Schneider ATS48D62Q Soft Starter

Serie: Altistart 48, Torque Control Soft Starter (TCS torque control, ideal for pumps & fans to eliminate water hammer) ✅ Model Code Definition ATS48 = Altistart 48 soft starter series D62 = Rated current 62A (line connection); equivalent 107A for motor delta terminal connection Q = Main circuit voltage version: AC 230~415V (Y version: 208–690V) ...

  • Detalles del producto

Serie: Altistart 48, Control de par Arrancador suave (TCS torque control, ideal for pumps & fans to eliminate water hammer)

✅ Definición del código del modelo

ATS48 = Altistart 48 soft starter series

D62 = Rated current 62A (line connection); equivalent 107A for motor delta terminal connection

Q = Main circuit voltage version: AC 230~415V (Y version: 208–690V)

📌 Parámetros eléctricos básicos

Tensión del circuito principal: Three-phase AC 230–415V

Corriente nominal: 62A (line connection) / 107A (motor delta terminal connection)

Power rating at 400V:

Line connection (standard duty): 30kilovatios; trabajo pesado: 22kilovatios

Delta connection (standard duty): 55kilovatios; trabajo pesado: 45kilovatios

Controlar el suministro: 110–230V AC

Modo de inicio: TCS torque control, max current limit 5×In (factory default 4×In)

Stop mode: Free coasting (por defecto) / torque ramp soft stop (0.5~60s, preferred for pumps)

Pérdida de energía: 201W under standard duty; 153W under heavy duty

Clase de protección: IP20, montaje en gabinete

Comunicación: Built-in Modbus-RTU (RJ45, RS485; tasa de baudios: 4800/9600/19200bps); expandable to Profibus, DeviceNet via external gateway

Terminales de E/S:

2 logic outputs LO1/LO2

3 salidas de relé: R1 (falla), R2 (end of start), R3 (motor energized)

1 analogue output AO: selectable 0–20mA / 4–20mA

Dimensiones (Ancho×Alto×Profundidad): 190 × 290 × 235 milímetros; Peso neto: 8.3kilos

Estándares: CEI/EN 60947-4-2; Certificaciones: CCC, CE, UL, CSA etc.

🧩 Recommended Replacement Model

Reemplazo directo del fabricante original: ATS480D62Y (New Generation Altistart 480)

62Una corriente nominal, voltage range extended to 208–690V; control supply fixed at 110–230V AC; fully compatible with ATS48 functions, with built-in bypass logic and dual configuration. This is Schneider’s official upgrade solution.

Nota: ATS48Q series is replaced by ATS480Y series. Hardware terminals and program parameters differ; verify drawings and program before cabinet retrofit.

📦 Customs HS Code Reference

Primary declaration code: 84798997 (soft starter controller, widely used for export spare parts)

Alternative code used by some customs brokers: 85044090

Confirm with local customs before declaration.

🛠️ Aplicaciones típicas & Directrices de selección

Suitable for centrifugal pumps, fans, compresores, transportadores; mainly used to eliminate water hammer and mechanical shock.

Servicio estándar: Zapatillas, fanáticos comunes; S1 duty cycle

Servicio pesado: Trituradoras, arranques y paradas frecuentes, cargas de alta inercia. Select one size higher or adopt delta connection.

External bypass contactor is recommended to avoid continuous heating after bypass.

⚠️ Common Fault Troubleshooting (ATS48 Series General)

PHF: Pérdida de fase / desequilibrio de fase

PIF: Error de secuencia de fases

DCF: sobrecorriente, cortocircuito de salida, thyristor damage, bypass contactor sticking

InF / 5d2: Internal fault; if power cycle reset fails, repair is required

FSU: Control supply loss

Use Schneider PowerSuite software to upload parameters and read the latest 5 registros de fallas.

📋 Adjacent Models in the Same Series (versión Q, 230–415V)

ATS48D62Q → ATS480D62Y Retrofit Comparison List

Key conclusion: Power main circuit, mounting hole positions and relay terminals are fully interchangeable with existing wiring. The biggest risk is the control supply voltage: ATS48D62Q accepts 220–415V AC, while ATS480D62Y only supports 110–230V AC. If the original control power is taken from 400V line, a control transformer must be added.

