| Segmento de modelo | Full Designation | Descripción |
| 2981800 | Número de pedido. | Contacto Fénix global unique part number |
| PSR | PSR | Phoenix Contact PSR series safety relay (Programmable Safety Relay) |
| SCP | SCP | Safety function: dedicated for Emergency Stop / Safety Gate monitoring (Safety Control for E-Stop/Door) |
| 24corriente continua | 24corriente continua | Control voltage: DC24V input |
| ESD | ESD | Function feature: Emergency Stop Delay |
| 4X1 | 4X1 | Configuración de contacto: 4 contactos (2 safety NO + 2 auxiliary NO), 1-channel safety input |
| 30 | 30 | Delay range: adjustable power-off delay 0.1s ~ 30s |
Aplicación principal: Single-channel safety relay for Emergency Stop and Safety Gate monitoring. It complies with safety rating SIL 3 / Cat.4 PL e, with 0.1–30s adjustable power-off delay. Suitable for protection scenarios of automated equipment requiring safety stop delay.
- Especificaciones principales
| Categoría de parámetro | Especificación detallada | Observaciones |
| Desempeño de seguridad | Nivel de seguridad: SIL 3 (CEI 61508) | Meets highest industrial safety requirements |
| Nivel de rendimiento: pl y, Categoría 4 (EN ISO 13849-1) | ||
| PFHd: 2.5×10⁻⁸/h | ||
| Características de entrada | Voltaje de control: CC 24 V (19.2~28.8V) | Compatible with standard industrial 24V DC control systems |
| Corriente de entrada: Max 40mA | ||
| Input Channel: 1 safety input (NC/NO optional) | ||
| Modo de reinicio: Automatic / Manual selectable | ||
| Características de salida | Safety Contacts: 2 pcs N/O (Force-guided) | Force-guided safety contacts ensure fail-safe operation |
| Contactos auxiliares: 2 pcs N/O | ||
| Calificación de contacto: AC-15: 230V/2.5A | ||
| DC-13: 24V/2.5A | ||
| Max Switching Voltage: 250VCA/CC | ||
| Max Switching Current: 6A | ||
| Delay Characteristics | Power-off delay: continuously adjustable 0.1s~30s | Adapt to different equipment stopping time requirements |
| Setting Accuracy: ±10% | ||
| Características físicas | Dimensiones: W22.5mm × H99mm × D121mm | Single-channel width, ahorra espacio en el gabinete |
| Peso: Aprox.. 0.22kilos | ||
| Montaje: 35carril DIN mm (EN 60715) | ||
| Alambrado: Plug-in screw terminals | ||
| Environmental Characteristics | Temperatura de funcionamiento: -20~+60℃ | Industrial-grade environmental adaptability for harsh working conditions |
| Temperatura de almacenamiento: -40~+85℃ | ||
| Humedad: 5~95%RH (sin condensación) | ||
| Vibration Resistance: 10~150Hz, 2gramo | ||
| Shock Resistance: 15gramo | ||
| Certificaciones de seguridad | CE, UL, CSA, TUV, ATEX | Cumple con los estándares internacionales de seguridad., globally applicable |
- Lista de accesorios & Installation Guidelines
3.1 Accesorios estándar
Safety relay unit ×1
Installation manual ×1
Terminal marking label ×1
Fixing clip ×2 (for DIN rail locking)
Delay adjustment screwdriver ×1 (special tool)
3.2 Precauciones de instalación
- Mounting Requirement: Install on standard 35mm DIN rail; maintain ≥5mm clearance from adjacent modules for heat dissipation.
- Especificación de cableado:
Circuito de control: Connect DC24V to A1(+)、A2(-)
Safety Input: Connect E-stop / safety gate contact to S11、S12 (NC contact preferred)
Salida de seguridad: Connect safety circuit (p.ej. bobina del contactor) a 13-14、23-24
Auxiliary Output: Connect alarm / indication circuit to 31-32、41-42
- Reset Setting:
Auto Reset: Automatically restore after power cycle
Reinicio manual: Requires external reset signal or manual reset button operation
- Delay Adjustment: Use the dedicated screwdriver to adjust the front panel potentiometer to set 0.1–30s power-off delay.
