Tipo de producto: Single-phase SSR (Solid State Relé), integrated heat sink, zero-cross turn-on
Aporte: DC 5~24V; Producción: AC 24~240V, 60A @ 40 ℃
- Especificaciones clave
Entrada de control: CC de 5 a 24 V, max control current 7mA; operate voltage ≤4V, release voltage ≥1V
Load Voltage: AC 24~240V (operating range 19~264VAC, 50/60Hz)
Corriente nominal: 60A (AC-1, 40℃); derate to 48A when densely installed side-by-side
Surge Current: 440A (60Hz, 1 ciclo); VDRM 600V
On-state Voltage Drop: ≤1.6V RMS; Off-state Leakage Current: ≤20mA @ 200VAC
Modo de disparo: Zero-crossing Turn-on, minimizes inrush & EMI
Aislamiento: Phototriac optocoupler isolation
Rigidez dieléctrica: 4000VAC 1min; Insulation Resistance ≥100MΩ (DC500V)
Montaje: Carril DIN / montaje con tornillos; with operation indicator
Temperatura ambiente: -30~+80℃ (sin condensación); Almacenamiento: -30~100℃
Característica: Replaceable power cartridge for low maintenance cost
- Decodificación del número de modelo
G3PA: Series of high-current SSR with replaceable power modules
2: Output voltage class AC24–240V (4 = AC200–400/480V high voltage)
60: Rated current 60A
B: Integrated heat sink
VD: DC voltage input (DC5–24V)
- Aplicaciones típicas
Resistive AC loads such as heating tubes, infrared lamps, ventiladores y transportadores; Accionado directamente por salidas de transistor PLC..
Nota: Add varistor/RC snubber for inductive motor loads; never operate over current or over temperature.
- Same Series Cross Reference
G3PA-240B-VD: 24-240 V CA, 40A
G3PA-430B-VD: AC200–400V, 30A
- Domestic Equivalents (DC5-24V input, CA24-240V, 60A zero-cross SSR)
Meigeer MGR-1 D60
Ximanton H360ZF
Yangming SSR-60DA-H
Application Scenarios for G3PA-260B-VD
Core features summary: DC5–24V control, AC24–240V single-phase output, 60A, zero-cross trigger, built-in heat sink, field-replaceable power cartridge, PLC direct drive, contactless, conmutación de alta frecuencia. First choice for resistive heating loads.
Recordatorios: This is a single-phase SSR; usar 3 units in parallel for 3-phase heating control (one per phase).
Aplicaciones principales (Best Match)
- Temperature-controlled heating systems (largest application)
Hornos industriales, gabinetes de secado, thermostatic baths, cámaras de prueba de envejecimiento; barrel heating for injection & máquinas de extrusión, controladores de temperatura del molde; heat-seal blades, hot plates on packaging machines; electroplating tank heaters, thermal oil heaters.
Ventaja: Zero-cross switching avoids voltage spikes; matches PID time-proportion control from temperature controllers; contact-free design delivers ultra-long life for frequent cycling.
- High-power resistive lighting
Infrared heating lamps, halogen lamps, greenhouse supplementary lighting arrays.
✘ Not recommended: Fluorescent lamps & LED power supplies (inductive/capacitive surge loads).
- Light-duty fans & transportadores (inductive loads with surge protection)
Pequeños ventiladores centrífugos, hot air circulation blowers, single-phase conveyor motors with infrequent starts.
⚠️ Motors are inductive loads; external varistor/RC snubber is mandatory to suppress back EMF, otherwise the SSR will break down easily. Not suitable for large motors or frequent forward/reverse operation.
Other General Automation Applications
- Maquinaria de embalaje: Heat shrinkers, hot-knife cutters, hot air power control
- Goma & equipo de plastico: Heating platens for vulcanization & thermoforming molds
- Environmental test equipment: Heating circuits in temperature & humidity chambers
- Maquinaria alimentaria: Baking lines, fryer heating elements, thermal blanching equipment
- climatización: Electric duct heaters, auxiliary air-conditioning heating sections
- Cabinet power distribution: Reemplace el relé + contactor combinations; quiet, arcless operation, Instalación en carril DIN.
