trip not fully reset. Press TEST button to reset before closing.
  5. Second-hand Inspection Checklist
  6. Apariencia: No cracked housing, burn marks, or overheating discoloration on terminals
  7. Mechanical operation: Smooth handle operation; TEST button triggers trip correctly and resets properly
  8. Continuidad: Main contacts conduct when closed and isolate when open; no internal short circuit
  9. Aislamiento: Measure insulation resistance between phases and to earth using a megger

Siemens 3RV2031-4KA10 (Marco S2) Dimensiones de instalación

All 3RV2031 models of frame S2 share identical outer dimensions

Unit Overall Dimensions (Ancho × Alto × Fondo)

Ancho W: 55 milímetros (55mm cabinet space per unit)

Altura H: 140 milímetros

Profundidad D: 149 milímetros (from rail mounting surface to front of operating handle)

Método de montaje

Carril: DIN 35mm standard rail (TU ÚNICO 60715), montaje con clip; optional screw locking

Orientación de montaje: any orientation (vertical, horizontal installation allowed)

Cabinet Clearances (Disipación de calor / Electrical clearance)

Side-by-side mounting: 0mm gap allowed for adjacent units

Vertical clearance top & abajo: ≥50mm at upper/lower terminal zones

Clearance to earthed cabinet metalwork: ≥10mm lateral clearance

Cabinet cutout (if door extension handle is used)

The 3RV2 unit is DIN-rail mounted inside the cabinet. If an extended door operating handle (se vende por separado) se requiere:

Cutout width: aprox. 48milímetros, cutout height: aprox. 130milímetros

Nota: No cabinet cutout required without extension handle; unit is fully installed inside enclosure on DIN rail.

Notas complementarias

With 3RV2901 side-mounted auxiliary contact: overall width unchanged, slight increase in depth

When back-to-back assembled with 3RT contactor as starter: total depth equals sum of both components

Siemens 3RV2031-4KA10 Weight

✅ Net weight (unit only, no packaging): 1.17 kilos (manufacturer nominal 1.172 kilos; use 1.17kg on engineering drawings)

All S2 frame 3RV2031 models have similar weight, range 1.07~1.18 kg. Variations come from internal trip components; standard value for 3RV2031-4KA10 is 1.17 kilos.

Notas complementarias

  1. Sin accesorios: No 3RV2901 auxiliary contacts, door extension handles or other attachments. Weight increases slightly when accessories are fitted.
  2. Gross weight with factory carton: aprox. 1.30 kilos (for logistics estimation)
  3. Unit conversion: 1.17 kg ≈ 2.58 libras

Siemens 3RV2031-4KA10|Cross-brand Comparison + MPCB Product Series List

Reference device: 3RV2031-4KA10, frame S2, 55mm de ancho, 3PAG, 62~73A, terminales de tornillo, Class10, Icu@400V=65kA, sin contactos auxiliares incorporados, for 37kW@400V motor

⚠️ Important notice: No fully pin-to-pin drop-in replacement available. The below are function/rating/frame equivalent selections. Cabinet mounting, accesorios, breaking capacity and instantaneous trip values must be verified. Protection coordination validation is mandatory before formal project replacement.

  1. Siemens Internal Cross-reference (Preferred Replacement)
ModeloDescripciónDifference vs 3RV2031-4KA10
3RV2031-4KA10Reference unit, imported Germany frame S2, 62~73A, terminales de tornillo, sin contactos auxiliares incorporadosBase unit
3RV2031-4KA15Misma calificación actual, fitted with 1NO+1NC auxiliary contactsComes with built-in aux contacts; rest parameters identical
3RV5031-4KA10Siemens China local frame S2, 62~73A screw terminalsParameters largely identical, slightly lower Icu, economical domestic version
3RV1031-4KA10Legacy 3RV1 frame S2, same current ratingOlder generation, eliminado gradualmente; similar outline but accessories not fully compatible

3RV2 frame size overview

S00: 45milímetros, max 16A, motor ≤7.5kW

S0: 45milímetros, max 40A, motor ≤18.5kW

T2: 55milímetros, max 80A, motor ≤37kW (frame of this model)