- Cross-model & Cross-brand Replacement
4.1 Phoenix Contact Same Series Alternative Models
| Model No. | Diferencia central | Escenario de aplicación |
| 2981800 | 1 canal, 2 seguridad + 2 contactos auxiliares, 0.1–30s delay | Standard E-stop / safety gate monitoring (current model) |
| 2981801 | 1 canal, 2 seguridad + 2 contactos auxiliares, 0.1–10s delay | Equipment with short stopping time |
| 2981802 | 1 canal, 2 seguridad + 2 contactos auxiliares, 0.1–1s delay | Fast stop equipment |
| 2981810 | 2 canales, 4 seguridad + 2 contactos auxiliares, no delay | Dual-channel redundant safety system |
| 2981820 | 1 canal, 2 seguridad + 2 contactos auxiliares, with alarm output | System requiring alarm indication |
4.2 Cross-brand Equivalent Solutions
| Marca | Modelo | Parámetros clave | Compatibility Note |
| Schneider | Zelio SR2P121BD | 1 canal, 2 safety contacts, 24En DC, Cat.4 | Similar function, different wiring layout |
| siemens | 3SK1111-1AB30 | 1 canal, 2 safety contacts, 24En DC, SIL 3 | Different dimensions, cabinet rearrangement required |
| Omrón | G9SA-321-T15 | 1 canal, 2 safety contacts, 24En DC, Cat.4 | Delay range 0.05–10s, slightly narrower |
| TEJIDO | MSR1275 | 1 canal, 2 safety contacts, 24En DC, SIL 3 | Precio más alto, fully identical function |
| Weidmüller | DRM570730LT | 1 canal, 2 safety contacts, 24En DC, Cat.4 | Fixed 1s non-adjustable delay |
- Selección & Pautas de reemplazo
5.1 Criterios de selección básicos
✅ Safety Level Matching: Ensure required safety rating (SIL/PL/Cat.) does not exceed product capability (SIL 3 / Cat.4 PL e).
✅ I/O Requirement:
Aporte: 1 channel sufficient; confirm NC or NO contact type.
Producción: Verify 2 seguridad + 2 auxiliary contacts meet control demands.
Capacidad de contacto: Ensure load current ≤2.5A (AC-15/DC-13).
✅ Delay Requirement: Confirm 0.1–30s adjustable range covers equipment stopping time.
✅ Reset Mode: Select auto or manual reset according to operation needs.
✅ Environmental Adaptation: Operating temperature ≤60℃ and humidity within industrial standard range.
5.2 Mejora & Opciones de reemplazo
Option A: Same Series Function Upgrade
More channels: 2981800 → 2981810 (2 canales, 4 safety contacts)
Add alarm output: 2981800 → 2981820 (with alarm output)
Shorter delay: 2981800 → 2981801 (0.1–10s) o 2981802 (0.1–1s)
Option B: Migrate from PSRclassic to PSRmini (Space Optimization)
Modelo de reemplazo: 2981900 (PSRmini-SCP-24DC/ESD/4X1/30)
Ventaja: Only 17.5mm width (5mm narrower), funciones idénticas, ahorra espacio en el gabinete.
Option C: Migrate from PSRclassic to PSRmodular (System Expansion)
Solución: PSRmodular system + safety function modules
Ventaja: Multi-channel expandable; integrates safety gate, Molestar, light curtain and other safety functions, suitable for complex safety systems.
5.3 Solución de problemas comunes
| Fenómeno de falla | Possible Cause | Solución |
| Module indicator off | Control power disconnected or faulty | Check DC24V input, measure voltage within 19.2~28.8V |
| No safety output action | Safety input loop open | Check E-stop / safety gate contact wiring and loop continuity |
| Abnormal delay time | Improper potentiometer adjustment | Readjust with dedicated screwdriver; calibrate with timer recommended |
| Reiniciar falla | Incorrect reset mode setting | Verify auto/manual reset configuration and check reset signal |
| Adhesión por contacto | Overload current exceeded | Measure load current; add intermediate relay if necessary |
Contacto Fénix 2981800 (PSR-SCP-24DC/ESD/4X1/30) is a single-channel safety relay with adjustable power-off delay, specially designed for emergency stop and safety gate monitoring, reaching the highest safety level SIL 3 / Cat.4 PL e. Its 22.5mm slim design and plug-in wiring facilitate installation and maintenance, while the 0.1–30s adjustable delay adapts to various equipment shutdown requirements. Durante la selección, focus on safety rating, configuración de E/S, delay range and reset mode. For upgrade, choose extended models in the same series or migrate to PSRmini / PSRmodular for space saving or system expansion.
