OMRON CP1E-N40DT-D PLC - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

 OMRON CP1E-N40DT-D PLC - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

OMRON CP1E-N40DT-D PLC

Model Code Breakdown Code Segment Definition CP1E OMRON compact economical PLC series N Application CPU: Supports pulse positioning, communication option boards and high-speed counters (E-type models have no pulse output function) 40 Total built-in I/O: 24 entradas + 16 outputs = 40 points D Power supply: DC24V power input T Output type: Transistor output D ...

  • Detalles del producto

Desglose del código del modelo

Segmento de códigoDefinición
CP1EOMRON compact economical SOCIEDAD ANÓNIMA serie
norteApplication CPU: Supports pulse positioning, communication option boards and high-speed counters (E-type models have no pulse output function)
40Total built-in I/O: 24 entradas + 16 outputs = 40 agujas
DFuente de alimentación: DC24V power input
tTipo de salida: Transistor output
DSinking transistor output (Current flows into PLC output terminals from external loads)

Additional distinction: CP1E-N40DT1-D = Sourcing transistor output. Wiring cannot be interchanged directly.

  1. Core Hardware Specifications

2.1 Configuración de E/S

Entradas digitales: 24-point DC24V, 7mA per point, sinking input type; apoya 8 interrupt input points

Salidas digitales: 16-point sinking transistor outputs, 0.5A per point, 8 points share one common terminal group; maximum total output current 2A

Capacidad de expansión: Arriba a 3 CP1W expansion modules (digital, cosa análoga, temperature modules); maximum total system I/O: 192 agujas

Incorporado 2 analog potentiometers on main unit (Removed on updated model N40SDT-D)

2.2 Operación & Memory Specifications

Program Capacity: 8K steps for Ladder Diagram / Structured Text (CALLE)

Memoria de datos (DM): 8K palabras

Contador de alta velocidad: 4-axis differential phase input (100kilociclos); supports AB-phase and single-phase pulse signals

Salida de pulso: 4 independent high-speed pulse axes (100kilociclos); supports servo/stepper positioning, origin search and electronic gearing – core positioning feature of N-series CP1E

2.3 Interfaces de comunicación

  1. Standard Onboard Ports: USB (direct programming connection with PC), RS-232C (for HMI / host computer)
  2. Expansion Slot: Accepts 1 communication option board (CP1W-CIF01 RS232 / CIF11 RS485 / CIF41 Ethernet)
  3. Supported Protocols: Modbus RTU, PLC Link (network up to 9 CP1E units), Host Link

2.4 Eléctrico & Parámetros ambientales

Fuente de alimentación: CC 24 V (20.4~26,4V); total power consumption approx. 15W.

Temperatura de funcionamiento: 0~55 ℃; Temperatura de almacenamiento: -20~65℃; Humedad: 10%~90% RH (sin condensación)

Certificaciones & Montaje: CE, UL, cULus certified; Montaje en carril DIN

Dimensiones: 150(W.) × 90(h) × 85(D) milímetros; Peso: aprox. 900gramo

  1. Comparison Between Old & Modelos de reemplazo (Official Discontinuation Notice)

Original model CP1E-N40DT-D is gradually discontinued; modelo de reemplazo: CP1E-N40SDT-D

ArtículoCP1E-N40DT-D (Old Version)CP1E-N40SDT-D (New Replacement Model)
Communication ExpansionSoportes 1 CIF option boardNo expansion slot; only built-in USB + RS232
Analog Potentiometers2 adjustable potentiometers onboardEliminated
Unit Depth85milímetros79milímetros (slimmer design)
E/S, Salida de pulso, Encimera, Program CapacityFully identicalFully identical

Recomendación de selección:

Retain stock of old model if Ethernet / RS485 expansion options are required.

If only HMI connection and PC programming are needed, directly replace with N40SDT-D. Programs are fully compatible; only communication expansion functions are unavailable.

  1. Escenarios de aplicación típicos
  2. Standalone Machine Automation: Máquinas de embalaje, conveyor lines, small assembly equipment, injection molding auxiliary machines
  3. Multi-axis Positioning: Simple multi-axis cutting, drilling and transfer mechanisms with stepper / servoaccionamientos (4-axis pulse output)
  4. Single-station Production Line Control: Assembly line workstations, test fixtures, small warehouse sorting systems
  5. Environmental Protection Equipment: Small-scale water treatment, logic control of fans and valves for waste gas purification
  6. List of Commonly Used Matching Expansion Modules

Digital Modules: CP1W-8ER / 16ER (Salida de relé), CP1W-8ET (Sinking Transistor Output)

Módulos analógicos: CP1W-MAD44 (4AI + 2HACIA), CP1W-MAD11 (4 Entradas analógicas)