T3: 70milímetros, max 100A, motor ≤45~55kW

  1. Imported Brand Equivalent Cross-reference (62~73A, S2 frame class MPCB)
MarcaSerie de productosModelo equivalenteKey Parameter Notes & Diferencias
SchneiderTeSys GV3 (GV3ME)GV3ME8056~80A adjustable, rotary knob, 3PAG, terminales de tornillo; 55marco de mm, Class10. GV2 max 40A, GV2 cannot replace this model. Icu to be checked; instantaneous trip differs from Siemens
TEJIDOMS series motor protection circuit breakerMS165-7360~73A adjustable, 3PAG, Carril DIN, 55marco de mm; MS165 is ABB equivalent to S2 frame. MS132 max 32A, insufficient rating, not suitable
Eaton (Möller)PKZ2 motor protectorPKZ2-7362~73A, 3PAG, rotary operation, S2 frame, Class10. PKZ1 small frame; PKZ2 corresponds to 3RV2 S2
OmrónBM series motor protection breakerBM6R-63Adjustment range near 62~73A, 3PAG; limited domestic adoption, verify breaking capacity during selection
  1. Alternativas de marcas nacionales (Cost Reduction for Projects)
MarcaSerieModelo equivalenteObservaciones
chintNS2 seriesNS2-80 62~73ANS2 motor protection breaker, 55milímetros, Class10, terminales de tornillo
DeliciosoCDV6 seriesCDV6-80 62~73ASame function MPCB, economical domestic type, lower Icu vs imported brands
NaderNDM2-MNDM2-M80 62~73AHigh-end industrial domestic, mayor capacidad de rotura, suitable for critical circuits
  1. MPCB Product Portfolio Overview by Brand (Thermal-Magnetic DIN Rail Motor Protection Circuit Breaker)

siemens

3RV2 (SIRIUS main import range: S00/S0/S2/S3, 0.1~100A)

3RV5 / 3RV6 (domestic economical range, S00/S0/S2)

3RV1 (modelo heredado, eliminación gradual)

3VU (old compact type, max 63A)

Schneider

GV2: Small frame 45mm, 0.1~40A

GV3: Medium frame 55mm, 40~80A (counterpart to 3RV2 S2)

GV7: Large frame, 80~150A

TEJIDO

MS116: Small frame

MS132: Marco mediano, max 32A

MS165: 55mm frame up to 80A (counterpart to 3RV2 S2)

MO series (high breaking capacity version)

Eaton (Möller)

PKZ0 / PKZ1: Low current

PKZ2: S2 frame up to 80A

PKZ3: Large frame

Main Domestic Brands

Chint NS2

Delixi CDV6

Nader NDM2-M

Changshu CM1-M (motor protection variant)

  1. Risks for Replacement Selection (Critical for Engineering)
  2. Different instantaneous short-circuit trip (N factor): 3RV2031-4KA10 fixed at 949A. Schneider GV3 and ABB MS165 have different electromagnetic trip thresholds. Short-circuit protection coordination changes. Direct replacement may cause loss of selectivity.
  3. Capacidad de rotura máxima Icu: 3RV2 is 65kA@400V. Domestic models generally have lower Icu and shall NOT be used for circuits with high prospective short-circuit current.
  4. Enclavamiento mecánico & contactor assembly: 3RV2 can directly snap onto 3RT contactor to form starter. Cross-brand devices cannot mechanically clip together, separate mounting brackets required.
  5. Auxiliary contact accessory systems are incompatible; mounting depth, terminal torque and maximum cable cross-section differ.
  6. UL/CE certification: No arbitrary brand replacement for export machines.
  7. Recommended Selection Rules

Cabinet retrofit, modificación mínima: Siemens 3RV5031-4KA10 (domestic same-brand replacement)

Import brand substitution: Schneider GV3ME80 / ABB MS165-73, short-circuit protection coordination recheck required

Non-critical domestic circuit cost saving: Chint NS2-80 / Delixi CDV6-80