Nombre del producto: TeSysD / Deca Mechanical Latch Block Function: After the contactor closes, it stays closed by mechanical locking; the coil does not need continuous power supply (ahorro de energía). Trip is triggered by pulse signal to terminals E1/E2; manual reset is also available. Model Definition LAD6K10: Mechanical latch main body F = Control voltage: ...

  • Detalles del producto

Nombre del producto: TeSysD / Deca Mechanical Latch Bloquear

Función: After the contactor closes, it stays closed by mechanical locking; the coil does not need continuous power supply (ahorro de energía). Trip is triggered by pulse signal to terminals E1/E2; manual reset is also available.

  1. Definición del modelo

LAD6K10: Mechanical latch main body

F = Control voltage: 110~127 V AC/DC (50/60 Hz)

  1. Contactores compatibles

LC1D09~D80A, LC1DT20~DT80A, CAD control relays

⚠️ Not compatible with low-consumption coil contactors

  1. Parámetros eléctricos clave

Control voltage Uc: 110–127 V AC / corriente continua

Pulse duration requirement: AC ≥ 100 EM; DC ≥ 250 EM; Max pulse duration ≤ 10 s

AC power consumption: 25 Virginia; DC power consumption: 30 W.

Frecuencia máxima de funcionamiento: 1200 ciclos/h

Vida mecánica: 500,000 ciclos

Tensión nominal de aislamiento Ui: 690 V

Clase de protección: IP2X

Temperatura de funcionamiento: -25℃ ~ +55 ℃

Montaje: Front snap-on installation; screw terminals E1, E2

Trip modes: Electric pulse trip + manual push-button reset

  1. Principio de funcionamiento
  2. Pulse power to contactor A1/A2 → Main contacts close; LAD6K10F mechanically latches and holds the closed state. The contactor remains closed even after the coil power is cut off.
  3. To open the contactor: Send a 110~127 V pulse to terminals E1-E2 of the latch block → Mechanical unlock, contactor drops out. Manual reset via the front button is also supported.
  4. Full Voltage Variant List (LAD6K10)

LAD6K10B: 24 VCA/CC

LAD6K10F: 110–127 V AC/DC (este modelo)

LAD6K10M: 220–240 V CA/CC

LAD6K10Q: 380–415 V AC/DC

LAD6K10L: 200–208 V AC/DC (interrumpido)

LAD6K10U: 256–277 V AC/DC (interrumpido)

  1. Aplicaciones típicas

Long-term closed loads, sistemas de almacenamiento de energía, bombas de agua, gate valves, and circuits requiring coil power cut-off after closing to reduce heating and power consumption.

Alambrado & PLC Timing Scheme for LAD6K10F (LC1D, 110~127V AC/DC trip)

Two independent pulse signals; never energize both at the same time. A1/A2 = closing pulse; E1/E2 = trip pulse; pulse duration shall not exceed 10 s.

Definición de terminal

contactor: A1, A2 → Closing coil (pulse only; keeps closed after mechanical latch without continuous power)

LAD6K10F: E1, E2 → Trip coil (110–127 V AC/DC for this model)

DIP switch on module: 0 = manual unlock; non-zero = enable mechanical latch (keep on non-zero for normal operation)

Cableado del circuito de control (PLC version)

Controlar el suministro: 110~127 V (match LAD6K10F voltage)

  1. PLC output Q0: Drive closing pulse → Contactor A1/A2 (use intermediate relay to protect PLC output)
  2. PLC output Q1: Drive trip pulse → Terminals E1/E2 of LAD6K10F
  3. Contactor NO auxiliary contact → PLC input I0 (comentarios de estado)
  4. Entrelazar: Software interlock between Q0 and Q1; simultaneous output is strictly forbidden.

Simplified wiring description:

l (110V) → KA0 coil → Q0 → N; KA0 main contacts connect to A1/A2

l (110V) → KA1 coil → Q1 → N; KA1 main contacts connect to E1/E2

Contactor NO contact: One side to L, the other to PLC input I0

Recommend intermediate relays; do not drive the coil directly with PLC points, as the DC coil has high inrush current (30 W power).

Timing Requirements (Obligatorio)

AC pulse ≥ 100 EM

DC pulse ≥ 250 EM

Upper pulse limit: ≤ 10 s (coil burnout if exceeded)

Secuencia de tiempo

  1. Apoyar: Contactor open, I0=OFF
  2. Closing command (I1 start): Q0 outputs 200 ms pulse → A1/A2 energized → Contactor closes and latches mechanically. Q0 cuts off after pulse ends; contactor stays closed, I0=ON.
  3. Holding stage: No output on Q0/Q1, zero power consumption.
  4. Trip command (I2 stop): Q1 outputs 300 ms pulse → E1/E2 energized for unlock → Contactor opens, I0=OFF; Q1 cuts off after pulse ends.