Complete Model List of Phoenix Contact Safety Relays (Structured Classification)
- Model Naming Rule Overview
| Prefijo | Código de serie | Middle Code | Significado | Sufijo | Significado |
| PSR | Basic identifier for Phoenix safety relay | SCP | Molestar / Safety Gate dedicated | 24corriente continua | Control voltage DC24V |
| PSR | Safety Relay | SPP | Standard Safety Protection | ESD | Emergency Stop Delay (0.1-30s) |
| PSR | Safety Relay | MC | Mini Compact | 4X1 | Contacto: 4 NO (2 seguridad + 2 auxiliar) |
| PSR | Safety Relay | MS | Monitoring Safety | 30 | Delay time range (0.1-30s) |
| PSR | Safety Relay | UNI | Universal Configurable | PI | Push-in spring terminal |
| PSR | Safety Relay | MM | Motion Monitoring | CAROLINA DEL SUR | Screw terminal |
- PSRclassic Series (Standard Safety Relays)
2.1 Molestar / Safety Gate (SCP Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-SCP-24DC/ESD/4X1/30 | 2981800 | 1Ch, 2Safety+2Aux, 0.1-30s delay | SIL 3/Cat.4 PL e | Standard E-stop / Safety Gate |
| PSR-SCP-24DC/ESD/4X1/10 | 2981801 | 1Ch, 2Safety+2Aux, 0.1-10s delay | SIL 3/Cat.4 PL e | Short stop time equipment |
| PSR-SCP-24DC/ESD/4X1/1 | 2981802 | 1Ch, 2Safety+2Aux, 0.1-1s delay | SIL 3/Cat.4 PL e | Fast stop equipment |
| PSR-SCP-24DC/ESD/5X1/1X2/300 | 2981428 | 1/2Ch, 3Safety+1NC+2Aux, 0.1-300s delay | SIL 3/Cat.4 PL e | Long delay shutdown system |
| PSR-SCP-24UC/ESA4/3X1/1X2/B | 2963763 | 2Ch, 3Safety+1Aux, no delay | SIL 3/Cat.4 PL e | Dual-channel redundant safety system |
| PSR-SCP-24DC/MXF3/4X1/2X2/B | 2903257 | Multi-Ch, 4Safety+2Aux, 3 safety functions | SIL 3/Cat.4 PL e | Multi-function safety monitoring |
2.2 Standard Safety Function (SPP Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-SPP-24DC/SDC4/2X1/B | 2901426 | 1Ch, 2Safety contacts, no delay | SIL 3/Cat.4 PL e | Basic safety loop |
| PSR-SPP-230AC/ESAM2/3X1/1X2/B | 2901431 | 1Ch, 3Safety+1Aux, CA 230 V. | SIL 3/Cat.4 PL e | AC power supply system |
| PSR-SPP-24UC/URM/3X1/3X2 | 2901427 | 1Ch, 3Safety+3Aux, universal voltage | SIL 3/Cat.4 PL e | Multi-voltage compatible system |
| PSR-SPP-24DC/ESD/3X1/1X2/30 | 2981427 | 1Ch, 3Safety+1Aux, 0.1-30s delay | SIL 3/Cat.4 PL e | Delay-type safety system |
2.3 Light Curtain Monitoring (SCR Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-SCR-24DC/3X1/1X2 | 2981500 | 2Ch, 3Safety+1Aux, dedicated for light curtain | SIL 3/Cat.4 PL e | Standard light curtain monitoring |
| PSR-SCR-24DC/4X1/2X2 | 2981501 | 2Ch, 4Safety+2Aux, dedicated for light curtain | SIL 3/Cat.4 PL e | Complex light curtain safety system |
| PSR-SCR-24DC/5X1/1X2 | 2981502 | 2Ch, 5Safety+1Aux, dedicated for light curtain | SIL 3/Cat.4 PL e | High-density safety output |
2.4 Two-Hand Control (SCT Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-SCT-24DC/2X1/1X2 | 2981600 | 2Ch, 2Safety+1Aux, two-hand control | SIL 3/Cat.4 PL e | Standard two-hand operation |
| PSR-SCT-24DC/3X1/2X2 | 2981601 | 2Ch, 3Safety+2Aux, two-hand control | SIL 3/Cat.4 PL e | Complex two-hand operation |
- PSRmini Series (Micro Compact, 17.5mm Width)
3.1 Basic Safety Function (MC Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-MC32-3NO-1NC-24-230UC-SP | 2700525 | 1/2Ch, 3Safety+1NC, universal voltage | SIL 3/Cat.4 PL e | General safety monitoring |
| PSR-MC34-3NO-1DO-24DC-SP | 2700548 | 1/2Ch, 3Safety+1diagnostic output, CC 24 V | SIL 3/Cat.4 PL e | System with diagnostic output |
| PSR-MC45-3NO-1DO-24DC-SC | 1082024 | 1Ch, 3Safety+1diagnostic output, CC 24 V | SIL 3/Cat.4 PL e | Compact E-stop system |
| PSR-MC22-2NO-1NC-24DC-SP | 2700500 | 1Ch, 2Safety+1NC, CC 24 V | SIL 3/Cat.4 PL e | Small safety loop |
3.2 Safety Monitoring Module (MS Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-MS21-1NO-1DO-24DC-SC | 2702192 | 1Ch, 1Safety+1digital output, CC 24 V | SIL 3/Cat.4 PL e | Safety controller expansion |
| PSR-MS31-2NO-1DO-24DC-SP | 2702200 | 1Ch, 2Safety+1digital output, CC 24 V | SIL 3/Cat.4 PL e | Safety status monitoring |