When to choose this SSR instead of electromagnetic contactors
Frequent ON/OFF cycling & PID power regulation (switching every several seconds)
Controlled by PLC or temperature controller DC24V transistor outputs
No arc noise, no contact burn-out & low maintenance required
DIN rail mounting with limited cabinet space, integrated heat sink included
Quick power cartridge replacement without full rewiring later
Unsuitable / Restricted Applications
Direct-on-line starting of large motors, frequently started pumps (high inrush current causes instant damage)
Capacitive loads, large switching power supply banks
400VAC loads (max rated voltage only 264VAC)
Cargas CC (this model is AC-output SSR only)
Circuits requiring short-circuit protection: SSR has no built-in short-circuit protection; fuse/circuit breaker must be installed upstream.
Sizing Tips
Derate to 48A when tightly mounted side-by-side (80% current rating); always leave current margin.
Cargas inductivas: Fit external 471K (470V, ≥1000A) varistor across output terminals, shortest wiring possible.
3-phase heating scheme: 3 independent G3PA-260B-VD, one per phase, keep 3-phase load balanced.
PID Power Regulation Wiring + Varistor Selection + Derating Installation Standard
Nota clave: This is a zero-crossing SSR, designed exclusively for time-proportion PID power regulation, not for phase-angle voltage regulation. DC5~24V input, control current ≤7mA; PLC transistor outputs and temperature controller SSR ports can drive it directly without auxiliary relays.
- PID Control Wiring (Controlador de temperatura / SOCIEDAD ANÓNIMA)
Definición de terminal (G3PA-260B-VD)
Entrada de control: A1(+), A2(-) (DC5~24V; reverse polarity will not burn the unit, just no operation)
Salida de energía: Line IN, Line OUT (series-connected on live wire, 24~240 VCA)
Recommended wiring: MCB → semiconductor fast fuse → SSR output → Load → Neutral (N wire bypasses SSR entirely).
Esquema 1: Driven by OMRON E5CC/E5EC Temperature Controller (Most Common Heating Loop)
- SSR output of temperature controller → A1(+), A2(-) of G3PA
- Separate power supply & PT100 thermocouple wiring
- Critical parameter settings
Modo de salida: RSS / Time Proportion (Zero-cross); DO NOT select phase-angle mode
Cycle Time (t): 20~40s for resistive heating; 30s for ovens & mold heaters. Too short a cycle causes overheating; too long creates large temperature fluctuations.
Run AT auto-tuning after stable temperature holding.
Nota: Open-collector outputs on temperature controllers have built-in 24VDC drive power, directly compatible with G3PA.
Esquema 2: PLC Transistor DO Drive (PNP / PNP)
salida PNP: PLC Y terminal → A1(+); 0V of 24VDC → A2(-)
salida NPN: 24VDC+ → A1(+); PLC Y terminal → A2(-)
programa PLC: Use fixed-cycle duty-cycle output (p.ej. 30s period, 0~100%). Avoid high-frequency PWM which overheats the thyristor.
Only 7mA input current; standard PLC transistor outputs can drive it without current-limiting resistors.
3-phase Heating (3× G3PA-260B-VD)
Independent phase control: one single-phase SSR per A/B/C phase. Inputs can share multi-channel SSR outputs from one temperature controller or multiple PLC DO points.
⚠️ This is not a 3-phase SSR; solo 3 separate single-phase units, keep load current balanced across 3 fases.
- varistor & RC Snubber Selection (Mandatory for Inductive Loads)
The G3PA has an internal varistor, but inductive back EMF exceeds internal absorption capacity; external MOV is required, wired directly across SSR output terminals with minimal lead length.