PLC Logic (Universal for Siemens / mitsubishi)

Logic rules:

✅ Closing: Rising edge triggers TON timer for fixed pulse output

✅ Tripping: Rising edge triggers another TON timer for fixed pulse output

✅ Interlock: Block trip pulse while closing pulse is active, y viceversa

✅ Fault detection: If I0 remains OFF 500 ms after closing pulse, trigger alarm.

Sample logic (S7-1200 style):

I1: Start button

I2: Stop button

I0: Contactor auxiliary contact feedback

Q0: Closing pulse

Q1: Trip pulse

T37: Closing pulse timer, PT=200 ms

T38: Trip pulse timer, PT=300 ms

  1. Rising edge of I1 → Start T37; T37.Q = Q0; T37 auto-resets upon timeout.
  2. Rising edge of I2 → Start T38; T38.Q = Q1; T38 auto-resets upon timeout.
  3. Normally closed T37.Q in T38 startup circuit; normally closed T38.Q in T37 startup circuit (software interlock).
  4. alarma de fallo: If I0=0 after 500 ms of closing pulse, activate alarm.

Solución de problemas & Errores comunes

  1. DIP switch set to 0: Latch function disabled; contactor opens immediately once A1/A2 power is lost.
  2. Simultaneous closing & tripping output: Mechanical jamming or coil burnout.
  3. Pulse too short: C.A. < 100 ms → latch/trip failure; corriente continua < 250 ms → high failure rate.
  4. Continuous pulse (no timer): Coil burns out after exceeding 10 s.
  5. Low-consumption coil contactor: Incompatible with LAD6K10; latching will not work.

Operación Manual

Switch the DIP switch to 0 to release mechanically without power; used for commissioning and maintenance.

Emergency Stop Extension

Wire E-Stop NC contact in series with the E1/E2 trip circuit. Pressing E-Stop directly sends a trip pulse to open the load immediately.

  1. Lista completa de modelos de Schneider TeSys D Mechanical Latch Blocks (Pulse Latch: LAD6K / LA6DK)

Two series:

LAD6K10 (small frame: LC1D09~D80A)

LA6DK20 (large frame: LC1D80~D150)

Suffix letter = trip coil voltage; AC/DC universal pulse trip; terminals E1/E2; front snap-on mounting with manual reset DIP switch.

LAD6K10 (For LC1D09~D80A, LC1DT20~DT80A, CAD relays; Low-consumption coils NOT supported)

ModeloTrip Voltage UcObservaciones
LAD6K10B24 VCA/CCPropósito general
LAD6K10F110~127 V AC/DCTu modelo seleccionado
LAD6K10M220~240 V AC/DCMost common in China
LAD6K10Q380~415 V AC/DC3-phase control circuit
LAD6K10L200~208 V AC/DCNorth American voltage, interrumpido
LAD6K10U256~277 V AC/DCNorth American voltage, interrumpido

LA6DK20 (For LC1D80~D150, LC1DT115~DT200 high-current contactors)

ModeloTrip Voltage Uc
LA6DK20B24 VCA/CC
LA6DK20F110~127 V AC/DC
LA6DK20M220~240 V AC/DC
LA6DK20Q380~415 V AC/DC

Unified Technical Specs

Pulse requirement: AC ≥ 100 EM, DC ≥ 250 EM; Max pulse duration ≤ 10 s

Vida mecánica: 500,000 ciclos

Frecuencia máxima de funcionamiento: 1200 ciclos/h

Protección: IP2X

⚠️ Distinción Importante: LAD9R1 / LAD9R3 are mechanical interlock blocks for two contactors (bloqueo de avance/retroceso), NOT pulse hold latches; completely different function, do not select incorrectly.

  1. Comparación equivalente entre marcas

Nota clave: LAD6K is an external snap-on electromagnetic mechanical pulse latch exclusive to Schneider TeSys D.

siemens, TEJIDO, Mitsubishi do NOT manufacture identical front-mounted external latch modules with the same wiring logic.

Two replacement solutions:

  1. Function-equivalent solution: Bi-stable contactors with built-in mechanical latch or independent pulse latch units (same control logic: pulse close, pulse trip).
  2. Drop-in aftermarket replacement: Domestic compatible LAD6K modules (direct snap-on fit for LC1D; same terminals E1/E2, same wiring & momento).