  1. Terminales de alimentación principales (L1/L2/L3, T1/T2/T3, Derivación)
ArtículoATS48D62QATS480D62YRetrofit Instruction
Line input terminalsL1, L2, L3L1, L2, L3Same position, cable size and torque; reuse existing cables directly
Motor output terminalsT1, T2, T3T1, T2, T3Delta terminal connection is also supported; rated current remains 62A, equivalent 107A in delta connection
Bypass terminalsBuilt-in bypass wiring terminalsBuilt-in bypass wiring terminalsBypass contactor wiring is compatible; ATS480 has enhanced bypass logic in parameters
Tensión del circuito principal230–415V AC208–690V ACWider voltage range for ATS480; fully workable on 400V systems; same unit for 690V applications
Dimensiones de montaje190×290×235mmMismo ancho & altura, slightly deeper depthMounting holes match perfectly for direct in-place installation; check rear cabinet clearance
  1. Control Terminal Mapping (Crítico)
ATS48D62Q TerminalFunciónCorresponding ATS480D62Y TerminalObservaciones
CL1 / CL2Controlar el suministroCL1 / CL2⚠️Gran diferencia: ATS48Q: 220~415V AC; ATS480: only 110~230V AC. If control power is taken from L1-L2 (400V), add a control transformer to step down to 220V.
DETENERStop inputDETENER2-cable / 3-wire control logic remains compatible
CORRERRun inputCORRER
LI3Programmable DI3DI3Renamed, misma funcion
LI4Programmable DI4DI4Renamed, misma funcion
R1A-R1CRelé 1 (falla / programable)R1A-R1CContacto normalmente abierto, default fault output. Max contact voltage for ATS480 is limited to 230VAC; evaluate original 400V relay circuits.
R2A-R2CRelé 2 (end of start)R2A-R2CCommonly used for bypass drive; direct wiring reuse
R3A-R3CRelé 3 (motor energized / programable)R3A-R3C
AO1 / COMAnalogue output 0–20/4–20mAAQ1 / COMRenamed, función idéntica
LO1, LO2Logic outputsDQ1, DQ2Original LO1/LO2 → DQ1/DQ2; 24V active output requires external 24VDC supply
—PTC motor temperature sensingPT1/PT2/PT3ATS48 has no native PTC input; ATS480 adds built-in PTC/PT100 temperature sensing

I/O Power Supplement: Digital inputs and DQ logic outputs on ATS480 require external 24VDC. The unit has built-in 24V terminals to power DI directly, consistent with ATS48 power supply scheme.

  1. Communication Interface Differences
ArtículoATS48D62QATS480D62Y
Onboard communicationModbus RTU (RJ45 RS485)Modbus RTU with extended baud rate: 1200~256000bps
Fieldbus expansionExternal communication cards: Profibus, DispositivoNetModular communication cards: Profinet, Ethernet/IP, Modbus TCP etc.
SoftwarePowerSuiteAsí que muévete (Use the migration tool to convert parameter files; PowerSuite projects cannot be downloaded directly)
DireccionamientoSlave address 1–247Same address range; but Modbus register mapping not 1:1; verify PLC program register addresses

⚠️ Importante: PLC Modbus read/write programs cannot be copied directly. Some status words, fault codes and parameter indexes are changed. Simple start-stop & current reading can be adapted quickly; always verify registers for custom protection settings.

  1. Parameter Menu & Directrices de migración
  2. Core start parameters remain compatible (TCS torque control retained, critical for pumps & fans)

Initial voltage, hora de inicio, detener el tiempo, límite actual, parada suave, protección actual, sobrecarga térmica del motor; parameter definitions are nearly identical.

  1. Menu structure revised:

ATS48: SEF, PRO, DRC, OI, POLICÍA, SORBER

ATS480: New tree menu with revised naming; no identical menu codes

  1. Recommended migration method:

Use the built-in ATS48→ATS480 conversion tool inside SoMove. Upload ATS48 parameter files, auto-convert then download to ATS480.

Avoid manual parameter entry, which easily omits protection settings, relay assignments and analogue calibration.

  1. Factory security update: ATS480 initializes on power-up, requiring language setup and security password; new encryption & firmware security policies added.
  2. Fault codes: Basic faults (PHF, FSU) keep the same meaning; interno & communication fault codes are updated.
  3. Relay Contact Voltage Risk (Error común)

ATS48 relay contacts: Max 400VAC

ATS480 on-board relay contacts: Max 230V AC only

👉 If R1/R2/R3 directly drive 400V contactor coils: Direct wiring is NOT allowed!

Solución: Add 220V intermediate relay isolation before driving 400V contactors.

  1. Delta Connection Compatibility

Both models support motor delta terminal connection (internal delta) to raise rated current; wiring topology is identical. Current conversion formula unchanged: Line In ×1.732 ≈ Delta equivalent current. ATS48D62Q and ATS480D62Y both have 62A main current, equivalent 107A in delta connection; power rating remains the same.

  1. On-site Retrofit Checklist (Follow in sequence)

CL1/CL2 control supply: Confirm voltage is 110–230V AC. If original power is 400V, install a control transformer.

Relay output loop: Check contactor coil voltage. Add intermediate isolation relays for 400V coils.

Cables de alimentación, bypass cables & toma de tierra: Reuse directly; keep tightening torque unchanged.

DI/DO/AQ terminal one-to-one mapping; add PTC temperature wiring if needed.

Comunicación: Convert parameters via SoMove; verify Modbus registers and fault codes in PLC program.

2-wire/3-wire control: ATS480 auto-detects wiring mode; no extra control mode setting required.

Cabinet depth clearance: Ensure cabinet door & cable trunking do not collide with the new unit.

Remote keypad: Old VW3G48101 keypad is incompatible; replace with ATS480 remote keypad kit.

  1. Summary of Incompatibilities
  2. Control supply voltage range (highest risk item)
  3. Max AC voltage rating of relay contacts
  4. Software tool change: PowerSuite → SoMove; parameters must be converted
  5. Mapeo de registros Modbus & fault codes are not fully consistent
  6. Newly added PTC temperature sensing, cyber security and dual-motor configuration functions

Schneider Altistart 48 (ATS48) Lista completa de modelos

Series Note: ATS48 is discontinued (Fecha del último pedido: 31 Dic 2023; service support until 31 Dic 2030). TCS torque-controlled soft starter, optimized for pump/fan water hammer suppression.

Definición de sufijo

q: Three-phase 230~415V AC; supports internal delta terminal connection

Y: Three-phase 208~690V AC; delta connection is NOT permitted

Prefix breakdown: D (baja potencia), do (potencia media), METRO (energía alta)

  1. ATS48 Q Version (230–415V, delta connection supported, most popular for export)
ModeloCorriente nominal (A)400V Standard Duty (Line Connection) kilovatios400V Standard Duty (Conexión delta) kilovatiosDimensions W×H×D mm
ATS48D17Q177.515160×275×190
ATS48D22Q221118.5160×275×190
ATS48D32Q321522160×275×190
ATS48D38Q3818.530160×275×190
ATS48D47Q472245160×275×190
ATS48D62Q623055190×290×235
ATS48D75Q753755190×290×235
ATS48D88Q884575190×290×235
ATS48C11Q1105590190×290×235
ATS48C14Q14075110200×340×265
ATS48C17Q17090132200×340×265
ATS48C21Q210110160320×380×265
ATS48C25Q250132220320×380×265
ATS48C32Q320160250320×380×265
ATS48C41Q410220315400×670×300
ATS48C48Q480250355400×670×300
ATS48C59Q590315450400×670×300
ATS48C66Q660355500400×670×300
ATS48C79Q790400560770×890×315
ATS48M10Q1000500710770×890×315
ATS48M12Q1200630800770×890×315
  1. ATS48 Y Version (208–690V, line connection only, delta connection forbidden)

Model numbering matches the above list exactly; only suffix changes to Y:

ATS48D17Y / D22Y / D32Y / D38Y / D47Y / D62Y / D75Y / D88Y

ATS48C11Y / C14Y / C17Y / C21Y / C25Y / C32Y / C41Y / C48Y / C59Y / C66Y / C79Y

ATS48M10Y / M12Y

Y version covers up to 690V, suitable for mining & overseas 660V systems. Nominal current is identical to the same code Q model; delta terminal current expansion is not supported.

  1. OEM Upgrade Mapping (ATS48 → ATS480, Referencia clave)

Regla: ATS48□□Q / ATS48□□Y → ATS480 same code + suffix Y

Ejemplos:

ATS48D62Q → ATS480D62Y

ATS48C41Q → ATS480C41Y

ATS48M12Y → ATS480M12Y

ATS480 only has Y suffix, voltage 208–690V, fixed control supply 110–230V AC; no Q version, no Q/Y split anymore.

  1. Dimension Group Summary (For cabinet retrofit verification)
  2. D17~D47: 160 × 275 × 190
  3. D62~C11: 190 × 290 × 235
  4. C14~C17: 200 × 340 × 265
  5. C21~C32: 320 × 380 × 265
  6. C41~C66: 400 × 670 × 300
  7. C79~M12: 770 × 890 × 315
  8. ATS48 Exclusive Accessories List

VW3G48101: Local keypad (modelo antiguo, NOT compatible with ATS480)

VW3A4810: Modbus terminal kit (Modbus built-in; no extra card required for most cases)

VW3A4820: Profibus DP communication expansion card

VW3A4830: DeviceNet communication expansion card

VZ3V481 / VZ3V482 / VZ3V483 / VZ3V484 / VZ3V485: Cooling fan spare parts (split by power range)

  1. Key Selection Reminders
  2. Delta connection only available on Q suffix units. Equivalent current ≈ nominal current ×1.732. Restrictions: partial soft-stop functions are limited; dual-motor switching is not supported.
  3. For heavy-duty loads (trituradoras, arranques y paradas frecuentes), select one power rating higher.
  4. Software difference: ATS48 uses PowerSuite; ATS480 uses SoMove. Parameter files cannot be imported directly and must be converted.
  5. Control supply difference: ATS48 Q/Y supports 110–415V AC; ATS480 only accepts 110–230V AC (the biggest retrofit risk).