220VAC System (Aplicación primaria)
varistor: 14D471K (470V, ≥1000A surge current); 10D471K also acceptable.
110VAC System: 14D271K (270V, ≥1000A)
amortiguador RC (for solenoid valves, pequeños fans & transformadores):
C=0.047~0.1μF / 630VACACIONES; R=100~220Ω / 2W., series RC across output terminals.
✅ Resistive heating tubes: External snubber optional; ✅ Fans, bobinas & transformers will blow the SSR without external MOV.
Upstream Fuse Protection (Crítico: SSR has no short-circuit protection)
Semiconductor SSR fails instantly under short-circuit conditions; use aR/gR semiconductor fast fuses, not standard gG general fuses.
Resistive heating loads: 80A fast fuse (1.2~1.5× rated current of 60A)
Inductive fan loads: 100A fast fuse
Install fuse immediately upstream of the SSR to shorten fault loop length.
- Reducción de potencia & Especificaciones de instalación (G3PA-260B-VD Special Rule)
The G3PA-260B-VD cannot be tightly mounted side-by-side (stated in official datasheet), different from 240B/220B models.
- Full rating condition: Vertical independent mounting, ≥10mm clearance left & bien, ambient temp ≤40℃ → 60A full current.
- Densely arranged on DIN rail:
2 or more units installed tightly together: Max current limited to 48A (80% reducción de potencia).
4+ units side-by-side: Maintain ≥10mm gap between adjacent SSRs, otherwise overheating failure occurs.
Apilamiento vertical: ≥80mm vertical gap between upper & lower SSRs to keep airflow.
- Horizontal flat mounting (heat sink sideways): Derate current by an additional 30%; avoid this mounting orientation.
- Cabinet ambient >40℃: Further derate current per temperature derating curve; add cabinet cooling fans.
- Par terminal: M3.5 screw terminals, tighten to 0.8~1.2N·m. Loose terminals cause overheating & terminales quemados.
- Cartridge replacement: G3PA allows standalone replacement of the G32A power cartridge without rewiring main power circuits, ideal for bulk maintenance.
- Commissioning Troubleshooting Checklist
- Never use this zero-cross SSR for phase-angle dimming/power control; it only supports time-proportion ON/OFF power regulation.
- Off-state leakage: ≤20mA residual voltage across load when SSR is OFF; always isolate upstream MCB before maintenance.
- Do not add large series resistors on input side; low voltage will cause false triggering.
- Separate DC24V control wiring from high-current power cables to avoid EMI interference.
- Cold heating element inrush current: Limit heater rated current to ≤70% of SSR rated current for extra safety margin.
- Diagnóstico rápido de fallas
Indicator ON, load no heat: Open circuit on main circuit, fusible quemado, broken heater element.
Indicator OFF: No input voltage/polarity reversed, temperature controller output disabled, PLC program no output.
Repeated SSR breakdown: No external MOV for inductive loads, insufficient heat dissipation, oversized fuses, frequent mains voltage surges.
Severe temperature oscillation: PID cycle time too short, P-gain too high, poor thermal insulation, thermocouple misposition.
OMRON Single-Phase SSR + Electromagnetic Power Relay List
Nota: All SSRs are zero-crossing, opto-isolated. G3PA series (tu modelo actual) features replaceable power cartridges, integrated heat sink & Montaje en carril DIN. G3NA/G3NE are cost-effective compact SSRs. Electromagnetic relays are plug-in cabinet relays for PLC & temperature control loops.