Temperature Acquisition Modules: CP1W-TS002 / TS004 (Thermocouple), CP1W-PT100

Communication Option Boards (Only compatible with old N40DT-D): CP1W-CIF41 (Ethernet), CIF11 (RS485 Modbus)

  1. Critical Wiring Rules & Operation Prohibitions
  2. Sinking Output Wiring: Connect positive pole of load to DC24V, negative pole to PLC output terminal, COM terminal to 0V. Reverse wiring is strictly forbidden and will burn output points.
  3. Servo Drive via Pulse Output: Pulse signal cables must be twisted-shielded and routed away from power cables to reduce interference and pulse loss.
  4. Do not share the same switching power supply for PLC main unit DC24V and external sensors, which may cause drift of input signals.
  5. Program Backup: Built-in lithium battery retains DM data and user programs. Service life approx. 5 años; replace with CP1W-BAT01 upon expiry.
  6. Troubleshooting Matrix for Common Faults
Síntoma de fallaCausa principalSolución
No pulse output actionReversed output wiring, COM terminal not connected to 0V, pulse instructions not enabled in programVerify sinking wiring; check parameters of PULS / SPED instructions
Input points permanently ON / No signal inputMissing external 24V power supply, mismatched NPN/PNP sensor typeNPN sensors match sinking input of this PLC; replace sensor or install signal conversion module
PLC Link communication failureRS485 terminal resistor not activated, duplicated station numbers, reversed A/B wiringEnable terminal resistors on both ends, standardize A/B cable sequence, modify duplicated station numbers
Red ERR light flashes after power-onProgram error, short-circuit on expansion module, low battery voltageClear program for testing; disconnect expansion modules one by one for inspection; replace lithium battery

Full Specification of Programming Software for OMRON CP1E-N40DT-D

  1. Core Programming Software: CX-Programmer (Abbreviated as CX-P)

It is the only official programming tool dedicated to all OMRON PLC series (CP1E/CP2E/CJ/CS etc.), fully compatible with CP1E-N40DT-D.

Minimum Version Requirements

  1. Funciones básicas (pulse control, comunicación RS485): CX-Programmer V9.03 or higher
  2. When using CP1W-CIF41 Ethernet option board: Must install V9.12 or higher
  3. New main units / updated N40SDT-D model: Recommended version V9.6 / V9.73 (included in CX-One V4 series)
  4. Two Installation Suites (CX-Programmer cannot be downloaded independently)

2.1 CX-One (Full Version, Recomendado)

Integrated OMRON automation toolset including all industrial control software:

CX-Programmer (PLC programming)

CX-Simulator (Offline PLC simulation; supports CP1E program emulation)

CX-Designer (HMI programming)

CX-Motion, CX-Protocol, communication drivers and other servo / HMI configuration tools

Suitable for projects requiring simultaneous debugging of PLC, HMI and servo drives.

2.2 CX-One Lite (Compact Version for Micro PLCs Only)

Only contains Micro PLC edition of CX-Programmer, without HMI and servo software. Smaller installation size, exclusively for compact CP1E/CP2E PLCs, ideal for standalone projects requiring only PLC programming.

  1. Supported Programming Languages (All compatible with CP1E-N40DT-D)
  2. Diagrama de escalera (LD) – Most widely used
  3. Diagrama de bloques de funciones (ETA)
  4. Structured Text (CALLE) – C-like high-level language
  5. Sequential Function Chart (SFC) – Step-based process flow

Pre-built function blocks for pulse positioning, high-speed counter and Modbus-RTU are embedded in the software, matching the 4-axis pulse output capability of this PLC.

  1. PC-PLC Connection Methods (Communication Settings in Software)
  2. Direct USB Connection (Most Convenient)

Mini-USB port on PLC main unit, standard printer USB cable. Seleccionar “USB” as communication type in software; driver-free recognition.

  1. RS232 Serial Port: Onboard DB9 port for connection with HMI or PC serial port
  2. RS485 Communication: Install CP1W-CIF11 option board
  3. Ethernet Communication: Install CP1W-CIF41 Ethernet option board for remote program upload/download
  4. Auxiliary Supporting Tools
  5. CX-Simulator: Offline simulation without physical PLC; supports logic debugging, pulse positioning and I/O simulation. Only available in full CX-One package.
  6. CX-Protocol: Debug custom communication messages between host computer and PLC
  7. SLM License Manager: Software activation and authorization tool
  8. Notas generales
  9. CX-One and CX-One Lite cannot be installed simultaneously; only one suite can be selected.
  10. This software is commercial licensed. Official trial versions with time limits are available; official license purchase is required for long-term use.
  11. Old CX-P versions V7 / V8 cannot recognize CP1E-N40DT-D and will trigger model mismatch errors.
  12. When creating a new project, select device type: CP1E → N40DT-D to fully activate 4-axis pulse control, expansion module and communication option board functions.