❌ Warning: ABB VM, Siemens 3RA19xx, Mitsubishi UN-MLxx are ONLY mechanical interlock pieces for two contactors (bloqueo de avance/retroceso), with NO power-hold function; they cannot replace LAD6K.

Equivalent Replacement Table (Pulse Close + Mechanical Hold + Pulse Trip)

Original Schneider ModelContactores compatiblesMarcaModelo de reemplazoDescripción
LAD6K10B/F/M/QLC1D09~D80ADomestic aftermarketLAD6K10B/F/M/Q (clone version)Direct snap-on installation; E1/E2 terminals unchanged; alambrado & PLC timing unchanged; rentable; verify pulse power consumption
LAD6K10*LC1D seriessiemens3RT bi-stable contactor (3RT10xx-1BP40 etc.)Integrated built-in latch; no external module required; same pulse control logic; precio más alto
LAD6K10*LC1D seriesTEJIDOAF series bi-stable contactor AFxx-30-00-11RTRT = latching version; mechanical latch integrated into contactor body, no external accessory
LAD6K10*LC1D seriesmitsubishiS-T bi-stable latch type S-TxxRTRT suffix = built-in mechanical hold
LAD6K10*LC1D seriesDeltaMCxx-RT bi-stable contactorIntegrated mechanical latch

Non-Equivalent Models (Only Interlock, No Holding Function — Avoid These)

MarcaModeloTipo de productoRisk Reminder
TEJIDOVM19 / VM300/460HDual-contactor mechanical interlock pieceOnly prevents simultaneous closing of two contactors; no power-off holding function
siemens3RA1924-2B, 3RA1954-2AMechanical interlock assemblyForward/reverse interlock only; cannot keep a single contactor closed without coil power
mitsubishiUN-ML21 / UN-ML80Mechanical interlock accessoryOnly interlock, no latching hold
chint / DeliciosoCJX2 mechanical interlock pieceInterlock accessorySame limitation above

Replacement Selection Advice

  1. If LC1D contactors remain in use: Choose domestic compatible LAD6K10; no changes to drawings or PLC program.
  2. If contactor replacement is allowed: Select RT-series bi-stable contactors with integrated latch; fewer spare parts and lower failure rate.
  3. Never use simple interlock pieces to replace LAD6K; control logic differs completely, and the contactor will drop out once coil power is removed.
  4. Full Compatibility List (Latch Block vs Contactors)

Regla: Low-consumption coil contactors are NOT compatible with all LAD6K / LA6DK latches.

Same model body fits the same contactor range regardless of voltage suffix (B/F/M/Q).

1) LAD6K10 (LAD6K10F belongs to this group)

Compatible devices:

3-contactores de polos: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38, LC1D40A, LC1D50A, LC1D65A, LC1D80A

4-contactores de polos (with neutral): LC1DT20, LC1DT25, LC1DT32, LC1DT40, LC1DT60A, LC1DT80A

Relés de control: CAD32, CAD50 (standard coil only; low-consumption excluded)

2) LA6DK10 (Mid-size latch block)

Compatible devices:

3-polo: LC1D40, LC1D50, LC1D65

4-polo: LC1D65004, LC1D65008, LP1D65004, LP1D65008

3) LA6DK20 (Large-current latch block)

Compatible devices:

3-polo: LC1D80, LC1D95, LC1D115, LC1D150 (C.A. & DC coil versions are both acceptable)

4-polo: LP1D80004, LP1D80008, LC1D115004, LC1DT200A

Summary Table

Latch Block ModelCompatible Contactor Range
LAD6K10B/F/M/QLC1D09~D80A, LC1DT20~DT80A, CAD32/CAD50 (standard coil)
LA6DK10B/F/M/QLC1D40/D50/D65, LP1D65 4-pole
LA6DK20B/F/M/QLC1D80~D150, LP1D80, LC1DT200A

❌ Incompatible Product List (Errores de selección)

  1. LC1D & CAD relays with low-consumption coils (latching mechanism cannot hold reliably)
  2. TeSysK, TeSys E, iCT, iC65N contactors / relevos
  3. LC1F, LC1G, LC2D reversing contactors (different housing structure)
  4. No-name clone LC1D contactors with modified mold

Notas complementarias

Montaje: All snap onto the front face without screws; only wire E1/E2 trip terminals.

Timing rule (universal): AC pulse ≥ 100 EM; DC pulse ≥ 250 EM; max pulse duration strictly ≤ 10 s.

Voltage suffix code (universal):

B=24V, F=110~127V, M=220~240V, Q=380~415V.