Parte 1: G3PA Series (Single-phase SSR, Priority Model)
| Modelo | Carga de salida | Entrada de control | Observaciones |
| G3PA-210B-VD-X | AC24~240V, 10A | DC5~24V | Slim low-current model |
| G3PA-220B-VD-X | AC24~240V, 20A | DC5~24V | Slim model |
| G3PA-240B-VD | AC24~240V, 40A | DC5~24V | Standard heating model |
| G3PA-260B-VD | AC24~240V, 60A | DC5~24V | ✅ Current model |
| G3PA-420B-VD | AC200~400V, 20A | DC12~24V | High voltage version |
| G3PA-420B-VD-2 | AC200~480V, 20A | DC12~24V | Wide high voltage range |
| G3PA-430B-VD | AC200~400V, 30A | DC12~24V | High voltage model |
| G3PA-430B-VD-2 | AC200~480V, 30A | DC12~24V | Wide high voltage range |
| G3PA-450B-VD-2 | AC200~480V, 50A | DC12~24V | High voltage high-current model |
Replaceable Power Cartridges
G32A-A20-VD-X: For G3PA-220B
G32A-A40-VD: For G3PA-240B
G32A-A60-VD: For G3PA-260B
Parte 2: G3NA Economy Single-phase SSR (No integrated heat sink)
| Modelo | Carga de salida | Entrada de control |
| G3NA-210B | AC24~240V, 10A | DC5–24V |
| G3NA-220B | AC24~240V, 20A | DC5–24V |
| G3NA-240B | AC24~240V, 40A | DC5–24V |
| G3NA-260B | AC24~240V, 60A | DC5–24V |
| G3NA-290B | AC24~240V, 90A | DC5–24V |
| G3NA-420B | AC200–400V, 20A | DC5–24V |
| G3NA-440B | AC200–400V, 40A | DC5–24V |
Parte 3: G3NE Compact Mini SSR (Space-saving low-power use)
| Modelo | Carga de salida | Entrada de control |
| G3NE-210T | AC24~240V, 10A | DC5–24V |
| G3NE-220T | AC24~240V, 20A | DC5–24V |
Parte 4: G3PJ / G3PE New Generation SSR (Spring terminals, high surge resistance)
G3PJ-225B: 24-240 V CA, 25A, DC5–24V
G3PJ-245B: 24-240 V CA, 45A, DC5–24V
G3PE-225B: 24-240 V CA, 25A, DC5–24V
G3PE-245B: 24-240 V CA, 45A, DC5–24V
Regla de codificación del modelo:
2 = AC24~240V (220V heating mainstream)
4 = AC200~400/480V high voltage
VD = DC input; A = AC input
Parte 5: OMRON Electromagnetic Power Relays (Plug-in cabinet type)
- Serie G2R (General-purpose Intermediate Relays)
| Modelo | Formulario de contacto | Calificación de contacto | Opciones de voltaje de bobina |
| G2R-1-SN | 1a | 10A 250VAC | CC 24 V, 12 V CC., CA 220 V. |
| G2R-2-SN | 2do | 5A 250VAC | CC 24 V, 12 V CC., CA 220 V. |
| G2R-1-E | 1a | 10A | PCB-mount version |
- LY High-current Plug-in Power Relays (Replace small contactors)
| Modelo | Formulario de contacto | Calificación de contacto |
| LY1N | 1a | 10A |
| LY2N | 2do | 10A |
| LY3N | 3do | 10A |
| LY4N | 4do | 10A |
| LY1F | 1a | 15A |
- G7L High-capacity Power Relays (30A direct single-phase load control)
| Modelo | Formulario de contacto | Calificación de contacto |
| G7L-1A-T | 1a | 30A 277VAC |
| G7L-2A-T | 2a | 30A 277VAC |
- G6B / G6D PCB Mini Relays (Onboard PLC & controladores de temperatura)
G6B-1174P: 1a, 5A, CC 24 V
G6D-1A: 1a, 5A, CC 24 V
Parte 6: Guía de selección: SSR vs Electromagnetic Relay
- Calefacción, PID power regulation, cambio frecuente & arcless operation → G3PA (Primera elección) / G3NA
- PLC DO signal conversion, low-frequency switching → G2R intermediate relay
- ≤30A low-frequency single-phase loads, cost-sensitive → G7L / LY relays
- Low-power, space-restricted applications → G3NE, G3PJ