- PSRmodular Series (Modular Safety System)
4.1 Main Control Module
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-UNI-L-1X4NO-1DO-24DC-PI | 1487648 | 1/2Ch, 4Safety+1DO, configurable | SIL 3/Cat.4 PL e | Universal configurable safety system |
| PSR-UNI-L-2X4NO-2DO-24DC-PI | 1487649 | 2Ch, 8Safety+2DO, configurable | SIL 3/Cat.4 PL e | Complex safety system |
| PSR-UNI-L-1X2NO-1NC-1DO-24DC-PI | 1487650 | 1/2Ch, 2Safety+1NC+1DO | SIL 3/Cat.4 PL e | System with NC output |
4.2 Expansion Module
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-EXT-L-1X4NO-24DC-PI | 1487651 | 4-safety output expansion | SIL 3/Cat.4 PL e | Output expansion |
| PSR-EXT-L-1X2NO-1NC-24DC-PI | 1487652 | 2Safety+1NC output expansion | SIL 3/Cat.4 PL e | Mixed output expansion |
- PSRmotion Series (Motion Monitoring Safety Relay)
5.1 Zero Speed / OverSpeed Monitoring
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-MM25-1NO-2DO-24DC-SC | 2702355 | Sensorless zero-speed monitoring, 3-motor de fase | SIL 3/Cat.3 PL e | Motor zero-speed safety protection |
| PSR-MM35-1NO-2DO-24DC-SC | 2702356 | Overspeed monitoring, 3-motor de fase | SIL 3/Cat.3 PL e | Motor overspeed safety protection |
| PSR-MM45-1NO-2DO-24DC-SC | 2702357 | Zero-speed + overspeed dual monitoring, 3-motor de fase | SIL 3/Cat.3 PL e | Full motor speed monitoring |
5.2 Rotation Direction Monitoring
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-MD25-1NO-2DO-24DC-SC | 2702360 | Rotation direction monitoring, 3-motor de fase | SIL 3/Cat.3 PL e | Motor rotation direction safety control |
- Safety Coupling Relays (PSR-SCP/SPP Series)
| Modelo | Número de pedido. | Core Parameter | Nivel de seguridad | Solicitud |
| PSR-SCP-24DC/FSP/1X1/1X2 | 2981700 | 1Safety+1Aux contact, coupling function | SIL 3 | Safety signal isolation |
| PSR-SCP-24DC/FSP2/2X1/1X2 | 2981701 | 2Safety+1Aux contact, coupling function | SIL 3 | Dual-channel safety isolation |
| PSR-PS21-1NO-1NC-24DC-SC | 2981702 | 1Safety+1NC contact, coupling function | SIL 3 | Safety signal switching |
- Key Selection Parameter Comparison
| Categoría de parámetro | Key Index | Consejos de selección |
| Nivel de seguridad | SIL 1-3, Cat.1-4, PL a-e | Determined by equipment risk assessment; max support SIL 3/Cat.4 PL e |
| Input Channel | 1 Channel / 2 Channel | Single channel for basic safety; dual channel for redundant safety |
| Configuración de contacto | Quantity of safety / contactos auxiliares | ≥2 safety contacts recommended; auxiliary contacts for alarm & indication |
| Voltaje de control | CC 24 V / CA 230 V. / Universal | Match on-site control system power supply |
| Function Feature | Delay / Diagnostic / Cross-circuit detection | E-stop requires delay; complex system needs diagnostic function |
| Mounting Width | 17.5milímetros / 22.5milímetros / 27.5milímetros | Choose PSRmini (17.5milímetros) for limited cabinet space |
| Wiring Type | Tornillo / Push-in spring | Push-in for frequent wiring; screw type for vibration environment |
- Notas complementarias
8.1 Posicionamiento en serie
PSRclassic: Standard type with complete functions, width starting from 22.5mm, suitable for conventional safety applications.
PSRmini: Micro compact type, only 17.5mm width, ahorra espacio en el gabinete.
PSRmodular: Configurable modular system, suitable for complex safety systems with expandable functions.
PSRmotion: Dedicated for motion monitoring, applicable to motor zero-speed / overspeed / rotation direction safety control.
8.2 Replacement Information
Old models are gradually phased out; priority recommended to select models manufactured after 2020.
Some models are discontinued; refer to Phoenix Contact official website or technical support for replacement.
8.3 Certificación de seguridad
Full series certified by CE, UL, CSA, TUV, Cumple con IEC 61508 and EN ISO 13849-1.
Partial models with ATEX certification for explosive atmosphere applications.
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares