Schneider 3CT-H1-100-C Current Transformer

Full Specification of Schneider 3CT-H1-100-C Current Transformer (Dedicated for EOCR) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • Detalles del producto

Full Specification of Schneider 3CT-H1-100-C Current Transformer (Dedicated for EOCR)

  1. Interpretación del código modelo
Segmento de códigoSignificadoDescripción
3ConnecticutSerie de productosThree-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1Código de especificaciónPrimary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100Rated Primary Current100A (numerator of transformation ratio)
doMounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. Parámetros técnicos básicos
Categoría de parámetroEspecificaciónRemark
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
Clase de precisiónClase 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10VirginiaMax permissible secondary loop impedance 200mΩ
Rango de frecuencia50/60HzGeneral industrial frequency
Tensión nominal de aislamientoCA 600 VMaximum continuous operating voltage
Withstand Voltage2kV (50Hz, 1mín.)Insulation test standard between windings and earth
Resistencia de aislamiento≥100MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
Dimensión generalW150×H71×D55mmEstructura compacta, space-saving installation
Tipo de montajePanel mountingCompatible con carril DIN estándar de 35 mm
MaterialPlástico de ingeniería ignífugoCompliant with UL94 V0 standard
PesoAprox.. 0.58kilosSingle unit weight
Proceso de dar un títuloCE, ULConforms to international safety standards
Número de orden3CT-H1-100-CExclusive official Schneider order code
  1. Full Model List (EOCR 3CT Series)
ModeloRelaciónAperture ShapeBore SizeCorriente nominalTipo de montaje
3CT-HS-75-C/Z75/5ACircularφ22mm75AC=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5ACircularφ25mm100AC=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5ACuadrado30×30mm150AC=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5ACuadrado35×35mm200AC=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5ACuadrado45×45mm300AC=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5ACuadrado55×55mm400AC=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
MarcaModeloRelaciónExactitudBurdenApertureCompatibilidad
Schneider

(SAMWHA)

3CT-H1-100-C100/5AClase 110Virginiaφ25mmPerfect match for EOCR
siemens5SD7410-7100/5AClase 110Virginiaφ25mmUniversal type, adaptation test required
TEJIDOCT-AR/100100/5AClase 115Virginiaφ25mmHigher burden capacity, EOCR compatible
chintbh-0.66/100100/5AClase 110Virginiaφ25mmCost-effective domestic alternative
DeliciosoLMZ1-0.66/100100/5AClase 110Virginiaφ25mmReemplazo interno, minor dimension difference

Notas de reemplazo

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. Solución de problemas & Mantenimiento
Fenómeno de fallaPosibles causasPasos de inspecciónSoluciones
No secondary outputCableado incorrecto, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
Insulation failureDampness, insulation aging, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

Safety Rules

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. Solicitud & Cases

Escenarios aplicables

EOCR motor protection system: sobrecorriente, undercurrent and phase loss protection

Low-voltage power distribution: Current monitoring and protection for circuits below AC 600V

Motor control center: Compact layout saves cabinet space

Líneas de producción industriales: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400Hz) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

Casos típicos

Caso 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

Caso 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, ahorro 50% espacio de instalación, simplifying wiring and improving operational reliability.

  1. Selección & Installation Guidelines

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

Precauciones de instalación

Keep correct S1(yo+) and S2(I-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

Programa de mantenimiento

ArtículoCycleEstándar
Visual inspectionMensualNo crack, looseness or overheating mark
Terminal tighteningTrimestralTorque range 2-3N·m
Prueba de aislamientoYearlyResistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 exactitud, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.